CO Fire Sprinkler flashcards
CO Fire Sprinkler · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NFPA 13 scope
- The standard for design and installation of automatic fire sprinkler systems in commercial, industrial, and institutional occupancies, covering hazard classification, hydraulic design, and acceptance testing.
- Light hazard occupancy
- Occupancy with low combustibility and low quantity of combustibles, such as offices, churches, and schools. Minimum design density is 0.10 gpm/ft² over 1,500 ft².
- Ordinary Hazard Group 1
- Occupancy with moderate combustibles and moderate stockpiles, such as parking garages and restaurants. Design density begins at 0.15 gpm/ft² over 1,500 ft².
- Ordinary Hazard Group 2
- Occupancy with higher combustibility or taller stockpiles, such as mercantile and machine shops. Design density begins at 0.20 gpm/ft² over 1,500 ft².
- Sprinkler K-factor
- Discharge coefficient relating flow to pressure by Q = K√P. A K=5.6 sprinkler flows about 21.7 gpm at 15 psi; higher K-factors deliver more flow at the same pressure.
- Minimum end sprinkler pressure
- The most remote sprinkler must have at least 7 psi residual pressure, and pressure must be high enough to produce the required density for the selected K-factor.
- Design area
- The remote floor area over which sprinkler density is calculated. It is 1,500 ft² for most light and ordinary hazard designs and is adjusted by density/area curves.
- Dry-pipe system design area
- Dry-pipe systems typically require the calculated design area to be increased by 30 percent to compensate for the delay while air is expelled and water reaches the sprinklers.
- Maximum sprinkler spacing
- Light hazard allows up to 15 ft between sprinklers and 15 ft between branch lines, with a maximum coverage of 225 ft² per sprinkler.
- Ordinary hazard coverage limit
- Maximum coverage area per sprinkler for ordinary hazard is 130 ft², with spacing generally not exceeding 15 ft on branch lines or between lines.
- Hydrostatic test requirement
- Sprinkler piping is tested at 200 psi for two hours, or at 50 psi above the maximum working pressure if that value exceeds 200 psi.
- Main drain flow test
- A test that flows water through the main drain to verify the water supply can deliver the required flow and pressure, confirming the supply curve used in design.
- Inspector's test connection
- A valve and orifice at the end of the most remote branch line that simulates a single sprinkler flow, used to verify alarm activation and water delivery.
- Wet-pipe system
- A system with water under pressure in the piping at all times. It is the most common and fastest-responding type, but cannot be used where piping may freeze.
- Dry-pipe system
- A system with pressurized air or nitrogen in the piping and water held back by a dry-pipe valve. It is used in unheated spaces and responds more slowly than wet systems.
- Preaction system
- A dry system with a detection system that must operate before the deluge or preaction valve releases water, protecting sensitive areas from accidental discharge.
- Deluge system
- A system with open sprinklers and a deluge valve that releases water to all sprinklers simultaneously when detection activates, used for high-hazard areas.
- Pipe schedule design
- A prescriptive method sizing pipe by the number of sprinklers served, limited to 160 or fewer sprinklers per NFPA 13. Larger systems require hydraulic calculations.
- Hydraulic calculation
- A calculation of pressure loss through piping, fittings, and sprinklers using friction loss formulas to confirm the supply can deliver the required density at the most remote sprinkler.
- Hazen-Williams formula
- A friction loss formula, P = 4.52 Q^1.85 / (C^1.85 d^4.87), used to calculate pressure loss in sprinkler piping where Q is flow, C is the roughness coefficient, and d is diameter.
- C-factor for steel pipe
- The Hazen-Williams roughness coefficient for new black steel pipe is 120; older or corroded pipe may be assigned a lower C-factor, increasing calculated friction loss.
- Quick-response sprinkler
- A sprinkler with a fast-responding thermal element that activates sooner than standard-response types, allowing reduced design areas in some occupancies under NFPA 13.
- Sprinkler temperature rating
- The activation temperature of the thermal element. Common ratings are 135°F, 155°F, 175°F, and 200°F; higher ratings are used near heat sources.
- Deflector distance
- The deflector must be positioned relative to the ceiling per listing, typically 1 to 12 inches below noncombustible ceilings, to form the required spray pattern.
- Obstruction rule
- Sprinklers must be positioned so construction or obstructions do not block spray. Obstructions wider than specified limits require additional sprinklers or shielding.
- Sprinkler in closets
- Small closets and concealed spaces may be exempt from sprinkler protection when combustibility and size limits in NFPA 13 are met, such as small noncombustible closets.
- Anti-freeze system
- A wet-pipe system filled with an antifreeze solution in areas subject to freezing. Solution concentration must be maintained and tested to keep the freeze point adequate.
- Fire department connection
- A connection allowing the fire department to pump supplemental water into the sprinkler system, typically required and sized based on the system demand.
- Water flow alarm
- A device that activates when water flows in the system, typically a vane or pressure switch, alerting occupants and the fire department to sprinkler operation.
- Riser and main drain
- The riser is the vertical supply pipe with control valves and alarms; the main drain valve allows flow testing to verify supply and detect obstructions.
- Acceptance test sequence
- After installation: hydrostatic test, flushing, alarm and valve testing, main drain flow test, and inspector's test connection flow to confirm the system meets design.
- Design density vs. area
- As required density increases on the density/area curve, the remote design area decreases, reflecting that higher-density designs address more severe hazards with less area.