DE Fire Alarm study materials
DE Fire Alarm study resources

DE Fire Alarm flashcards

DE Fire Alarm · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

NFPA 72 purpose
NFPA 72 provides requirements for the design, installation, commissioning, inspection, testing, and maintenance of fire detection and alarm systems, including notification and emergency communications.
Authority having jurisdiction
The organization, office, or individual responsible for enforcing code requirements or approving equipment, materials, installations, or procedures.
Listed device
Equipment included in a list published by an organization acceptable to the AHJ that maintains periodic inspection of production and whose listing states compliance with a recognized standard.
Supervisory signal
A signal indicating a condition of a system or protected premises requiring action, such as a closed valve or low air pressure, distinct from alarm and trouble signals.
Trouble signal
A signal indicating a fault in a circuit, component, or power supply that compromises system operation, requiring distinct audible and visual characteristics.
Smoke detector spacing
Spot-type smoke detectors on a smooth ceiling are spaced at 30 ft (9.1 m) listed spacing, reduced by a 0.7 multiplier for ceilings above 10 ft.
Ionization vs photoelectric
Ionization detectors respond better to small particles from flaming fires; photoelectric detectors respond better to larger particles from smoldering fires.
Manual fire alarm box location
Manual boxes must be within 5 ft of an exit door, mounted 42 to 48 in. above the floor, and spaced so travel distance does not exceed 200 ft.
Heat detector spacing
Fixed-temperature and rate-of-rise spot heat detectors commonly use 25 ft (7.6 m) listed spacing for 10 ft ceilings, reduced by 0.7 for higher ceilings.
Duct smoke detector requirement
Duct smoke detectors are required in air handling systems over 2,000 cfm where the system serves more than one story or more than 15,000 sq ft.
Temporal-three pattern
The standard evacuation signal: 0.5 s on, 0.5 s off, 0.5 s on, 0.5 s off, 0.5 s on, 1.5 s off, repeated.
Audible signal level
Public mode audible signals must produce at least 15 dBA above ambient or 5 dBA above ambient where ambient exceeds 105 dBA, measured 10 ft from the appliance.
Visible appliance candela rule
Public mode visible appliances require 0.0375 candela per square foot of floor area with a minimum of 15 cd, mounted 80 to 96 in. above the floor.
Sleeping area sound level
Private mode sleeping areas require at least 75 dBA at the pillow or 15 dBA above ambient, whichever is greater.
Voice system intelligibility
Voice evacuation systems must produce speech at least 15 dBA above ambient and meet intelligibility criteria such as CIS or STI where required by the AHJ.
Class A circuit
A supervised circuit that provides redundant paths and continues to operate during a single open or ground fault, unlike Class B circuits.
Class X circuit
A supervised circuit that continues to operate during a single open, ground fault, or short circuit, providing the highest pathway integrity.
End-of-line device
A resistor or listed module installed at the end of a notification appliance circuit to allow the control unit to supervise the circuit for opens and shorts.
Survivability requirement
Where required by the building code, fire alarm circuits must be protected by a 2-hour fire-rated pathway or listed circuit integrity cable.
Primary power connection
The control unit must connect to a dedicated, unswitched branch circuit marked at the disconnect means and provided with lockout/tagout capability.
Secondary power duration
Secondary power must operate the system for 24 hours plus 5 minutes of alarm signaling, or 15 minutes for voice evacuation, unless the AHJ requires 60 hours.
Battery calculation formula
Standby current times standby hours plus alarm current times alarm minutes divided by 60 equals ampere-hours, then add a 20 percent derating factor.
Battery charging requirement
The charger must restore the battery to 70 percent capacity within 4 hours and provide charging current per the manufacturer's listing, typically 13.8 V float for 12 V batteries.
Annual testing requirement
Initiating devices, notification appliances, and control equipment must be inspected and tested annually, with records maintained and made available to the AHJ.
Smoke detector test method
Smoke detectors are tested annually with a listed aerosol or calibrated test method, and heat detectors with a listed heat source or manufacturer's method.
Record of completion
A document completed at acceptance that records the system installation, calculations, and testing results, retained for the life of the system.
Battery test interval
Batteries are inspected and tested semiannually or per manufacturer instructions and replaced when they fail load testing, typically every 5 years.
Design hazard analysis
Design begins with a hazard analysis and review of the building code and NFPA 101 to determine whether a system is required and what type.
Detector location near HVAC
Detectors must be at least 3 ft from HVAC supply diffusers and 36 in. from air handling openings to avoid dilution of smoke.
Notification appliance spacing
Audible appliances are spaced to achieve required dBA throughout the area; visible appliances use the 0.0375 cd per square foot rule and listed spacing.
Delaware fire code adoption
Delaware adopts the International Fire Code and NFPA 1 as the state fire prevention code, with NFPA 72 referenced for fire alarm installation and testing.
Delaware licensing authority
The Delaware State Fire Prevention Commission licenses fire alarm contractors and technicians, requiring examination, renewal, and continuing education.