FOA CPCT flashcards
FOA CPCT · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Horizontal permanent link length
- Maximum horizontal cable length is 90 m, from the telecommunications outlet to the horizontal cross-connect. The 10 m of equipment and patch cords brings the total channel to 100 m.
- TIA-606 scope
- The administration standard for telecommunications infrastructure. It defines labeling schemes, records, and identifiers so every cable, port, and pathway can be traced and documented.
- TIA-607 bonding and grounding
- Specifies the telecommunications bonding backbone, the main grounding busbar, and telecommunications grounding busbars. All are bonded to the building grounding electrode system to equalize potential.
- Plenum cable rating CMP
- CMP cable is rated for air-handling spaces and has low smoke and flame spread characteristics. Installing non-plenum cable in a plenum ceiling violates building and fire code.
- Backbone fiber distance limit
- Multimode backbone runs are commonly limited to about 300 m and singlemode to about 3000 m, but the exact limit depends on the application and the media selected.
- Category 6A frequency
- Category 6A balanced twisted-pair cable is characterized to 500 MHz and supports 10GBASE-T over full 100 m channels. It usually uses a separator or shielding to control alien crosstalk.
- T568A versus T568B
- T568A assigns the green pair to pins 1 and 2 and the orange pair to pins 3 and 6. T568B swaps those pairs. Both ends must match for a straight-through cable.
- Untwist limit at termination
- Category 6 and 6A terminations allow no more than about 13 mm of untwisted conductor. More untwisting increases near-end crosstalk and can fail certification testing.
- Split pair fault
- A wiring error where a conductor is paired with a conductor from a different pair. Wiremap may show continuity, but crosstalk and noise rise sharply and the link fails testing.
- Characteristic impedance UTP
- Unshielded twisted-pair premises cable has a nominal characteristic impedance of 100 ohms. Impedance mismatches cause reflections, which appear as return loss failures.
- Stranded versus solid termination
- RJ45 plugs are designed for stranded patch cable. Solid conductor cable belongs on insulation displacement connectors such as jacks and patch panels, where the blade grips the conductor.
- NEXT definition
- Near-end crosstalk is signal coupled from a transmitting pair into another pair, measured at the same end. Higher values in dB mean better separation between pairs.
- OM3 and OM4 fiber
- Laser-optimized 50/125 um multimode fiber. OM3 supports 10GBASE-SR to 300 m and OM4 to 400 m. Both use 850 nm vertical cavity surface emitting lasers.
- APC connector polish
- Angled physical contact connectors have an 8-degree endface, usually green. They must only mate with other APC connectors; mating with UPC or PC creates an air gap and high loss.
- Singlemode core size
- Singlemode fiber typically has a 9 um core and 125 um cladding. It carries one propagation mode and supports long distances at 1310 nm and 1550 nm.
- Fusion splice loss
- An arc-welded fusion splice typically shows about 0.1 dB loss or less, the lowest of any joining method. Mechanical splices and field-installable connectors generally show higher loss.
- LC connector ferrule
- The LC is a small form factor connector with a 1.25 mm ferrule and a latch. It is common in high-density patch panels and duplex fiber transceivers.
- Multimode attenuation values
- Typical maximum multimode attenuation is about 3.5 dB/km at 850 nm and 1.5 dB/km at 1300 nm. Singlemode is lower, about 1.0 and 0.5 dB/km.
- OTDR purpose
- An optical time-domain reflectometer sends pulses and measures backscatter to locate breaks, splices, and connectors, and to report distance and loss along the fiber.
- Fiber bend radius
- Installed fiber should not be bent tighter than about 10 times the cable outside diameter under load. Tighter bends cause macrobend loss and can crack the glass.
- Copper pull tension limit
- Four-pair copper cable is typically limited to 25 lbf, or about 110 N, during installation. Exceeding it stretches conductors, changes impedance, and degrades performance.
- OLTS reference methods
- One-jumper, two-jumper, and three-jumper reference methods produce different loss budgets. Record which method was used so test results can be compared fairly.
- Wiremap test
- A wiremap verifies pin-to-pin continuity and detects opens, shorts, reversed pairs, and split pairs. It does not measure crosstalk or return loss.
- Certification tester setup
- Select the correct test limit, such as Category 6 permanent link, and the correct cable type before testing. A wrong limit produces results that cannot be compared to the standard.
- Fiber endface inspection
- Inspect every connector endface with a scope before mating. A single dust particle can cause high loss or permanent scratches, so clean and re-inspect when contamination is seen.
- Fiber scrap hazard
- Cleaved fiber scraps are sharp and can penetrate skin or eyes. Keep safety glasses on and place all scraps in a labeled sharps container, never in ordinary trash.
- Laser eye safety
- Never look into a fiber or connector with the unaided eye. Use an optical power meter to confirm whether a source is live, and treat unknown fiber as energized.
- Class 1 laser system
- Class 1 laser products are safe under normal use because the beam is enclosed. Class 1M is safe unless optics such as magnifiers are used, so avoid viewing with lenses.
- Troubleshooting high NEXT
- If NEXT fails, suspect excessive untwisting at the jack, a split pair, a crushed cable, or a jack damaged during termination. Re-terminate and retest before replacing the run.
- Troubleshooting high fiber loss
- Check for dirty endfaces, wrong polish mating such as APC to UPC, tight bends, and damaged splices. Clean and inspect first, then measure with an OLTS or OTDR.
- Pathway fill and support
- Cable trays and conduits have fill limits, and cables must be supported at intervals set by code and standard. Overfilling makes pulls hard and can damage cable jackets.
- Documenting test results
- Save and label test results by cable identifier, matching the administration records. Results must show the test limit, date, tester, and pass or fail for each link.