Pancyprian Electrical Engineering III (Practical) study materials
Pancyprian Electrical Engineering III (Practical) study resources

Pancyprian Electrical Engineering III (Practical) practice questions

One question at a time. Build your Pancyprian Electrical Engineering III (Practical) understanding.

First 50 of 200 questions. Each one lists the choices, the correct answer, and an explanation. The checker at the top of this page saves progress in this browser when it is available.

Continue in the practice tool above to load more questions, 50 at a time.

Question 1Health and Safety, Electrical Safety and Safe Isolation

Under the Cyprus safety requirements for work on electrical installations, which document must be completed and signed before a circuit is isolated and proved dead for maintenance?

  1. A permit to work with a lock-off record Correct answer.
  2. A customer satisfaction survey
  3. A material requisition form
  4. A delivery note from the cable supplier

Explanation

Formal isolation for maintenance is controlled by a permit to work that records the circuit, the isolation points, the lock-off, the proving dead and the person in charge. It creates an auditable chain of responsibility so the circuit cannot be re-energised while someone is working on it.

Question 2Health and Safety, Electrical Safety and Safe Isolation

What is the primary purpose of a lock and a personal danger tag applied to an isolation device during maintenance?

  1. To indicate the voltage rating of the switchgear
  2. To record the date of the next periodic inspection
  3. To prevent unauthorised re-energisation of the isolated circuit Correct answer.
  4. To show which electrician installed the circuit originally

Explanation

A lock physically prevents operation of the isolating device and the tag warns others that the circuit is under the control of a named person. Together they stop a third party from closing the switch while work is in progress. Only the person who applied the lock should remove it.

Question 3Health and Safety, Electrical Safety and Safe Isolation

An approved voltage indicator used for proving dead on a low-voltage installation must be proved immediately before and after the test. What is the purpose of the second proving step?

  1. To measure the earth fault loop impedance
  2. To confirm the indicator still functions correctly after the test Correct answer.
  3. To verify the prospective short-circuit current
  4. To check the polarity of the supply

Explanation

Proving the indicator on a known live source before and after the test confirms it was working when the circuit was tested. If the indicator failed during the test, the second proving step exposes that failure so the dead result cannot be trusted.

Question 4Health and Safety, Electrical Safety and Safe Isolation

Which item of personal protective equipment is specifically required when racking out or operating live low-voltage switchgear where arc flash risk exists?

  1. Steel-capped boots only
  2. A high-visibility vest
  3. Anti-static wrist strap
  4. Arc-rated face protection and flame-retardant clothing Correct answer.

Explanation

Operating switchgear can initiate an arc flash, so arc-rated face protection and flame-retardant clothing are needed to limit burn injury. A high-visibility vest and ordinary boots give no thermal protection against an arc.

Question 5Health and Safety, Electrical Safety and Safe Isolation

Before starting work in a low-voltage distribution board, an electrician finds the main switch locked off but no danger tag. What is the correct action?

  1. Ask a colleague to stand by the switch instead of tagging
  2. Remove the lock to check the supply is off
  3. Proceed because the lock already prevents re-energisation
  4. Attach a personal danger tag and confirm the isolation before starting Correct answer.

Explanation

The lock prevents operation but the tag identifies who controls the isolation and warns others, so a personal tag must be added and the isolation confirmed. Working under an unidentified lock risks another person removing it or not knowing work is in progress.

Question 6Health and Safety, Electrical Safety and Safe Isolation

A circuit is isolated at the distribution board and proved dead at the socket outlet. Why must the earthing conductor at the point of work also be proved dead before touching conductors?

  1. To measure the insulation resistance of the circuit
  2. To ensure no parallel path or back-feed is energising the earth conductor Correct answer.
  3. To check the rating of the protective device
  4. To confirm the earthing system type is TN-C-S

Explanation

Proving only line and neutral dead can miss a back-feed or a parallel earth path that leaves the earthing conductor live. Confirming the earth is dead protects the worker from a shock through the protective conductor.

Question 7Health and Safety, Electrical Safety and Safe Isolation

An electrician must replace a faulty luminaire on a lighting circuit. The switch for the circuit is a two-way arrangement controlled from two positions. Which isolation point gives reliable isolation?

  1. Either of the two-way switches
  2. The circuit's protective device at the distribution board Correct answer.
  3. The nearest two-way switch
  4. The lamp holder itself

Explanation

Two-way switching means either switch position can leave the luminaire live, so neither switch is a safe isolation point. The circuit must be isolated at the protective device in the distribution board and locked off.

