Power Supplies, Batteries, and Secondary Power Calculations
This domain tests whether the system keeps working when the utility fails. You need the primary supply rules, the standby-plus-alarm duration, and the arithmetic of a battery calculation including the derating factor.
Primary and secondary power
- Primary power is a dedicated branch circuit, protected by overcurrent device, marked for fire alarm use, and accessible only to authorized personnel.
- Secondary power is typically sealed lead-acid or nickel-cadmium batteries, or a generator. Secondary supply must carry the system under maximum normal load for 24 hours and then operate it under alarm conditions for 5 minutes. Voice evacuation systems require 15 minutes of alarm operation instead of 5.
- Special occupancies or AHJ conditions can extend standby to 60 hours.
- The charging means must be listed and sized to restore the battery in the time the manufacturer and code allow (commonly 4 hours).
Battery calculation method
- Sum standby current for all equipment (panel, annunciators, modules, transponders) and multiply by 24 hours.
- Sum alarm current for all equipment, including notification appliances and the panel itself, and multiply by 5/60 hour (0.0833) or 15/60 (0.25) for voice.
- Add the two results.
- Multiply by 1.20 for battery aging and discharge-rate derating.
- Select the next standard battery size above the result (4.5, 5, 7, 7.5, 8, 12, 18, 26 Ah).
Worked example
Standby load: panel 0.12 A + three NAC extenders at 0.045 A = 0.135 A + annunciator 0.035 A, total 0.29 A. Standby capacity = 0.29 × 24 = 6.96 Ah. Alarm load: panel 0.20 A + 40 addressable devices at 0.3 mA = 0.012 A + notification appliances 1.64 A, total 1.85 A. Alarm capacity = 1.85 × 0.0833 = 0.154 Ah. Sum = 7.114 Ah; × 1.20 = 8.54 Ah. The next standard size is 12 Ah, so a 12 Ah battery is specified. Then verify the charger can recharge 12 Ah within the allowed time and that battery-lead voltage drop at 1.85 A does not pull panel terminals below their minimum.
Traps
- Omitting the 1.20 derating factor.
- Using the 5-minute alarm duration on a voice evacuation system that needs 15 minutes.
- Leaving the panel's own alarm current out of the alarm total.
- Choosing a battery that equals the calculated value instead of the next size above.