CT Fire Sprinkler study materials
CT Fire Sprinkler study resources

CT Fire Sprinkler flashcards

CT Fire Sprinkler · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Design density
The amount of water, in gallons per minute per square foot, applied over the hydraulically most remote area. It is selected from the hazard classification curve and drives pipe sizing.
Remote area
The portion of the sprinkler system that is hydraulically most demanding. Its size depends on hazard, sprinkler type, and ceiling height, and it may be reduced under specific conditions.
Hose stream allowance
Water flow reserved for fire department hose use, added to the sprinkler demand at the base of the riser. It varies with hazard classification and supply adequacy.
Light hazard
An occupancy classification for low-combustibility contents and low fire load, such as offices, schools, and churches. It typically permits larger sprinkler coverage and lower design density.
Ordinary hazard Group 1
A hazard classification for occupancies with moderate combustibility and stockpiles below a stated height, such as parking garages and restaurants. It requires greater density than light hazard.
Ordinary hazard Group 2
A hazard classification for occupancies with higher combustibility or taller stockpiles, such as mercantile and manufacturing. It requires higher density and smaller sprinkler coverage than Group 1.
Extra hazard
The most severe hazard classification, covering occupancies with high combustibility, flammable liquids, or heavy dust. It uses the highest design densities and the largest remote areas.
Sprinkler temperature rating
The nominal activation temperature of a sprinkler's heat-responsive element. Ratings are grouped into ordinary, intermediate, and high ranges and must exceed expected ceiling temperature.
Ordinary temperature rating
A sprinkler rating range of roughly 135 to 170 degrees Fahrenheit, used in most occupied spaces with normal ceiling temperatures. It is the default for many light and ordinary hazard areas.
Intermediate temperature rating
A sprinkler rating range of roughly 175 to 225 degrees Fahrenheit, used where ceiling temperatures are elevated, such as near skylights, heaters, or attic spaces.
High temperature rating
A sprinkler rating range of roughly 250 to 300 degrees Fahrenheit, used in high-heat environments such as near furnaces or in certain industrial processes.
Quick-response sprinkler
A sprinkler with a fast-acting heat-responsive element, often a glass bulb. In qualifying wet systems it can permit a reduced design area in light-hazard occupancies.
Standard-response sprinkler
A sprinkler with a slower heat-responsive element, typically a fusible link. It is used where quick-response reduction is not permitted or where the hazard requires a robust spray.
Extended coverage sprinkler
A sprinkler listed for coverage areas larger than standard, allowing wider spacing. Its use is limited by listing, hazard, and ceiling height, and it requires higher minimum pressure.
Sidewall sprinkler
A sprinkler mounted on a wall or side of a soffit that discharges outward across the protected area. Spacing and coverage rules differ from pendant and upright sprinklers.
Pendent sprinkler
A sprinkler that hangs below the branch line and discharges downward, typically with a deflector that spreads water over the floor. It is common in finished ceilings.
Upright sprinkler
A sprinkler mounted above the branch line with the deflector facing up, discharging upward against the ceiling. It is common in exposed-structure and warehouse settings.
Wet-pipe system
A system in which the piping is filled with pressurized water at all times, so a sprinkler opens and water discharges immediately. It is the most common and simplest type.
Dry-pipe system
A system in which the piping holds pressurized air or nitrogen, and water is admitted when a sprinkler opens and pressure drops. It requires an increased remote area.
Preaction system
A dry-pipe arrangement in which a detection system must operate before water enters the piping, reducing accidental discharge risk. It is used where water damage is a concern.
Deluge system
A system with open sprinklers and a deluge valve that releases water to all sprinklers at once upon detection. It is used for high-hazard or special protection applications.
Wet alarm valve
A valve in a wet-pipe system that opens on water flow and activates the alarm. It includes a check valve and connections for gauges, drain, and alarm devices.
Dry-pipe valve
A valve that holds back water until air pressure in the system drops, then admits water. It includes a clapper, priming water, and alarm connections.
Flow switch
A device that detects water movement in the piping and sends an alarm signal. It is installed on the riser or branch and tested during acceptance and periodic inspections.
Main drain test
A test that opens the main drain to measure static and residual pressure at the riser, confirming supply adequacy and valve condition. Results are compared to prior readings.
Hydrostatic test
A pressure test of the piping at a specified pressure above working pressure for a specified duration, performed before the system is placed in service to verify integrity.
Hydraulic calculation
A calculation of pressure loss through pipe, fittings, and devices to determine required supply pressure and flow. It confirms the system meets design density at the remote area.
Pipe schedule method
A prescriptive sizing method using tables that relate pipe diameter to the number of sprinklers served. It is limited to small, light-hazard systems within stated limits.
Sprinkler coverage area
The floor area protected by one sprinkler, determined by spacing along and between branch lines. Maximum coverage depends on hazard and sprinkler listing.
Branch-line spacing
The maximum distance between sprinklers along a branch line, set by hazard and sprinkler type. The distance from the last sprinkler to the branch end is also limited.
Deflector distance
The required distance between a sprinkler deflector and the ceiling or obstruction, set by listing and standard. It ensures proper spray pattern development.
Water supply flow test
A test measuring static and residual pressure at known flow to characterize the available water supply. Results are plotted and compared to the system demand.