Question 8Health and Safety, Electrical Safety and Safe Isolation

When carrying out safe isolation on a three-phase motor circuit, which sequence of steps is correct?

  1. Isolate, lock off, prove dead, then start work Correct answer.
  2. Isolate, prove dead, lock off, then start work
  3. Prove dead, isolate, lock off, then start work
  4. Lock off, prove dead, isolate, then start work

Explanation

The circuit must be isolated first, then locked off and tagged to prevent re-energisation, and only then proved dead at the point of work. Proving dead before isolation would test a live circuit and could expose the worker to danger.

Question 9Health and Safety, Electrical Safety and Safe Isolation

Which test instrument is appropriate for confirming that a low-voltage circuit is dead before work begins?

  1. A multimeter set to continuity
  2. A voltage indicator approved for the nominal voltage Correct answer.
  3. An insulation resistance tester
  4. A clamp meter set to current

Explanation

An approved voltage indicator rated for the nominal voltage is the correct instrument for proving dead because it presents a known load and clearly indicates the presence of voltage. Insulation testers, continuity ranges and clamp meters are not designed for this safety-critical check.

Question 10Health and Safety, Electrical Safety and Safe Isolation

During a risk assessment for work in a plant room, a notice states that the supply is TT with a high earth loop impedance. Which additional hazard should the assessment highlight for portable tools?

  1. Reduced risk because the earth electrode limits touch voltage
  2. No effect because TT systems are always safer
  3. Increased risk of arc flash only
  4. Increased risk of electric shock because fault current may be too low to trip the device quickly Correct answer.

Explanation

In a TT system the fault path is through the earth electrode, so a high loop impedance can limit fault current and delay or prevent automatic disconnection. The assessment should therefore require additional protection such as RCDs for portable tools.

Question 11Health and Safety, Electrical Safety and Safe Isolation

An apprentice is asked to work inside a metal enclosure containing live busbars. Which control best reduces the risk of accidental contact during the task?

  1. Wearing cotton gloves
  2. Asking a colleague to watch from a distance
  3. Working quickly to minimise exposure time
  4. Using insulated tools and temporary insulating barriers Correct answer.

Explanation

Insulated tools and temporary insulating barriers physically separate the worker from live parts and are recognised controls for work near live busbars. Speed, cotton gloves and a distant observer do not prevent contact.

Question 12Health and Safety, Electrical Safety and Safe Isolation

A residual current device protecting a socket circuit is rated at 30 mA. What does this rating represent?

  1. The residual operating current at which the device is intended to trip Correct answer.
  2. The prospective short-circuit current at the socket
  3. The maximum load current the circuit may carry
  4. The insulation resistance value required for the circuit

Explanation

The 30 mA figure is the rated residual operating current, the earth leakage at which the RCD is designed to operate and provide additional protection against electric shock. It is not a load rating or a fault-current rating.

Question 13Health and Safety, Electrical Safety and Safe Isolation

Before energising a newly installed circuit, which check confirms that the protective conductor is connected to the earthing terminal of each accessory?

  1. A continuity test of the protective conductors Correct answer.
  2. An insulation resistance test between live conductors
  3. A polarity check at the origin
  4. A functional test of the RCD

Explanation

Continuity testing of the protective conductors confirms that each accessory's earth terminal is connected back to the main earthing terminal. Polarity, insulation resistance and RCD tests check different characteristics and would not reveal a missing earth connection.

Question 14Health and Safety, Electrical Safety and Safe Isolation

An electrician is working alone in a remote location and needs to isolate a circuit. Which practice is most appropriate for emergency rescue arrangements?

  1. Work without isolation to reduce time on site
  2. Rely on a mobile phone as the only rescue provision
  3. Inform a responsible person of the location and expected duration and carry a means of summoning help Correct answer.
  4. Leave the distribution board unlocked so others can restore power

Explanation

Lone workers must ensure someone knows where they are and when they are expected to finish, and must be able to summon help if an incident occurs. This is a basic element of the emergency arrangements required by the risk assessment.

Question 15Health and Safety, Electrical Safety and Safe Isolation

Which document should be consulted to confirm the isolation points and the identity of circuits before starting work on an unfamiliar distribution board?

  1. The manufacturer's brochure for the switchgear
  2. The building's fire certificate
  3. The current installation schedule and labelling at the board Correct answer.
  4. The electricity bill for the premises

Explanation

The installation schedule and the labels at the board identify each circuit and its protective device so the correct isolation point can be selected. Relying on guesswork or unrelated documents risks isolating the wrong circuit.

