DE Water Operator flashcards
DE Water Operator · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- CT value
- CT equals disinfectant residual concentration in mg/L multiplied by effective contact time in minutes, expressed as mg·min/L; it quantifies disinfection exposure for inactivation credit.
- Chlorine demand
- The difference between the chlorine dose applied and the residual remaining after a specified contact time. Demand comes from oxidizable matter such as organics, iron, manganese, and ammonia.
- Hypochlorous acid fraction
- HOCl is the stronger disinfectant form of free chlorine. Its fraction increases as pH decreases, dropping sharply above pH 7.5 where hypochlorite ion dominates.
- Jar test purpose
- A bench-scale test that determines the optimum coagulant dose and pH for turbidity and organic removal before full-scale treatment adjustments are made.
- Filter uniformity coefficient
- The sieve size at 60% passing divided by the sieve size at 10% passing of filter media. Values of 1.5 or less indicate well-graded media.
- Combined filter effluent turbidity
- Turbidity of all filtered water combined. Conventional systems must stay at or below 0.3 NTU in 95% of monthly samples and never exceed 1 NTU.
- TTHM and HAA5
- Total trihalomethanes and five haloacetic acids, disinfection byproducts formed when chlorine reacts with natural organic matter; both have enforceable running annual average limits.
- Backwash purpose
- Reverse flow through a filter at a rate that expands the media bed, releasing trapped particles and restoring head loss and run time.
- Minimum distribution pressure
- Twenty psi is the regulatory minimum at all points in the distribution system under all conditions, including fire flow and main break scenarios.
- Feet of head to psi
- One psi equals approximately 2.31 feet of water column. Convert head in feet to psi by dividing by 2.31.
- Hazen-Williams head loss
- Empirical pipe friction formula where head loss rises with flow to the 1.85 power and falls with pipe diameter to the 4.87 power and roughness coefficient C to the 1.85 power.
- Air gap
- A physical, non-mechanical separation between a potable water outlet and the flood-level rim of a receiving vessel; the only backflow protection immune to failure.
- Reduced pressure zone assembly
- A testable backflow preventer with two check valves and a relief valve, used where both backpressure and back-siphonage hazards exist.
- Dead-end main risk
- Mains with only one flow path stagnate, lose disinfectant residual, and grow biofilm; chloraminated systems may nitrify. Flushing or looping mitigates.
- Main repair disinfection
- After repair, the main is chlorinated, typically to 25 to 100 mg/L for at least 24 hours, flushed, then sampled for coliform and residual before service.
- Storage tank turnover
- The time needed to cycle tank volume. Long detention consumes residual and raises disinfection byproduct and stagnation risk, so operations target adequate turnover.
- GWUDI definition
- Groundwater under the direct influence of surface water, meaning it is hydraulically connected to surface water and may carry pathogens; it is regulated like surface water.
- Turbidity as surrogate
- Turbidity measured in NTU indicates particle levels and serves as a proxy for treatment performance and pathogen removal, not a direct pathogen measurement.
- Hardness categories
- Total hardness reported as mg/L calcium carbonate: soft below 60, moderately hard 60 to 120, hard 120 to 180, very hard above 180.
- Iron and manganese limits
- Secondary limits are about 0.3 mg/L iron and 0.05 mg/L manganese; above these, staining and taste complaints occur. Treatment is oxidation followed by filtration.
- Nitrate MCL
- The nitrate limit is 10 mg/L measured as nitrogen. Exceedance triggers public notice due to methemoglobinemia risk in infants under six months.
- Langelier Saturation Index
- An index comparing actual pH to calcium-carbonate saturation pH. Near zero is balanced, negative tends to be corrosive, positive tends to form scale.
- Total coliform positive
- A routine positive total coliform sample triggers repeat sampling at the site and nearby locations, plus testing for E. coli and fecal indicators.
- Surface Water Treatment Rule log credits
- The rule requires 3-log Giardia and 4-log virus removal or inactivation, achieved through filtration and disinfection credited by CT tables.
- Stage 2 DBP LRAA
- Disinfection byproducts are limited on a locational running annual average basis: TTHM 80 µg/L and HAA5 60 µg/L at each monitoring location.
- Lead and copper action levels
- Tap sample 90th percentile action levels are 0.015 mg/L lead and 1.3 mg/L copper. Exceedance triggers corrosion control treatment and public education.
- Tier 1 public notice
- Immediate notice, within 24 hours, for acute violations such as E. coli or nitrate MCL exceedance, using radio, TV, hand delivery, or other required methods.
- Consumer Confidence Report
- An annual report delivered to customers by July 1 that lists source water, detected contaminants, compliance status, and required health effects language.
- Confined space atmosphere
- Acceptable entry atmosphere is oxygen between 19.5 and 23.5 percent, flammable gas below 10 percent of LEL, and hydrogen sulfide below 10 ppm.
- Chlorine gas behavior
- Chlorine gas is about 2.5 times heavier than air and collects in low areas, so escape requires moving upwind and to higher ground with proper respiratory protection.
- Lockout tagout steps
- Identify all energy sources, notify affected workers, shut down and isolate, apply locks and tags, release stored energy, then verify zero energy before work.
- Excavation protective system
- Any trench 5 feet deep or deeper requires a protective system such as sloping, shoring, or a trench box; spoil and equipment stay at least 2 feet back.