FL Water Operator flashcards
FL Water Operator · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Coagulation
- Process that neutralizes particle charges and destabilizes suspended solids so they can clump together; rapid mixing disperses the coagulant throughout the raw water.
- Flocculation
- Gentle, prolonged mixing that encourages destabilized particles to collide and form larger, settleable floc; it follows rapid mix and precedes sedimentation.
- Sedimentation basin loading rate
- Surface overflow rate equals flow divided by clarifier surface area, usually expressed as gpm/ft²; higher rates reduce settling and may carry floc over.
- Detention time formula
- Detention time equals tank volume divided by flow rate; use consistent units so volume and flow produce the desired time units.
- CT value
- CT is disinfectant residual concentration in mg/L multiplied by effective contact time in minutes; it estimates pathogen inactivation and rises with stronger residual or longer contact.
- Jar test purpose
- Bench-scale test that simulates coagulation, flocculation, and settling to select coagulant dose, pH, and mixing conditions before full-scale adjustment.
- Breakpoint chlorination
- Point where chlorine demand is satisfied and further chlorine addition produces a rising free chlorine residual; past breakpoint, free chlorine persists for disinfection.
- Hazen-Williams head loss
- Empirical pipe friction formula relating head loss to flow, pipe diameter, length, and roughness coefficient; smaller diameter or rougher pipe sharply increases head loss.
- Water hammer cause
- Pressure surge created when water velocity changes suddenly, such as rapid valve closure or pump trip; slow valve operation and surge protection reduce damage.
- Cross-connection
- Any actual or potential link between potable water and a contamination source; backflow prevention devices or an air gap protect the public water supply.
- Air gap backflow prevention
- Physical separation between a potable water outlet and the flood level of a receiving vessel; it provides the highest protection against backflow contamination.
- Dead-end main problem
- Pipe section with no through flow where water stagnates, disinfectant residual decays, and sediment accumulates; looping or routine flushing improves quality.
- Thrust block purpose
- Concrete or restrained block installed at bends, tees, and caps to resist unbalanced pressure forces that would otherwise separate pipe joints.
- Storage tank turnover
- Replacing stored water through normal demand and cycling so age does not become excessive; poor turnover can reduce residual and promote stagnation.
- Affinity laws
- For a centrifugal pump, flow changes with speed, head with speed squared, and power with speed cubed when impeller diameter is unchanged.
- Water horsepower formula
- Water horsepower equals flow in gpm times total head in feet divided by 3960; brake horsepower equals water horsepower divided by pump efficiency.
- NPSH margin
- Net positive suction head available must exceed the pump's required NPSH; insufficient margin causes cavitation, vibration, and impeller damage.
- Cavitation symptoms
- Cavitation produces gravel-like noise, vibration, reduced flow or head, and pitting of the impeller; it occurs when local pressure drops below vapor pressure.
- Parallel pump operation
- Two pumps discharging into a common header increase total flow, but each operates near its own curve; head rise is usually limited compared with series operation.
- Lockout tagout purpose
- Procedure that isolates hazardous energy before maintenance so equipment cannot start unexpectedly; each worker applies a personal lock and verifies isolation.
- HOCl versus OCl-
- Hypochlorous acid is the more effective chlorine disinfectant; it dominates at lower pH, while hypochlorite ion dominates at higher pH.
- Turbidity and disinfection
- Turbidity particles can shield microorganisms and consume disinfectant; low filtered-water turbidity is required for effective disinfection and treatment performance.
- Sodium thiosulfate sampling
- Chemical added to bacteriological sample bottles to neutralize chlorine and prevent continued disinfection during transport; it does not sterilize the bottle.
- DPD chlorine test
- Colorimetric method using DPD reagent to measure free and total chlorine residual; free chlorine reacts immediately, and total includes combined chlorine.
- Sample tap flushing
- Running the tap before collecting a water sample clears the service line and aerator of stagnant water so the sample represents the main.
- Combined chlorine
- Chlorine that has reacted with ammonia or nitrogen compounds to form chloramines; it is a weaker disinfectant and can produce taste and odor complaints.
- Tier 1 public notice
- Immediate notice for serious violations or emergencies with health risk; the water system must notify the public as soon as possible, generally within 24 hours.
- Consumer Confidence Report
- Annual report that community water systems provide to customers, summarizing source water, detected contaminants, compliance, and health effects information.
- Confined space entry
- Entry into a space with limited access and possible hazardous atmosphere; requires atmospheric testing, ventilation, an attendant, and a permit before entry.
- SDS purpose
- Safety Data Sheet provides hazard, handling, first-aid, and spill information for a chemical; it must be accessible to employees under hazard communication rules.
- Recordkeeping purpose
- Daily logs of flows, residuals, chemical doses, and maintenance create an operating record used for compliance reporting, troubleshooting, and trend analysis.
- Chlorine gas leak response
- Evacuate, alert responders, and use appropriate respiratory protection; never enter a chlorine release area without training and self-contained breathing apparatus.