Question 16Health and Safety, Electrical Safety and Safe Isolation

During maintenance, a colleague removes the lock you placed on the main switch and re-energises the circuit. Which control would most effectively have prevented this?

  1. A warning sign posted at the site entrance
  2. A single lock with the key left in the switch
  3. A verbal instruction at the morning briefing
  4. A multi-lock hasp with a personal lock for each worker Correct answer.

Explanation

A multi-lock hasp allows each worker to fit a personal lock, so the circuit cannot be re-energised until every lock is removed. A single lock with the key left in place offers no protection, and signs or briefings do not physically prevent operation.

Question 17Health and Safety, Electrical Safety and Safe Isolation

A portable hand lamp is required inside a metal tank. Which supply arrangement is most appropriate?

  1. A 110 V centre-tapped earth lamp supplied from a safety isolating transformer Correct answer.
  2. A 230 V lamp with an earthed metal guard
  3. A battery torch taped to the tank wall
  4. A 230 V lamp with an extension lead

Explanation

A 110 V centre-tapped earth supply from a safety isolating transformer limits the voltage to earth to 55 V and is the standard reduced-voltage arrangement for confined and wet locations. A 230 V lamp presents a much higher shock risk inside a metal tank.

Question 18Health and Safety, Electrical Safety and Safe Isolation

An electrician is asked to work on a live 400 V distribution board because production cannot stop. Which condition must be satisfied before such work is permitted?

  1. The work takes less than thirty minutes
  2. The electrician has more than five years of experience
  3. The work is justified as unreasonable to de-energise and suitable precautions are in place with authorisation Correct answer.
  4. The board is labelled with a danger sign

Explanation

Live work is only permitted where de-energising is unreasonable and suitable precautions, including authorisation and appropriate equipment, are in place. Experience, signage or a short duration alone do not justify live work.

Question 19Health and Safety, Electrical Safety and Safe Isolation

Which combination correctly describes the protective measures for a circuit supplying equipment in a wet area where the risk assessment requires additional protection?

  1. A voltage-operated earth leakage device only
  2. A 100 mA RCD only
  3. An MCB with a higher breaking capacity only
  4. An RCD with a rated residual current not exceeding 30 mA and supplementary bonding where required Correct answer.

Explanation

Additional protection in wet areas is provided by a 30 mA RCD, with supplementary equipotential bonding where the installation conditions require it. Higher-rated RCDs, overcurrent devices alone or voltage-operated devices do not provide the required additional shock protection.

Question 20Health and Safety, Electrical Safety and Safe Isolation

A maintenance team must prove a circuit dead, but the approved voltage indicator fails its self-test. What is the correct course of action?

  1. Use the indicator anyway because the circuit is believed to be isolated
  2. Proceed after checking the circuit with a non-contact voltage pen only
  3. Obtain a second approved indicator and repeat the proving procedure Correct answer.
  4. Use a multimeter as a substitute and proceed

Explanation

A failed self-test means the indicator cannot be trusted, so a second approved indicator must be obtained and the full prove-test-prove procedure repeated. Substituting unapproved instruments or relying on a non-contact pen does not give a reliable dead result.

Question 21Health and Safety, Electrical Safety and Safe Isolation

In a TT installation, a circuit protected only by an MCB has a measured earth fault loop impedance too high to operate the device within the required disconnection time. Which remedy best restores automatic disconnection?

  1. Lengthen the circuit to lower the impedance
  2. Increase the rating of the MCB
  3. Reduce the size of the earthing conductor
  4. Install an RCD to provide the required disconnection Correct answer.

Explanation

When the loop impedance is too high for the overcurrent device to disconnect within the required time, an RCD can provide automatic disconnection because it responds to residual current rather than fault current magnitude. Increasing the MCB rating or altering the earthing conductor would not correct the fault path.

Question 22Health and Safety, Electrical Safety and Safe Isolation

Which of the following is a recognised method of confirming that a circuit is isolated before work begins?

  1. Checking that the switch is in the off position
  2. Proving dead at the point of work with an approved indicator Correct answer.
  3. Asking the building owner to confirm the supply is off
  4. Listening for the absence of hum from the equipment

Explanation

Isolation is only confirmed by proving the circuit dead at the point of work with an approved voltage indicator after the isolation has been applied and locked off. Switch position, verbal confirmation and the absence of noise are not proof of a dead circuit.

Question 23Health and Safety, Electrical Safety and Safe Isolation

What does the term 'safe isolation' mean in the context of electrical maintenance?

