Refrigeration Operator B flashcards
Refrigeration Operator B · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Compressor function
- Raises refrigerant pressure and temperature, moving vapour from the low-side evaporator pressure to the high-side condensing pressure. It is the primary energy consumer in a vapour-compression cycle.
- Condenser heat rejection
- Rejects heat absorbed in the evaporator plus compressor work. Q_cond = Q_evap + W_comp. Air-cooled condensers typically reject 1.2 to 1.3 times evaporator load.
- Evaporator superheat
- Difference between suction line temperature and saturated suction temperature at the same pressure. Thermostatic expansion valves maintain stable superheat, commonly 5 to 10 K at the evaporator outlet.
- Liquid subcooling
- Difference between saturated condensing temperature and liquid line temperature. Subcooling ensures solid liquid reaches the metering device and prevents flash gas at the valve inlet.
- Oil return requirements
- Suction line velocity must be high enough to carry oil back to the compressor, typically 4 to 7 m/s in horizontal runs. Oil separators and traps assist return in low-temperature systems.
- Scroll compressor
- Uses two interleaved spiral scrolls; one orbits while the other stays fixed, trapping and compressing gas pockets. Common in mid-range packaged and split air-conditioning systems with few moving parts.
- Pressure-enthalpy diagram
- Plots refrigerant pressure against enthalpy. The four processes are compression, condensation at constant pressure, isenthalpic expansion, and evaporation at constant pressure; used to calculate COP and capacity.
- Ammonia refrigerant properties
- R-717 has zero ODP and GWP under 1. It is toxic and flammable at high concentration, detectable by odour near 5 ppm, and attacks copper and brass, so steel piping is used.
- R-410A characteristics
- Near-azeotropic blend of R-32 and R-125 at 50/50. Operates at higher pressures than R-22, requires POE oil, and must be charged as a liquid to avoid fractionation.
- Refrigerant glide
- Temperature difference between bubble point and dew point at constant pressure in a zeotropic blend. Glide affects superheat settings and requires liquid charging and careful servicing.
- Coefficient of performance
- COP = Q_evap / W_comp, the ratio of cooling delivered to work input. COP increases with higher evaporating temperature and lower condensing temperature.
- Montreal Protocol and Kigali
- The Montreal Protocol phased out CFCs and HCFCs such as R-12 and R-22. The Kigali Amendment phases down HFCs; Canadian regulations restrict high-GWP refrigerants and require leak reporting.
- Refrigerant leak testing
- Use electronic detectors, UV dye, soap bubbles, or dry nitrogen pressure testing. Never use oxygen or compressed air to pressure-test because of fire and explosion risk.
- High-pressure cut-out
- Safety switch that stops the compressor when discharge pressure exceeds a set limit below design pressure. It usually requires manual reset after tripping to force investigation.
- Low-pressure cut-out
- Switch that stops the compressor on low suction pressure, protecting against loss of charge or freezing. May be automatic reset for normal cycling or manual reset for safety trips.
- Oil pressure safety switch
- Trips the compressor if net oil pressure (oil pump pressure minus suction pressure) does not build within a set time, typically 30 to 120 seconds after start.
- Relief valve piping
- Relief devices protect against overpressure. Discharge must be piped to a safe location; ammonia relief valves vent to atmosphere through a vent line sized to prevent back pressure.
- Ammonia room safety
- Machinery rooms require ammonia detectors, mechanical ventilation, and emergency ventilation interlocked with detection. Alarms and evacuation procedures must be posted and tested.
- Pump-down cycle
- The compressor runs until a low-pressure switch evacuates the evaporator, then stops. It prevents liquid migration to the compressor during off cycles and is common in larger systems.
- Lockout tagout
- Energy-isolation procedure before servicing: disconnect power, lock the disconnect, tag it, and verify absence of voltage. Required before electrical or mechanical work on equipment.
- Shift log readings
- Record suction and discharge pressures and temperatures, condensing and evaporating temperatures, superheat, subcooling, oil pressure, motor current, and sight glass condition each shift.
- Sight glass indicators
- Bubbles indicate flash gas or low charge; a colour change in the moisture indicator signals moisture, requiring drier replacement. Check during steady operation, not right after start.
- Condenser cleaning
- Dirty or scaled condenser tubes reduce heat transfer and raise condensing pressure, increasing power use. Water-cooled condensers need periodic tube cleaning and cooling tower water treatment.
- High discharge pressure causes
- Common causes are a dirty condenser, overcharge, non-condensable gases, high ambient temperature, or restricted airflow. Investigate in that order before adding or removing charge.
- Low suction pressure causes
- Common causes are a restricted metering device, low refrigerant charge, blocked or frosted evaporator, or restricted suction line. Check superheat and sight glass to narrow the cause.
- Preventive maintenance schedule
- Includes electrical connection checks, condenser cleaning, charge verification, oil and filter changes, safety control testing, relief device inspection, and running-hour records for overhauls.
- TSSA and Operating Engineers
- The Technical Standards and Safety Act, 2000 governs pressure equipment in Ontario. TSSA administers O. Reg. 219/01, which sets plant classification and the required operating engineer class.
- Plant log book
- Record of operating readings, maintenance, tests, and unusual events. Entries must be legible, dated, and signed by the operator, and retained as required by regulation.
- Certificate of qualification
- Issued by TSSA and required to operate a plant of a given class. It must be valid and current, and the operator may only operate plants within the certified class.
- CSA B52 scope
- Mechanical Refrigeration Code covering design, installation, and operation of refrigeration systems in Canada, including safety devices, machinery rooms, and refrigerant limits.
- Refrigerant record keeping
- Federal halocarbon regulations and Ontario rules require tracking refrigerant purchases, use, leaks, and recovery, with certified technicians for certain handling and leak reporting above thresholds.
- Bypassing safety devices
- Never bypass a safety control without written authorization and compensating controls. The operator must report defects promptly and restore protection before returning equipment to service.