Electrical and Electronic Controls, Motors, and Wiring

The Electrical and Electronic Controls, Motors, and Wiring domain tests whether you can read a wiring diagram, meter a circuit safely, and diagnose a control fault without guessing. Expect Ohm's law, single and three-phase motors, capacitors, contactors, defrost and pressure controls, motor protection, VFD basics and Canadian Electrical Code wiring rules.

Fundamentals

  • Ohm's law V = I × R; power P = V × I for single phase and P = √3 × V × I × PF for three phase.
  • 24 V Class 2 control circuits are separated from line voltage; a shorted or broken control wire is the most common no-cool call.
  • In parallel, loads see the same voltage and opening one branch does not stop the others; in series, one open stops everything.

Motors and starting

  • PSC motors use a run capacitor in series with the start winding; a failed capacitor gives low torque and a hot motor. Discharge and test microfarads.
  • Three-phase rotation reverses by swapping any two leads; verify rotation on scroll and screw compressors before running, because a scroll run backwards can be destroyed in seconds.
  • Internal overloads sit in the winding; external overloads and contactor heaters protect the circuit.
  • Insulation resistance to ground below about 1 megohm suggests moisture or winding breakdown - test with a megohmmeter, never a common ohmmeter.

Worked example

A 5 kW, 240 V single-phase heat strip: I = 5000 ÷ 240 = 20.8 A. A continuous load needs 125%, or 26 A, so a 30 A breaker and conductors rated at least that. The nameplate maximum overcurrent protection is the upper limit; never size above it.

Controls

Low-pressure controls for pump-down, high-pressure lockouts, defrost timers, and electronic boards with thermistor sensors. Check the sensor resistance against a known thermometer before condemning a controller.

Traps

  • Measuring resistance in a live circuit.
  • Not discharging a capacitor before testing microfarads.
  • Reading FLA where the nameplate gives MCA or MOP - those are already sized values.
  • Treating a tripped breaker as the fault instead of a symptom.