  1. Disconnecting the neutral conductor only
  2. Working during a planned power cut without further precautions
  3. Switching off the lighting in the work area
  4. A documented procedure that isolates, locks off, proves dead and secures the circuit before work Correct answer.

Explanation

Safe isolation is the full documented procedure of identifying the circuit, isolating it, locking off and tagging, proving dead and securing the point of work. It is more than switching off a single device or relying on a planned outage.

Question 24Health and Safety, Electrical Safety and Safe Isolation

Which of the following is the correct action if a danger tag is found on a switch and the person named on it cannot be located?

  1. Ignore the tag because the circuit is probably not in use
  2. Leave the tag in place and escalate through the responsible person Correct answer.
  3. Replace the tag with a handwritten note
  4. Remove the tag and energise the circuit

Explanation

A danger tag indicates that a person has control of the isolation, so it must not be removed by anyone else. If the named person cannot be found, the matter must be escalated to the responsible person so the isolation can be formally resolved.

Question 25Electrical Science, Principles and Calculations

Σε μονοφασικό κύκλωμα εναλλασσόμενου ρεύματος με ωμικό φορτίο, ποια είναι η σχέση μεταξύ της ενεργού ισχύος P, της τάσης V και του ρεύματος I;

  1. P = V·I·√3
  2. P = V·I·συνφ, με συνφ = 1 Correct answer.
  3. P = V·I·ημφ
  4. P = V·I/2

Explanation

Σε καθαρά ωμικό φορτίο η τάση και το ρεύμα είναι σε φάση, άρα η γωνία φ είναι μηδέν και ο συντελεστής ισχύος ισούται με τη μονάδα. Η ενεργός ισχύς δίνεται από τη γενική σχέση P = V·I·συνφ, η οποία ανάγεται σε P = V·I.

Question 26Electrical Science, Principles and Calculations

Αντιστάτης 220 Ω συνδέεται σε τάση 110 V. Ποια είναι η ισχύς που καταναλώνει;

  1. 0,5 W
  2. 55 W Correct answer.
  3. 22 W
  4. 110 W

Explanation

Η ισχύς υπολογίζεται από τη σχέση P = V²/R. Αντικαθιστώντας P = 110²/220 = 12100/220 = 55 W. Εναλλακτικά, το ρεύμα είναι I = V/R = 0,5 A και P = V·I = 55 W.

Question 27Electrical Science, Principles and Calculations

Τρεις αντιστάσεις 6 Ω συνδέονται παράλληλα. Ποια είναι η ισοδύναμη αντίσταση του συνδυασμού;

  1. 6 Ω
  2. 3 Ω
  3. 18 Ω
  4. 2 Ω Correct answer.

Explanation

Σε παράλληλη σύνδεση n ίσων αντιστάσεων R, η ισοδύναμη αντίσταση είναι R/n. Εδώ 6/3 = 2 Ω. Επαληθεύεται και από το άθροισμα των αγωγιμοτήτων: 1/6 + 1/6 + 1/6 = 1/2 S, άρα 2 Ω.

Question 28Electrical Science, Principles and Calculations

Ποια είναι η μονάδα μέτρησης της χωρητικότητας στο Διεθνές Σύστημα (SI);

  1. Βολτ (V)
  2. Φάραντ (F) Correct answer.
  3. Χένρι (H)
  4. Κουλόμπ (C)

Explanation

Η χωρητικότητα εκφράζει φορτίο ανά μονάδα τάσης, C = Q/V, και μετριέται σε φάραντ. Ένα φάραντ ισούται με ένα κουλόμπ ανά βολτ.

Question 29Electrical Science, Principles and Calculations

Σε κύκλωμα εναλλασσόμενου ρεύματος με πηνίο ιδανικά επαγωγικό, πώς συμπεριφέρεται η τάση ως προς το ρεύμα;

  1. Η τάση προηγείται του ρεύματος κατά 180°
  2. Η τάση έπεται του ρεύματος κατά 90°
  3. Η τάση προηγείται του ρεύματος κατά 90° Correct answer.
  4. Η τάση είναι σε φάση με το ρεύμα

Explanation

Σε ιδανικό πηνίο η τάση κορυφώνεται πριν από το ρεύμα, δηλαδή προηγείται κατά γωνία 90°. Αυτό προκύπτει από τη σχέση v = L·di/dt, όπου η τάση είναι ανάλογη της μεταβολής του ρεύματος.

