SCO Plumbing & Gas flashcards
SCO Plumbing & Gas · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Fixture unit (FU)
- A unit that expresses the drainage load of a fixture relative to a fixed standard, allowing pipe sizes to be summed and read from a sizing table.
- Minimum drain slope
- The smallest fall permitted on a drain, typically 1 in 50 for small pipe and 1 in 100 for larger pipe, set to keep solids moving.
- Trap seal depth
- The vertical water seal in a fixture trap, usually between 50 mm and 100 mm, which blocks sewer gas from entering the building.
- Vent size rule
- A vent must be at least half the diameter of the drain it serves and never smaller than 32 mm, so air can follow the discharge.
- Air gap
- The highest form of backflow protection, an unobstructed vertical distance between a supply outlet and the flood level of the receiving vessel.
- Reduced pressure zone
- A testable backflow assembly with two check valves and a relief valve, used for high-hazard connections where backpressure and backsiphonage are both possible.
- Residual pressure
- The pressure remaining at the most remote fixture while the system is flowing, which must meet the minimum for the fixture type.
- Water supply pressure test
- A test of the supply pipework at 1.5 times working pressure or at least 1000 kPa, held for two hours with no loss.
- Drainage air test
- A test of the drainage system using air at about 35 to 50 kPa, held for the period set by the code, used where a water test is impractical.
- Developed length
- The total equivalent pipe length of a run, including the actual pipe plus the equivalent lengths of fittings and valves.
- Wet vent
- A single pipe that serves as both the drain for one fixture and the vent for another, permitted only under the conditions set by the code.
- Cleanout requirement
- A cleanout is required at the base of each stack, at changes of direction over 45 degrees, and at intervals on long horizontal runs.
- Backwater valve
- A valve on the building drain that closes automatically to prevent sewage from the street sewer from flowing back into the building.
- Grease interceptor
- A device that slows kitchen waste flow so grease floats and is retained, sized by fixture units and retention time and pumped out periodically.
- Thermal expansion of pipe
- The increase in pipe length caused by temperature rise, calculated from the coefficient of expansion, the length, and the temperature change.
- Water hammer arrestor
- A device with a trapped air or gas cushion installed near a quick-closing valve to absorb the pressure surge when flow stops.
- Natural gas heat content
- The energy released by burning a unit volume of natural gas, approximately 37 to 38 MJ per cubic metre at standard conditions.
- Propane heat content
- The energy released by burning a unit volume of propane vapour, approximately 93 MJ per cubic metre, about two and a half times that of natural gas.
- Specific gravity of gas
- The ratio of a gas density to air density; natural gas is about 0.60 and propane vapour about 1.53, which affects where leaks collect.
- Longest-run gas sizing
- A sizing method that measures the developed length from the meter to the most remote appliance, sums the load, and reads the capacity table.
- Gas pressure drop allowance
- The permitted loss of pressure between the meter and the appliance, typically 0.125 kPa for low-pressure systems, used to select pipe size.
- Appliance regulator
- A device that reduces the supply pressure to the appliance manifold pressure and must be vented to a safe location.
- Combustion air requirement
- The air needed for complete burning plus dilution, roughly 1 cubic metre per megajoule of input, supplied through permanent openings.
- Flue termination height
- The minimum height above the roof and the clearance from windows and air intakes that a flue must meet to carry products away safely.
- Gas leak test pressure
- The pressure used to prove gas pipework tight, typically 1.5 times maximum operating pressure but not less than 7 kPa for low-pressure systems.
- Gas detector placement
- Methane detectors are mounted high because the gas is lighter than air, while propane detectors are mounted low because the vapour is heavier.
- Flame failure device
- A safety control that shuts off the gas supply if the flame is lost, using a thermocouple or flame rectification sensor.
- Carbon monoxide risk
- A poisonous gas produced by incomplete combustion, controlled by correct appliance adjustment, adequate air, and a working flue.
- Gas pipe bonding
- The connection of the gas piping to the electrical earth with a conductor sized by the electrical code, to prevent a difference in potential.
- Drip leg
- A capped vertical section at the appliance connection that collects condensate and debris before it reaches the controls.
- Appliance connector limits
- An approved flexible connector must not pass through a wall, floor, or ceiling, must not be concealed, and is limited in length.
- Garage ignition height
- In a residential garage, a gas appliance ignition source must be at least 450 mm above the floor because petrol vapour is heavier than air.