Pancyprian Electrical Engineering III (Practical) study materials
Pancyprian Electrical Engineering III (Practical) study resources

Pancyprian Electrical Engineering III (Practical) flashcards

Pancyprian Electrical Engineering III (Practical) · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Let-go threshold
The current at which a person can still release a gripped conductor, roughly 10 mA at 50 Hz; higher currents cause muscle contraction and prevent release.
Hierarchy of control
Order of risk reduction: eliminate the hazard, substitute, use engineering controls such as isolation, then administrative controls, with PPE as the last resort.
Safe isolation procedure
Identify the circuit, isolate, lock off and tag, prove the tester on a known source, prove dead at the point of work, then re-prove the tester.
GS38 voltage indicator
An approved voltage tester with fused or current-limited probes, finger guards and exposed tips no longer than 4 mm, proved before and after use.
Ohm's law
The relationship V = I × R, where voltage in volts equals current in amperes multiplied by resistance in ohms, valid for resistive circuits at constant temperature.
Power factor
The ratio of true power in watts to apparent power in volt-amperes, equal to cos φ, where φ is the phase angle between voltage and current.
Parallel resistance
The reciprocal of the total resistance equals the sum of the reciprocals of the branch resistances, so the total is always less than the smallest branch.
Design current Ib
The current the circuit is intended to carry in normal use, calculated from the load, and used to select the protective device rating In.
Voltage drop formula
For a single-phase circuit, Vd = (mV/A/m × Ib × L) / 1000, where mV/A/m is the tabulated value, Ib the design current and L the length in metres.
Adiabatic equation
The minimum protective conductor size S = √(I²t) / k, where I²t is the fault energy let-through and k depends on conductor material and insulation.
BS 7671
The IET Wiring Regulations, the technical standard for the design, installation and verification of electrical installations, currently the 18th Edition with Amendment 2.
Minor Electrical Installation Works Certificate
A certificate used for small alterations or additions to an existing installation that do not extend the existing certification, recording the work and test results.
Competent person
A person with sufficient technical knowledge, experience and skill to prevent danger and injury from the electrical work they undertake.
Safe zone
A permitted concealed cable route within 150 mm of a ceiling or corner, or aligned vertically or horizontally with an accessory, where cables are unlikely to be penetrated.
Cable grouping factor
A correction factor Cg applied when cables are bunched or enclosed, reducing the current-carrying capacity because heat cannot dissipate as freely.
MCB Type B
A miniature circuit breaker that trips between 3 and 5 times its rated current, suitable for resistive loads with low inrush current.
RCD additional protection
A 30 mA residual current device that provides additional protection against electric shock but does not replace basic or fault protection.
Breaking capacity Icn
The maximum prospective short-circuit current a protective device can safely interrupt without damage, which must not be less than the fault level at its position.
TN-C-S system
An earthing arrangement where the neutral and protective earth are combined in the supply and separated at the origin, also known as protective multiple earthing.
Main protective bonding
The connection of extraneous conductive parts such as gas and water pipes to the main earthing terminal, using a conductor of at least 10 mm².
Earth fault loop impedance
The total impedance of the path taken by fault current from the origin through the live conductor, the fault and back via the protective conductor and earth.
Insulation resistance test
A dead test at 500 V DC between live conductors and earth, with a minimum acceptable value of 1 MΩ for a 230 V circuit.
Ring final circuit test
End-to-end resistance measurements of line, neutral and CPC, where the CPC reading is about 1.67 times the line reading for 2.5/1.5 mm² cable.
RCD trip time
At rated residual current the device must trip within 300 ms; at five times rated current within 40 ms for a 30 mA device.
Earth fault loop impedance test
A live test measuring Zs at the furthest point of a circuit, which must not exceed the maximum value for the protective device to disconnect within the required time.
N-E fault
A connection between neutral and earth, often caused by moisture or damage, which causes an RCD to trip because current bypasses the sensing coil.
Thermal imaging
A diagnostic technique using an infrared camera to detect hot terminals, overloaded conductors and loose connections before they fail or cause fire.
Split-load consumer unit
A board with circuits divided so that socket outlets are protected by a 30 mA RCD while lighting and other circuits remain on a separate section.
Main switch
The device at the origin of an installation that isolates both line and neutral, allowing the consumer unit to be made dead for maintenance.
Overload relay
A protective device in a motor circuit that detects sustained overcurrent and trips the contactor, protecting the motor from overheating.
Terminal torque
The tightening force specified by the manufacturer for a terminal screw, which ensures a low-resistance connection and prevents loosening under thermal cycling.
Cable gland
A fitting that secures a cable at its entry to an enclosure, provides strain relief and maintains the ingress protection rating of the enclosure.