Question 30Electrical Science, Principles and Calculations

Κινητήρας τριφασικού συστήματος 400 V απορροφά γραμμικό ρεύμα 10 A με συντελεστή ισχύος 0,8. Ποια είναι προσεγγιστικά η φαινόμενη ισχύς;

  1. 8,0 kVA
  2. 5,5 kVA
  3. 3,2 kVA
  4. 6,9 kVA Correct answer.

Explanation

Η φαινόμενη ισχύς σε τριφασικό σύστημα δίνεται από S = √3·V·I. Έτσι S = 1,732 × 400 × 10 ≈ 6 928 VA, δηλαδή περίπου 6,9 kVA. Ο συντελεστής ισχύος χρησιμοποιείται μόνο για τη μετάβαση στην ενεργό ισχύ.

Question 31Electrical Science, Principles and Calculations

Πυκνωτής 100 μF φορτίζεται μέσω αντίστασης 10 kΩ. Ποια είναι η σταθερά χρόνου του κυκλώματος;

  1. 10 s
  2. 0,1 s
  3. 1 s Correct answer.
  4. 0,01 s

Explanation

Η σταθερά χρόνου κυκλώματος RC δίνεται από τ = R·C. Με R = 10 000 Ω και C = 100×10⁻⁶ F προκύπτει τ = 1 s. Σε χρόνο ίσο με μία σταθερά χρόνου ο πυκνωτής φτάνει περίπου στο 63 % της τελικής τάσης.

Question 32Electrical Science, Principles and Calculations

Σε κύκλωμα RLC σειράς με R = 30 Ω, X_L = 50 Ω και X_C = 10 Ω, ποια είναι η σύνθετη αντίσταση (εμπέδηση) Z;

  1. 30 Ω
  2. 50 Ω Correct answer.
  3. 40 Ω
  4. 70 Ω

Explanation

Η εμπέδηση σειράς υπολογίζεται από Z = √(R² + (X_L − X_C)²). Εδώ X_L − X_C = 40 Ω, άρα Z = √(900 + 1600) = √2500 = 50 Ω.

Question 33Electrical Science, Principles and Calculations

Σε κύκλωμα σειράς, δύο αντιστάσεις 100 Ω και 200 Ω διαρρέονται από ρεύμα 0,5 A. Ποια είναι η τάση στα άκρα της διάταξης;

  1. 150 V Correct answer.
  2. 100 V
  3. 50 V
  4. 300 V

Explanation

Σε σειρά το ρεύμα είναι κοινό και οι αντιστάσεις προστίθενται: R_ολ = 300 Ω. Η συνολική τάση είναι V = I·R = 0,5 × 300 = 150 V.

Question 34Electrical Science, Principles and Calculations

Ποιος είναι ο συντελεστής ισχύος κυκλώματος με ενεργό ισχύ 800 W και φαινόμενη ισχύ 1000 VA;

  1. 0,8 Correct answer.
  2. 0,6
  3. 1,25
  4. 0,75

Explanation

Ο συντελεστής ισχύος ορίζεται ως ο λόγος της ενεργού προς τη φαινόμενη ισχύ, συνφ = P/S. Έτσι 800/1000 = 0,8. Η τιμή αυτή αντιστοιχεί σε γωνία φ περίπου 36,9°.

Question 35Electrical Science, Principles and Calculations

Σε κύκλωμα εναλλασσόμενου ρεύματος, ένας πυκνωτής χωρητικότητας C = 50 μF συνδέεται σε τάση 230 V με συχνότητα 50 Hz. Ποια είναι προσεγγιστικά η χωρητική αντίδραση X_C;

  1. 31,8 Ω
  2. 63,7 Ω Correct answer.
  3. 636 Ω
  4. 127 Ω

Explanation

Η χωρητική αντίδραση δίνεται από X_C = 1/(2πfC). Με f = 50 Hz και C = 50×10⁻⁶ F προκύπτει X_C = 1/(2π × 50 × 50×10⁻⁶) ≈ 63,7 Ω.

Question 36Electrical Science, Principles and Calculations

Σε κύκλωμα με ημιτονοειδή τάση ενεργού τιμής 230 V, ποια είναι η μέγιστη (κορυφαία) τιμή της τάσης;

  1. 230 V
  2. 460 V
  3. 162,6 V
  4. 325 V Correct answer.

Explanation

Η μέγιστη τιμή συνδέεται με την ενεργό τιμή μέσω της σχέσης V_max = √2·V_rms. Έτσι 1,414 × 230 ≈ 325 V. Η ενεργός τιμή είναι εκείνη που παράγει την ίδια θερμική ισχύ με συνεχή τάση ίση με αυτήν.

