New 28 V DC feeder: voltage drop versus breaker size

EASA Module 7 · Put your knowledge to work in context.

All case studies

New 28 V DC feeder: voltage drop versus breaker size

You are installing a 28 V DC feeder to a new 20 A continuous-load unit in the aft equipment bay. The route measures 11 m one-way, so the conductor loop is 22 m. The cable drawn from stores is 8 AWG (8.37 mm²), conductor resistance 2.06 mΩ/m at 20 °C. It runs in a bundle in an unpressurised area where the maximum conductor temperature in service is 70 °C, which gives a resistance multiplier of 1.20. The maintenance manual requires a total feeder voltage drop of not more than 1.0 V, and a circuit breaker rated at least 125 % of the continuous load but not more than the cable's rating in this bundle (8 AWG: 45 A). A 25 A breaker is proposed. The technician estimates 'about 0.9 V' and considers the job done.

1. Calculate the voltage drop at maximum conductor temperature for the 8 AWG cable and state whether the installation meets the manual.

Read the worked answer

Loop resistance at 20 °C: 22 m × 2.06 mΩ/m = 45.3 mΩ

At 70 °C: 45.3 mΩ × 1.20 = 54.4 mΩ

Voltage drop: 20 A × 0.0544 Ω = 1.09 V

That is 3.9 % of 28 V and it exceeds the 1.0 V limit - the installation does not meet the manual.

The technician's 0.9 V is the 20 °C figure. Copper resistance rises with temperature, and a feeder in an unpressurised bundle will run hot; the hot case is the one that must be shown to comply, because it is the worst case the equipment will ever see. The margin is only 9 %, but 9 % over the limit is a non-conformance, not a rounding argument.

2. Select the next standard cable size and verify it, then check the breaker coordination.

Read the worked answer

Next size up: 6 AWG (13.3 mm²), 1.30 mΩ/m at 20 °C.

  • Loop resistance at 20 °C: 22 × 1.30 = 28.6 mΩ
  • At 70 °C: 28.6 × 1.20 = 34.3 mΩ
  • Voltage drop: 20 × 0.0343 = 0.686 V (2.4 % of 28 V) - comfortably inside the 1.0 V limit.

Breaker check:

  • 125 % of 20 A = 25 A, so a 25 A breaker is the minimum acceptable rating.
  • 6 AWG in this bundle is rated above the 8 AWG figure of 45 A, so 25 A protects the cable with margin.
  • The 25 A breaker must also be acceptable to the equipment manufacturer's approval basis (some equipment specifies a maximum protective device); verify before fitting.
  • Note the breaker protects the wire; the voltage-drop requirement is a separate check on conductor size, and both must pass independently.

3. The technician suggests fitting a 30 A breaker 'to give some margin'. Is that acceptable? Explain.

Read the worked answer

No. A larger breaker does nothing for voltage drop - the drop is set by current and conductor resistance, and both are unchanged. It buys no margin at all; it removes margin.

Specifically:

  • 30 A is 150 % of the continuous load, outside the 125 % design basis, so the circuit is over-protected relative to its design intent and the equipment's approval basis.
  • The breaker must protect the smallest conductor in the circuit. If any downstream wire or equipment internal wiring is smaller than the feeder, a 30 A device may allow a sustained overload that the small wire cannot survive - that is the classic EWIS fire scenario.
  • The correct fix is to attack the cause: increase conductor size (6 AWG), shorten the route, or reduce the load. Where a component is replaced, the change must be recorded against the wiring diagram and the load analysis updated.
  • Any change of protective device rating also requires approved data and an update to the circuit schedule, not an ad-hoc substitution.