Light hazard density
Light hazard design density is 0.10 gpm/ft² over a 1,500 ft² remote area, per NFPA 13 density/area curves, unless quick-response reduction applies.
Maximum sprinkler spacing
Standard spray sprinklers in light hazard shall be spaced not more than 15 ft apart and not more than 7 ft 6 in from walls, per NFPA 13.
Deflector distance
Standard spray sprinkler deflectors must be 1 in to 12 in below the ceiling; extended-coverage sprinklers allow 1 in to 18 in per listing.
Remote area shape
The remote area for hydraulic calculation is rectangular with length parallel to branch lines, or a shape with a 1.2√A aspect ratio per NFPA 13.
Quick-response reduction
Quick-response sprinklers in wet systems may reduce the design area by up to 30% when the remote area is ≤1,000 ft² and ceiling height ≤10 ft, per NFPA 13.
Extended coverage area
Extended-coverage sprinklers allow larger coverage per sprinkler (e.g., 400 ft² for light hazard) and greater spacing, as listed by the manufacturer.
Residential sprinkler density
NFPA 13D residential sprinklers require a minimum density of 0.05–0.10 gpm/ft² depending on the number of heads flowing, with maximum 400 ft² coverage per head.
NFPA 13 scope
NFPA 13 covers design and installation of automatic sprinkler systems for commercial, industrial, and high-rise residential occupancies, including water supply and hydraulic calculations.
Hanger spacing steel pipe
Steel pipe 1 in and smaller requires hangers at ≤12 ft intervals; 1¼ in and larger at ≤15 ft; hangers within 3 ft of sprinklers and 6 ft of direction changes.
Hydrostatic test pressure
Sprinkler piping must be hydrostatically tested at 200 psi for 2 hours, or 50 psi above working pressure if working pressure exceeds 150 psi, per NFPA 13.
Spare sprinkler cabinet
A spare sprinkler cabinet must contain at least 6 spare sprinklers of each type and temperature rating, or 2% of the total, whichever is greater, plus a wrench.
Control valve supervision
All sprinkler control valves must be supervised open using tamper switches or locked open, with supervisory signals monitored per NFPA 72.
Pipe schedule limits
The pipe schedule method is limited to specific pipe sizes and hazards; most new systems require hydraulic calculations per NFPA 13.
Underground main size
Fire service underground mains shall be at least 6 in in diameter unless hydraulic calculations justify a smaller size, per NFPA 13 and NFPA 24.
Hazen-Williams formula
Friction loss P = 4.52 Q^1.85 / (C^1.85 d^4.87), where Q is gpm, d is inside diameter in inches, and C is the roughness coefficient (steel 120, copper 150).
Flow test calculation
Available pressure at demand flow = static − (static − residual) × (Q_demand / Q_test)^1.85, using a flow test's static, residual, and flow values.
Safety margin
A safety margin of 10 psi or 5% of the demand pressure, whichever is greater, must exist between the water supply and system demand at the base of the riser.
Hose stream allowance
Hose allowance added to sprinkler demand is 100 gpm for light hazard, 250 gpm for ordinary hazard, and 500 gpm for extra hazard, per NFPA 13.
Elevation pressure loss
Each foot of elevation change equals 0.433 psi; add for rises and subtract for drops when calculating available pressure at sprinklers.
Fire pump churn pressure
Centrifugal fire pump shutoff (churn) pressure must not exceed 140% of rated pressure; the pump should be selected so demand is within 150% of rated flow.
Backflow preventer loss
Friction loss through backflow preventers and water meters must be included in hydraulic calculations using manufacturer-supplied curves at the design flow.
Velocity limit
Sprinkler piping velocity should generally not exceed 20 ft/s in supply mains and 10–15 ft/s in branch lines to limit friction loss and noise.
Weekly inspection
Weekly inspections include verifying control valves are open, gauges read normal, and fire pump status is operational, per NFPA 25.
Main drain test
A main drain flow test records static and residual pressure; a drop exceeding 10% from the baseline may indicate a supply obstruction or valve closure.
Dry pipe trip test
Dry pipe valves must be trip-tested annually; water must reach the test valve within 60 seconds of trip, and results are recorded in the ITM log.
Fire pump flow test
Annual fire pump flow tests measure pressure at churn, 100%, and 150% of rated flow; results are compared to baseline and kept on site.
Gauge calibration
Sprinkler system gauges must be replaced or recalibrated every 5 years, and alarm/supervisory circuits tested per NFPA 72.
Impairment procedure
When a system is impaired, notify the fire department and insurer, establish a fire watch, and follow NFPA 25 impairment handling until restoration.
Spare head replacement
Painted, corroded, or damaged sprinklers must be replaced with matching type and temperature rating; spare stock must be maintained in the cabinet.
Delaware code adoption
Delaware adopts NFPA 13, 13R, 13D, and NFPA 25 through the State Fire Prevention Regulations, with local amendments in Wilmington and New Castle County.
Plan review permit
Construction documents must be submitted to the Delaware State Fire Marshal or local AHJ for plan review and permit before sprinkler installation begins.
Contractor licensing
Delaware sprinkler contractors need a business license and certified fitters; verify licensing with the Delaware Division of Fire Prevention before contracting.