Question 37Electrical Science, Principles and Calculations

Σε κύκλωμα RLC σειράς με R = 10 Ω, L = 0,1 H και C = 100 μF, σε ποια συχνότητα συντονισμού βρίσκεται το κύκλωμα;

  1. περίπου 159 Hz Correct answer.
  2. περίπου 1000 Hz
  3. περίπου 15,9 Hz
  4. περίπου 50 Hz

Explanation

Η συχνότητα συντονισμού δίνεται από f₀ = 1/(2π√(LC)). Με L = 0,1 H και C = 100×10⁻⁶ F, το γινόμενο LC = 10⁻⁵ και η ρίζα του είναι 3,16×10⁻³, άρα f₀ ≈ 159 Hz. Στον συντονισμό X_L = X_C και η εμπέδηση γίνεται ελάχιστη, ίση με R.

Question 38Electrical Science, Principles and Calculations

Σε τριφασικό συμμετρικό φορτίο συνδεδεμένο σε αστέρα (Y) με τάση φάσης 230 V και αντίσταση 23 Ω ανά φάση, ποιο είναι το ρεύμα γραμμής;

  1. 17,3 A
  2. 10 A Correct answer.
  3. 30 A
  4. 3,3 A

Explanation

Σε σύνδεση αστέρα το ρεύμα γραμμής ισούται με το ρεύμα φάσης, το οποίο υπολογίζεται από τη φασική τάση: I = V_φάσης/R = 230/23 = 10 A. Σε σύνδεση τριγώνου θα χρησιμοποιούνταν η πολική τάση και ο συντελεστής √3 για το ρεύμα γραμμής.

Question 39Electrical Science, Principles and Calculations

Πηνίο με ωμική αντίσταση 8 Ω και επαγωγική αντίδραση 6 Ω συνδέεται σε τάση 100 V. Ποια είναι η ενεργός ισχύς που καταναλώνει;

  1. 1000 W
  2. 600 W
  3. 1200 W
  4. 800 W Correct answer.

Explanation

Η εμπέδηση είναι Z = √(R² + X_L²) = √(64 + 36) = 10 Ω, άρα το ρεύμα είναι I = 100/10 = 10 A. Η ενεργός ισχύς καταναλώνεται μόνο στην ωμική αντίσταση: P = I²·R = 100 × 8 = 800 W.

Question 40Electrical Science, Principles and Calculations

Ένα πηνίο με επαγωγή L = 0,2 H διαρρέεται από ρεύμα που αυξάνεται με σταθερό ρυθμό 50 A/s. Ποιο είναι το μέτρο της επαγωγικής τάσης (ΗΕΔ αυτεπαγωγής) που αναπτύσσεται στα άκρα του πηνίου;

  1. 10 V Correct answer.
  2. 0,004 V
  3. 0,1 V
  4. 250 V

Explanation

Ο νόμος του Faraday για αυτεπαγωγή δίνει e = L · (di/dt), δηλαδή το μέτρο της επαγωγικής τάσης ισούται με το γινόμενο της επαγωγής επί τον ρυθμό μεταβολής του ρεύματος. Εδώ L = 0,2 H και di/dt = 50 A/s, άρα e = 0,2 × 50 = 10 V. Το πρόσημο της ΗΕΔ εξαρτάται από τη φορά της μεταβολής (νόμος Lenz), αλλά το μέτρο είναι 10 V.

Question 41Regulations, Standards and Legal Framework for Electrical Installations

Σύμφωνα με το πρότυπο που διέπει τις ηλεκτρικές εγκαταστάσεις χαμηλής τάσης στην Κύπρο, ποια είναι η τυπική ονομαστική τάση λειτουργίας των μονοφασικών οικιακών παροχών;

  1. 690 V μεταξύ φάσης και ουδετέρου
  2. 230 V μεταξύ φάσης και ουδετέρου Correct answer.
  3. 400 V μεταξύ φάσης και ουδετέρου
  4. 110 V μεταξύ φάσης και ουδετέρου

Explanation

Το εναρμονισμένο ευρωπαϊκό σύστημα που εφαρμόζεται και στην Κύπρο προβλέπει 230 V μεταξύ φάσης και ουδετέρου και 400 V μεταξύ δύο φάσεων. Η τιμή αυτή αποτελεί τη βάση για τον υπολογισμό διατομών, πτώσης τάσης και επιλογής προστατευτικών διατάξεων.

