- Ohm's Law
- Voltage equals current times resistance (V = I × R). Power equals voltage times current (P = V × I). These two relationships underlie every low-voltage circuit calculation, including power supply sizing and voltage drop.
- Voltage Drop Formula
- For a two-conductor DC circuit, V_drop = 2 × L × I × R, where L is one-way length in feet and R is resistance per foot. Doubling accounts for the return conductor. Keep drop under 5% for most low-voltage loads.
- Characteristic Impedance
- The transmission-line impedance of a cable, such as 100 Ω for CAT6 or 120 Ω for RS-485. It depends on conductor geometry and insulation, not length. Mismatches cause signal reflections and increased return loss.
- Twisted Pair Noise Rejection
- Equal and opposite currents in a twisted pair create canceling magnetic fields, rejecting common-mode noise. The twist rate determines which frequencies are rejected. This is why pair integrity must be maintained at terminations.
- Class 2 vs Class 3
- Both are power-limited circuits under NEC Article 725, each limited to 100 VA per circuit. Class 2 is lower voltage and power; Class 3 allows higher voltage. Class 1 uses Chapter 3 wiring methods with no power limit.
- Plenum Rated Cable
- Cable listed CMP for installation in air-handling spaces. It uses low-smoke, low-flame-spread insulation. Riser cable (CMR) is for vertical shafts; general-purpose CM is for horizontal runs outside plenums.
- T568A vs T568B
- Two standard RJ-45 pinouts that differ only in the assignment of pairs 2 and 3. Either works if used consistently on both ends. T568B is more common in US commercial installations.
- Cable Bend Radius
- The minimum curve a cable can tolerate without damage. Unshielded twisted pair typically requires 4× the cable diameter during installation; fiber requires 10× or the manufacturer's rating, whichever is greater.
- Article 725 Scope
- NEC Article 725 governs remote-control, signaling, and power-limited circuits that are not integral to equipment. It defines Class 1, Class 2, and Class 3 circuits and their wiring, separation, and listing requirements.
- Intersystem Bonding Termination
- A listed device required by NEC 250.94 that provides a single accessible point for bonding communications, CATV, and satellite system grounds to the building grounding electrode system. Usually mounted outside.
- Environmental Air Space Rule
- NEC 300.22(C) permits only wiring methods specifically listed for plenum use inside environmental air spaces. This is why CMP cable, not general-purpose CM, must be used above suspended ceilings used as return air.
- Box Accessibility
- NEC 314.29 requires junction boxes and conduit bodies to remain accessible without removing building finish. Low-voltage splice points must not be buried in walls or ceilings, even though box fill rules may not apply.
- Category Cable Ratings
- CAT5e is rated to 100 MHz, CAT6 to 250 MHz, and CAT6A to 500 MHz. Higher categories support higher data rates over longer distances, with CAT6A reaching 100 m at 10GBASE-T.
- Permanent Link Limit
- The horizontal cable run may not exceed 90 m (295 ft). Adding patch cords at each end gives a 100 m channel. Exceeding the limit causes insertion loss and crosstalk failures during certification.
- NEXT Test
- Near-end crosstalk measures signal coupling from one pair to another at the transmitter end. High NEXT indicates poor termination, untwisted conductors, or a split pair and is a common cause of certification failure.
- Single-Mode Fiber
- Fiber with a small core (about 9 µm) that carries one propagation mode, using 1310 or 1550 nm lasers. It supports kilometers of distance and is used for campus and building backbone links.
- Class A vs Class B Circuit
- NFPA 72 circuit classifications. Class A keeps the circuit operational after a single open or ground fault by providing a redundant path. Class B supervises for opens but loses the circuit on a single fault.
- Smoke Detector Spacing
- On a smooth ceiling, detectors are spaced 30 ft apart nominally, with the first within 15 ft of a wall, covering up to 900 sq ft. Spacing is reduced for ceiling heights above 10 ft.
- NAC Voltage Drop
- Notification appliance circuits must deliver adequate voltage to the last device. Calculate V_drop = 2 × L × I × R and verify the final appliance stays within its listed operating range, often 16–33 V.
- Pull Station Height
- Manual fire alarm pull stations are mounted 42–48 in. above finished floor and within 5 ft of an exit door. They must be unobstructed and visible along the normal path of egress.
- Wiegand Interface
- A legacy access control interface using clock and data lines at 5 V, carrying a 26-bit format with facility code and card number. It is unidirectional and unencrypted, limited to about 500 ft.
- Fail-Safe vs Fail-Secure
- Fail-safe locks unlock when power is lost and are used on egress doors. Fail-secure locks stay locked on power loss and require a mechanical release for life safety. Selection is driven by code.
- OSDP Protocol
- Open Supervised Device Protocol is a bidirectional, encrypted access control standard that replaces Wiegand. It supports secure channel encryption, tamper reporting, and firmware updates over RS-485.
- RS-485 Termination
- A differential bus requiring 120 Ω termination at each physical end, daisy-chain topology, and up to 32 unit loads. Stubs and star wiring cause reflections and communication errors.
- 70.7 Volt Distributed Audio
- A constant-voltage speaker system where each speaker has a wattage tap. Total tap wattage must not exceed amplifier output. Higher line voltage reduces loss over long cable runs compared with 8 Ω systems.
- HDBaseT
- A standard that extends HDMI video, audio, Ethernet, control, and power over a single twisted-pair cable up to 100 m. It uses a proprietary chipset at both ends rather than standard IP networking.
- DMX512
- A lighting control protocol using RS-485 at 250 kbps, carrying 512 channels per universe. It is unidirectional, uses 5-pin XLR connectors, and requires termination at the end of the daisy chain.
- Speaker Impedance Loading
- On 8 Ω systems, parallel speakers halve the load: two 8 Ω speakers present 4 Ω. Never go below the amplifier's minimum rated impedance, or the amplifier will overheat or shut down.
- Grounding Electrode System
- NEC 250.50 requires all available electrodes, including metal water pipe, building steel, concrete-encased electrode, ground ring, and rods, to be bonded together into one system.
- Single-Point Bonding
- Bonding a cable shield or drain wire at only one end prevents ground loops caused by potential differences between locations. The far end is left floating or capacitively terminated to drain RF.
- Surge Protective Device Ratings
- SPDs are specified by MCOV, clamping voltage, surge current capacity in kA per mode, and response time. Type 1 installs at the service, Type 2 at distribution panels, and Type 3 at point of use.
- Delaware Licensing Authority
- The Delaware Board of Electrical Examiners, within the Division of Professional Regulation, licenses electricians and electrical contractors. Low-voltage work falls under the state electrical statutes and local permit authorities.