EPA 608 Type I flashcards
EPA 608 Type I · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Section 608 venting prohibition
- It is illegal to knowingly vent ozone-depleting refrigerants and their substitutes during service, maintenance, repair, or disposal of appliances. Good-faith recovery and brief gauge connection releases are narrow exceptions.
- Small appliance definition
- A factory-sealed appliance charged with 5 pounds or less of refrigerant, such as a household refrigerator, freezer, window air conditioner, or dehumidifier. Motor vehicle air conditioners are excluded.
- Type I evacuation level
- Recovery equipment for small appliances must evacuate the appliance to 80 percent vacuum, roughly 4 inches Hg vacuum, or to the level certified by the equipment manufacturer.
- Recovery cylinder fill limit
- A recovery cylinder may be filled to no more than 80 percent of its capacity by liquid volume, leaving room for liquid expansion and preventing hydrostatic rupture.
- ODP of CFC-12
- CFC-12 has an ozone depletion potential of 1.0, the reference value. It is a Class I ozone-depleting substance and its venting is prohibited under Section 608.
- GWP reference
- Global warming potential uses carbon dioxide as the reference with a value of 1. R-134a is about 1,430 and R-410A about 2,088, so recovery reduces climate impact even for zero-ODP refrigerants.
- High-pressure evacuation, 5-50 lb
- For appliances containing 5 to 50 pounds, recovery equipment made after November 15, 1993 must evacuate to 0 inches Hg vacuum; older equipment must reach 10 inches Hg.
- Very high-pressure refrigerant handling
- R-410A and R-32 operate at higher pressures than R-22, so only R-410A-rated manifolds, hoses, and recovery equipment may be used to prevent hose failure and injury.
- Low-pressure evacuation level
- Low-pressure appliances must be evacuated to 25 inches Hg vacuum using recovery equipment made after November 15, 1993, or 20 inches Hg with older equipment.
- Leak repair 50-pound rule
- Appliances containing 50 or more pounds of refrigerant must have leaks repaired within 30 days of discovery, or the owner must create a retrofit or retirement plan.
- System-dependent recovery limit
- System-dependent recovery equipment relies on the appliance compressor and is limited to high-pressure appliances containing 15 pounds or less of refrigerant with an operating compressor.
- Piercing valve use
- Small appliances often lack service ports, so a piercing or line-tap valve is installed to access the sealed system for recovery before disposal or repair.
- Recovery before disposal
- The final person in the disposal chain must ensure refrigerant is recovered from a small appliance before it is shredded or crushed, and must verify recovery occurred.
- Purge unit function
- Low-pressure chillers run below atmospheric pressure, so a purge unit removes air and moisture that enter the system; purge exhaust must be recovered rather than vented.
- R-123 ODP
- R-123 is an HCFC with an ozone depletion potential of about 0.012. It is regulated under Section 608, so recovery and leak repair requirements apply.
- Vacuum dehydration target
- After repair, a system is evacuated with a vacuum pump and micron gauge to 500 microns or lower and held to confirm no moisture or leaks before charging.
- Nitrogen for leak detection
- Nitrogen is used to pressurize a system for leak detection. Refrigerant must never be used as a pressurizing gas because it would be vented during the test.
- Mixed refrigerant consequence
- Mixing different refrigerants in one recovery cylinder makes the contents non-reclaimable and may require destruction, so each refrigerant type needs a dedicated labeled cylinder.
- Section 608 certification scope
- Certification is required for technicians who maintain, service, repair, or dispose of appliances containing regulated refrigerant, and it is specific to the appliance type.
- Type I certification coverage
- Type I certification covers small appliances charged with 5 pounds or less, including household refrigerators, freezers, window units, and dehumidifiers, but not motor vehicle air conditioners.
- Recovered refrigerant disposition
- Refrigerant recovered from small appliances may be recycled on-site with certified equipment or sent to a reclamation facility; it may never be vented to the atmosphere.
- Standing vacuum test
- On a low-pressure chiller, a rise in pressure during a standing vacuum test indicates air or moisture entering the system through a leak.
- Moisture in low-pressure chillers
- Water entering a low-pressure chiller reacts with refrigerant to form corrosive acids, so moisture must be removed with dehydration filters and proper evacuation before charging.
- Relief device on chillers
- Low-pressure chillers use rupture discs and relief devices for overpressure protection; a ruptured disc releases refrigerant and the charge must be recovered before repair.
- R-410A GWP
- R-410A has a global warming potential of about 2,088 relative to carbon dioxide at 1, so recovering rather than venting it substantially reduces climate impact.
- De minimis release
- Small refrigerant releases during good-faith recovery or while connecting and disconnecting gauges are permitted; routine purging of hoses to atmosphere is a violation.
- Refrigerant frostbite hazard
- Liquid refrigerant at room temperature is under pressure and boils rapidly at atmospheric pressure, causing frostbite on skin contact; gloves and eye protection are required.
- Asphyxiation risk
- Refrigerant vapor is heavier than air and displaces oxygen in confined spaces such as basements and mechanical rooms, so ventilation and leak detection must precede work.
- Recovery cylinder marking
- Recovery cylinders must be DOT-approved, evacuated before first use, and marked with the refrigerant type; unmarked or mixed cylinders cannot be legally reclaimed.
- Small appliance recordkeeping exemption
- Small appliances of 5 pounds or less are exempt from Section 608 leak repair and refrigerant management recordkeeping rules, but venting and recovery-before-disposal rules still apply.
- High-pressure appliance definition
- High-pressure appliances include most commercial refrigeration and residential split systems using R-22, R-134a, and similar refrigerants; very high-pressure units use R-410A or R-32.
- Low-pressure appliance definition
- Low-pressure appliances operate with low-side pressure below atmospheric, typically centrifugal chillers using R-11, R-113, or R-123, and require specialized recovery methods.