Question 42Regulations, Standards and Legal Framework for Electrical Installations

Σε μια μονοφασική οικιακή εγκατάσταση, ποια διάταξη προστατεύει πρωτίστως τα πρόσωπα από ηλεκτροπληξία λόγω ρεύματος διαρροής προς γη;

  1. Ο αυτόματος διακόπτης ισχύος (MCB)
  2. Ο διακόπτης διαφυγής έντασης (RCD) Correct answer.
  3. Ο διακόπτης απομόνωσης
  4. Η ασφάλεια τήξεως

Explanation

Ο διακόπτης διαφυγής έντασης (RCD) ανιχνεύει τη διαφορά ρεύματος μεταξύ φάσης και ουδετέρου και αποσυνδέει το κύκλωμα όταν η διαρροή προς γη υπερβεί την ονομαστική τιμή ευαισθησίας. Οι διατάξεις υπερέντασης δεν ανιχνεύουν ρεύμα διαρροής προς γη.

Question 43Regulations, Standards and Legal Framework for Electrical Installations

Ποιος είναι ο σκοπός της σύνδεσης του αγωγού προστασίας (PE) με το σύστημα γείωσης της εγκατάστασης;

  1. Η αύξηση της διατομής των αγωγών φάσης
  2. Η μείωση της πτώσης τάσης στα κυκλώματα φωτισμού
  3. Η βελτίωση του συντελεστή ισχύος των φορτίων
  4. Η δημιουργία οδού σφάλματος ώστε να λειτουργήσει η προστασία και να εκτονωθεί το δυναμικό του σώματος Correct answer.

Explanation

Ο αγωγός προστασίας συνδέει τα εκτεθειμένα αγώγιμα μέρη με τη γείωση, ώστε σε σφάλμα μόνωσης να δημιουργηθεί ρεύμα σφάλματος ικανό να ενεργοποιήσει την προστατευτική διάταξη και να κρατήσει τα μεταλλικά μέρη σε ασφαλές δυναμικό.

Question 44Regulations, Standards and Legal Framework for Electrical Installations

Ποια είναι η μέγιστη τιμή ρεύματος ενεργοποίησης που απαιτείται συνήθως για πρόσθετη προστασία έναντι ηλεκτροπληξίας σε τελικά κυκλώματα πριζών οικιακής χρήσης;

  1. 30 mA Correct answer.
  2. 500 mA
  3. 1 A
  4. 300 mA

Explanation

Για πρόσθετη προστασία ατόμων σε κυκλώματα πριζών απαιτείται RCD με ονομαστικό ρεύμα ενεργοποίησης που δεν υπερβαίνει τα 30 mA. Μεγαλύτερες τιμές δεν θεωρούνται επαρκείς για προστασία έναντι επικίνδυνης ηλεκτροπληξίας.

Question 45Regulations, Standards and Legal Framework for Electrical Installations

Ποια αρχή είναι αρμόδια για την έκδοση και τον έλεγχο της άδειας ηλεκτρολόγου εγκαταστάτη στην Κύπρο;

  1. Η Ρυθμιστική Αρχή Ενέργειας Κύπρου Correct answer.
  2. Το Υπουργείο Εργασίας και Κοινωνικών Ασφαλίσεων
  3. Ο Δήμος της περιοχής του εγκαταστάτη
  4. Η Αρχή Ηλεκτρισμού Κύπρου

Explanation

Η Ρυθμιστική Αρχή Ενέργειας Κύπρου (ΡΑΕΚ) είναι η αρμόδια ρυθμιστική αρχή για θέματα ηλεκτρισμού, περιλαμβανομένης της αδειοδότησης των επαγγελματιών ηλεκτρολόγων. Οι τοπικές αρχές εκδίδουν οικοδομικές άδειες αλλά όχι άδειες άσκησης επαγγέλματος ηλεκτρολόγου.

Question 46Regulations, Standards and Legal Framework for Electrical Installations

Ένας εγκαταστάτης πρόκειται να επέμβει σε πίνακα διανομής υπό τάση. Ποια είναι η ορθή σειρά ενεργειών σύμφωνα με τους κανόνες ασφαλείας;

  1. Απομόνωση, επαλήθευση απουσίας τάσης, γείωση και ασφάλιση έναντι επανασύνδεσης Correct answer.
  2. Γείωση, απομόνωση, επαλήθευση απουσίας τάσης
  3. Επαλήθευση απουσίας τάσης, απομόνωση, αφαίρεση ασφάλισης
  4. Επανασύνδεση, απομόνωση, μέτρηση τάσης

Explanation

Η ασφαλής εργασία σε εγκατάσταση απαιτεί πλήρη απομόνωση, επαλήθευση απουσίας τάσης με κατάλληλο όργανο, γείωση και ασφάλιση έναντι τυχαίας ή εκούσιας επανασύνδεσης. Η σειρά αυτή εξασφαλίζει ότι ο εργαζόμενος δεν εκτίθεται σε επικίνδυνη τάση.

