TP EIMSA flashcards
TP EIMSA · Build recall with a focused review session.
31 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Touch voltage limit
- Maximum permissible touch voltage under IEC 60364-4-41 is 50 V AC or 120 V DC in ordinary locations, reduced to 25 V AC or 60 V DC in wet or confined conductive locations.
- Earth-fault loop impedance
- Zs must not exceed U0 divided by Ia, where Ia is the current causing the protective device to operate within the required disconnection time for that circuit.
- RCD 30 mA purpose
- A 30 mA residual current device provides additional protection against electric shock for socket-outlets up to 32 A and for circuits in locations with increased shock risk.
- IP code meaning
- The IP rating states ingress protection: first digit for solids from 0 to 6, second digit for water from 0 to 9K, for example IP65 is dust-tight and jet-proof.
- Arc flash incident energy
- Incident energy at a working distance depends on bolted fault current, protective device clearing time, electrode gap and working distance, and determines the required PPE category.
- Three-phase power formula
- For a balanced three-phase load, active power P equals root three times line voltage times line current times power factor; reactive power uses sine of the angle.
- Star-delta relationships
- In a star connection line voltage is root three times phase voltage and line current equals phase current; in delta the reverse applies to current and voltage.
- Per-unit impedance
- Per-unit impedance equals actual impedance divided by base impedance, where base impedance is base voltage squared divided by base apparent power.
- Synchronous speed
- Synchronous speed of an induction motor equals 120 times supply frequency divided by number of poles; slip is the difference between synchronous and rotor speed over synchronous speed.
- Power factor correction
- Capacitance per phase needed to raise power factor equals active power times the difference of tangents of the initial and target angles, divided by two pi f V squared.
- Conductor colour code
- Under IEC 60446 line conductors are brown, black and grey, neutral is blue, and the protective conductor is green-yellow; these colours must not be reused for other purposes.
- Minimum conductor sizes
- Copper lighting circuits require at least 1.5 square millimetres, socket-outlet circuits at least 2.5 square millimetres, subject to correction factors and protective device rating.
- Fire-rated cable
- Fire-resistant cables maintain circuit integrity for a defined period such as 30, 60 or 120 minutes and are required for fire alarm, emergency lighting and smoke control circuits.
- Cable tray fill
- Cable tray and conduit fill limits cap the sum of cable cross-sections, commonly 40 to 50 percent of the containment cross-section, to allow heat dissipation and later pulling.
- SWA cable gland
- Steel wire armoured cable requires a gland that clamps and earths the armour; the gland must match the cable type and, in hazardous areas, carry the appropriate certification.
- Lockout tagout sequence
- Isolate the supply, lock and tag, prove dead with a tested voltage detector, apply earths and short-circuits, guard adjacent live parts, then issue the permit to work.
- Insulation resistance test voltage
- Apply 500 V DC for circuits rated up to 500 V and 1000 V DC for 690 V systems; the minimum acceptable result is generally 1 megohm per circuit.
- Ring circuit continuity
- For a ring final circuit the resistance of the protective conductor end-to-end must not exceed the line conductor end-to-end resistance, confirming the ring is complete.
- Thermographic survey
- An infrared survey under load reveals loose or high-resistance connections by comparing phase-to-phase and phase-to-ambient temperature rises before failure occurs.
- Initial verification sequence
- IEC 60364-6 order: visual inspection, continuity, insulation resistance, polarity, earth electrode resistance, loop impedance, RCD operation and functional tests, recorded on a certificate.
- RCD trip time limits
- A general-type RCD must trip within 300 milliseconds at rated residual current and within 40 milliseconds at five times rated current, and must not trip at half rated current.
- Fall-of-potential method
- Earth electrode resistance is measured by driving two auxiliary rods at defined spacings and measuring voltage and current; the result is plotted to confirm the plateau reading.
- Loop impedance correction
- Measured loop impedance is compared with the tabulated maximum after applying a 0.8 correction factor to account for conductor resistance at operating temperature.
- Protection relay secondary injection
- Secondary injection applies known currents and voltages to relay terminals to verify pickup, timing and trip contacts against the coordination study settings before energisation.
- Half-split method
- Divide the circuit or signal path into two halves, test at the midpoint, then repeat on the faulty half, reducing the number of test points needed logarithmically.
- Nuisance RCD tripping
- Cumulative leakage from many loads, transient surges, or a genuine insulation fault can trip an RCD; insulation resistance tests and progressive disconnection separate the causes.
- Motor fails to start
- Check supply voltage and phase balance, control circuit, overload relay state, winding resistance and insulation, then the mechanical load, before replacing the motor.
- Harmonic symptoms
- Neutral current exceeding phase current, transformer overheating and distorted waveforms indicate harmonics; a power quality analyser records total harmonic distortion and spectra.
- IEC 60364 protection measures
- Permitted shock protection measures include automatic disconnection, double or reinforced insulation, SELV and PELV, electrical separation, and extra-low voltage with limited energy.
- Ex zone classification
- IEC 60079-10-1 defines gas zones 0, 1 and 2 and dust zones 20, 21 and 22; equipment group, category and temperature class must match the zone.
- Test certificate contents
- A test certificate records installation identification, extent and limitations, instrument serial numbers and calibration dates, results, departures, and the signature of the competent person.