Design density
The minimum water flow rate in gallons per minute per square foot applied over the design area; selected from the occupancy hazard curve and multiplied by the remote area to determine required flow.
Remote area
The hydraulically most demanding area of sprinkler operation used in calculations; typically 1,500 square feet for light hazard, increased for dry systems, sloped ceilings, and pitched roofs.
K-factor
A sprinkler discharge coefficient relating flow to pressure by Q equals K times the square root of P; a K-5.6 sprinkler flows 5.6 gpm at 1 psi.
Deflector distance
The vertical distance from the sprinkler deflector to the ceiling; typically 1 inch below noncombustible or combustible ceilings and at least 18 inches below the ceiling for storage applications.
Maximum sprinkler spacing
The greatest allowable distance between sprinklers on a branch line and between branch lines; 15 feet for light hazard and 12 feet for ordinary hazard in hydraulically calculated systems.
Hose stream allowance
The water flow reserved for fire department hose use in a hydraulic calculation; typically 100 gpm for light hazard and 250 gpm for ordinary hazard, added to sprinkler demand.
Sprinkler temperature rating
The activation temperature of a sprinkler head, typically 155°F or 165°F for ordinary ratings; must be at least 100°F above the maximum expected ceiling temperature.
Dry-pipe system
A sprinkler system with air or nitrogen under pressure in the piping; the dry-pipe valve opens when a sprinkler operates and air escapes, allowing water to flow.
Preaction system
A system where a detection device must operate before water enters the piping; single-interlock requires detection only, double-interlock requires both detection and sprinkler operation.
Alarm check valve
A wet-pipe riser valve that opens on water flow and transmits an alarm through a retard chamber and water motor gong; it also serves as a check valve.
Waterflow switch
A device on the riser that detects water flow and sends an alarm signal to the fire alarm panel; typically set to operate at 10 to 30 gpm.
Tamper switch
A supervisory device that monitors the open or closed position of a control valve and reports an off-normal condition to the fire alarm panel.
Escutcheon
A decorative and functional plate that covers the annular space between the sprinkler and the ceiling or wall; required for recessed and concealed pendants.
Backflow preventer
A device such as a reduced-pressure-zone or double-check assembly that prevents contamination of the potable water supply by reverse flow from the sprinkler system.
Hanger rod sizing
The diameter of the rod supporting sprinkler pipe; 3/8 inch for pipe up to 2 inches, 1/2 inch for 2.5 to 4 inches, and 5/8 inch for 5 to 6 inches.
Hydrostatic test
A pressure test of the piping system, typically 200 psi for 2 hours for systems operating at 150 psi or less, to verify joints and fittings are leak-free.
Inspector's test valve
A valve at the most remote end of the sprinkler system, piped to drain, that simulates the flow of a single sprinkler to verify water reaches the end of the line.
Main drain test
A flow test at the riser that records static and residual pressure; a residual drop exceeding 10 percent indicates an obstruction or supply problem.
Pipe pitch
The slope of sprinkler piping to allow drainage; typically 1/2 inch per 10 feet toward the drain, with auxiliary drains at low points.
Firestopping
Listed materials used to seal penetrations through fire-rated assemblies so the fire-resistance rating is maintained; required for sprinkler pipe passing through walls and floors.
Sway bracing
Lateral and longitudinal bracing installed to resist seismic forces on sprinkler piping; required in seismic design categories where NFPA 13 mandates it.
Underground cover
The minimum depth of cover over the underground supply main, typically 42 inches in the DC area to protect against frost and physical damage.
Weekly gauge check
A weekly inspection of the system gauges to confirm normal water and air pressure and that control valves are open and supervised or locked.
Annual trip test
A test of a dry-pipe or preaction valve performed annually to verify it opens at the correct air pressure and that water reaches the inspector's test connection.
Gauge replacement
Sprinkler system gauges must be replaced every 5 years and whenever the reading is off by more than 5 percent of full scale.
Sprinkler head replacement
Heads must be replaced if corroded, painted, damaged, or if they reach 50 years for quick-response or 75 years for standard-response unless sample testing proves them functional.
NFPA 25
The standard for inspection, testing, and maintenance of water-based fire protection systems; it defines frequencies and acceptance criteria for sprinkler systems.
Valve supervision
All control valves must be open and either locked or electrically supervised; closed valves must be documented and reported to the fire department.
NFPA 13
The standard for the design and installation of automatic sprinkler systems in commercial and industrial occupancies; it covers density, spacing, hydraulics, and materials.
NFPA 13R
The standard for sprinkler systems in residential occupancies up to and including four stories; it permits reduced design criteria compared with NFPA 13.
DC fire protection permit
A permit issued by the DC Department of Buildings and approved by DC Fire and EMS before sprinkler installation; final inspection and acceptance testing are witnessed by the Fire Marshal.
Master fire protection contractor
A license issued through the DC Board of Industrial Trades authorizing a contractor to install and maintain fire protection systems; individual installers must work under such a licensee.