Question 47Regulations, Standards and Legal Framework for Electrical Installations

Σε κύκλωμα φωτισμού με φορτίο 10 A και MCB ονομαστικής έντασης 16 A τύπου B, ποια είναι η ελάχιστη τιμή ρεύματος στιγμιαίας ενεργοποίησης που αναμένεται;

  1. 80 A
  2. 160 A Correct answer.
  3. 32 A
  4. 16 A

Explanation

Ο διακόπτης τύπου B ενεργοποιεί στιγμιαία σε ρεύμα μεταξύ 3 και 5 φορές την ονομαστική του ένταση. Για ονομαστική ένταση 16 A, η ελάχιστη τιμή είναι 3 × 16 = 48 A και η μέγιστη 5 × 16 = 80 A, οπότε η ζητούμενη τιμή εμπίπτει στο εύρος αυτό.

Question 48Regulations, Standards and Legal Framework for Electrical Installations

Ποια είναι η κύρια λειτουργία του συστήματος ισοδυναμικής σύνδεσης σε ένα λουτρό;

  1. Η αντιστάθμιση άεργου ισχύος
  2. Η μείωση των ρευμάτων βραχυκυκλώματος
  3. Η εξίσωση δυναμικών μεταξύ μεταλλικών μερών ώστε να αποφεύγονται επικίνδυνες διαφορές τάσης Correct answer.
  4. Η αύξηση της αντίστασης μόνωσης των καλωδίων

Explanation

Η ισοδυναμική σύνδεση συνδέει όλα τα εκτεθειμένα και ξένα αγώγιμα μέρη ώστε να βρίσκονται στο ίδιο δυναμικό. Έτσι, ακόμη και αν εμφανιστεί τάση σφάλματος, δεν αναπτύσσεται επικίνδυνη διαφορά τάσης μεταξύ των μερών που μπορεί να αγγίξει ένα πρόσωπο.

Question 49Regulations, Standards and Legal Framework for Electrical Installations

Ποια είναι η ελάχιστη απαιτούμενη απόσταση ασφαλείας από εναέριες γραμμές μέσης τάσης κατά την εκτέλεση εργασιών με φορητή μεταλλική σκάλα;

  1. Αρκεί απόσταση 10 cm από τον αγωγό
  2. Δεν απαιτείται απόσταση εφόσον η σκάλα είναι ξύλινη
  3. Η επαφή επιτρέπεται εφόσον φοριούνται μονωτικά γάντια
  4. Να τηρείται η απόσταση ασφαλείας που καθορίζεται από τους κανονισμούς και την τάση της γραμμής, με ελάχιστο όριο που δεν επιτρέπει επαφή ή επικίνδυνη προσέγγιση Correct answer.

Explanation

Οι κανονισμοί ασφαλείας καθορίζουν ελάχιστες αποστάσεις προσέγγισης από ενεργά μέρη ανάλογα με την τάση, ώστε να αποκλείεται επαφή ή επικίνδυνη προσέγγιση ακόμη και με αγώγιμα εργαλεία. Η τήρηση των αποστάσεων αυτών είναι υποχρεωτική και δεν υποκαθίσταται από ατομικό προστατευτικό εξοπλισμό.

Question 50Regulations, Standards and Legal Framework for Electrical Installations

Πότε απαιτείται έκδοση Πιστοποιητικού Τελικής Αποδοχής ηλεκτρικής εγκατάστασης;

  1. Μετά την ολοκλήρωση νέας εγκατάστασης ή ουσιώδους τροποποίησης, πριν από την ενεργοποίηση ή επανασύνδεση Correct answer.
  2. Μόνο όταν η εγκατάσταση τροφοδοτείται από γεννήτρια
  3. Μόνο μετά από κάθε αλλαγή λαμπτήρα
  4. Κάθε φορά που αλλάζει ο ιδιοκτήτης του ακινήτου

Explanation

Το πιστοποιητικό τελικής αποδοχής εκδίδεται από αδειούχο ηλεκτρολόγο μετά την ολοκλήρωση νέας εγκατάστασης ή σημαντικής τροποποίησης και αποτελεί προϋπόθεση για την ενεργοποίηση ή επανασύνδεση της παροχής. Βεβαιώνει ότι η εγκατάσταση συμμορφώνεται με τους κανονισμούς.