GA Elevator Mechanic study materials
GA Elevator Mechanic study resources

GA Elevator Mechanic cheat sheet

GA Elevator Mechanic · Keep the key ideas within reach.

Quick reference

Elevator and Escalator Code Compliance and Inspection

  • ASME A17.1/CSA B44 is the model safety code for elevators and escalators; ASME A17.2 covers inspection, testing, and maintenance frequency and procedures, and ASME A17.3 governs existing installations.

  • Georgia adopts A17.1 through Rules of the Georgia Safety Fire Commissioner, Elevator Rules and Regulations, Chapter 120-3-13; the adopted edition in force governs plan review and acceptance testing.

  • Periodic inspection categories under A17.2: escalators and moving walks are typically inspected every 6 months; elevators by type (electric traction, hydraulic, etc.) carry defined intervals, and Georgia's rules set the actual required frequency.

  • A Category 1 test is performed with the car empty at rated speed; a Category 5 test is performed with rated load (or specified load) and includes the tripping of the safety and the buffer test where applicable.

  • Acceptance tests on new installations include: safety gear test and governor tripping speed, buffer test, oil buffer verification, terminal stopping devices, emergency brake, and rated-load speed and current checks.

  • Governor tripping speed for a car safety must fall within the range specified in A17.1 for the rated speed; the safety must stop and hold the car with rated load without permanent deformation of guide rails.

  • Escalator safety devices that must be tested: comb plate switches, skirt guard (side) switches, handrail entry switches, step/skirt clearance and step sag devices, missing-step device, and the emergency stop button.

  • Clearances under A17.1: minimum refuge (runby) space in the pit, top-of-car clearance to overhead, and minimum overhead clearance for escalators are code-defined dimensions that must be verified at inspection.

  • Inspection findings are documented and corrected within the timeframe set by the authority having jurisdiction; failure to correct can lead to suspension of the operating certificate.

Quick reference

Elevator and Escalator Installation and Maintenance Practice

  • Plumb the guide rails to the code-specified tolerance: rail alignment (plumb) is typically no more than 0.5 mm per 5 m (about 1/16 in. per 15 ft) for each rail, and rail-to-rail twist is limited; verify against the adopted code edition.

  • Guide rail bracket spacing depends on rail size and load; typical maximum spacing is about 4.9 m (16 ft) for standard rails, with closer spacing where the code or rail manufacturer requires.

  • Machine room and overhead requirements: adequate ventilation, machine room temperature limits, a lockable door opening outward, and working space for maintenance and testing.

  • Pit requirements: a ladder or stairway for pit access, a pit light and GFCI receptacle, a sump or drain where required, and a stop switch accessible at the pit entrance.

  • Hydraulic elevator maintenance: check oil level and condition, valve operation, jack packing for leaks, and the pressure relief valve setting; the relief valve must be set to bypass at a pressure below the system's design limit.

  • Traction elevator maintenance: inspect ropes for broken wires, wear, and corrosion per the retirement criteria; check sheave wear, rope equalization, brake lining wear, and brake setting/clearance.

  • Escalator maintenance: check step chain tension and elongation, handrail speed synchronization, comb segment condition, and the step-to-skirt clearance, and verify the step level (sag) at the landing.

  • Before returning an elevator to service after maintenance, verify: door operation, leveling accuracy at each landing, terminal limits, and that all safety switches are functional.

Quick reference

Electrical and Mechanical Controls and Safety Devices

  • A car safety gear is tripped by the governor when the car overspeeds in the down direction (for most traction elevators); the safety is mechanically applied and must stop and hold the car.

  • The governor tripping speed for a car safety is set relative to rated speed; for typical traction elevators it is roughly 115% of rated speed, with the exact value set by A17.1.

  • Final and normal terminal stopping devices: normal limits slow/stop the car at the terminal landing, final limits are a backup, and the final limit switch must open the power circuit to prevent overtravel.

  • Door interlocks: the car cannot move unless all hoistway doors and the car door are closed and locked; the interlock must be electrically monitored so a car cannot start with a door unlocked.

  • The emergency stop switch (where provided) and the machine room disconnect: the main line disconnect must be lockable, and the disconnect must remove power from the driving machine and controller.

  • Hydraulic elevator safety: a pressure relief valve, a check valve, a rupture (pipe break) valve, and a low-oil/oil-temperature protection device; the rupture valve limits oil flow on a pipe failure.

  • Escalator electrical safety chain: any opened safety switch (comb, skirt, handrail, step) opens the control circuit and stops the escalator; the escalator must not restart automatically after a safety trip.

  • Motor overload and phase protection: overload relays protect the driving machine motor, and phase-reversal/phase-failure protection prevents the motor from running in the wrong direction or on a lost phase.

  • Brake setting: the brake must be capable of holding the car at 125% of rated load (per code requirements for the applicable equipment); verify lining condition and spring setting.

Quick reference

Georgia Licensing Law, Rules, and Safety Fire Regulations

  • Elevator contractor and mechanic licensing in Georgia is administered through the Georgia Safety Fire Commissioner's Office, Elevator Division, under Chapter 120-3-13 of the Georgia Rules and Regulations.

  • A licensed elevator mechanic must be at least 18 years old, meet experience requirements (typically several years of documented elevator work under a licensed mechanic), and pass the licensing examination.

  • Work on elevators and escalators must be performed by or under the direct supervision of a licensed elevator mechanic; an apprentice or helper must work under supervision.

  • A permit is required before installing or altering an elevator or escalator; plans are reviewed by the Elevator Division, and an inspection/acceptance test is required before the operating certificate is issued.

  • The operating certificate must be posted in the elevator car or machine room and kept current; operating an elevator without a valid certificate is a violation subject to enforcement action.

  • The Safety Fire Commissioner may suspend or revoke a license or certificate for violations, and may order an elevator taken out of service when it presents an imminent hazard.

  • Reportable accidents (injury or fatality) and serious equipment failures must be reported to the Elevator Division, and the equipment may be required to remain out of service pending investigation.

  • License renewal, continuing education, and fee requirements are set by rule; failure to renew can result in a lapsed license and prohibited practice.

Quick reference

Elevator and Escalator Code Compliance and Inspection

  • ASME A17.1/CSA B44 is the model safety code for elevators and escalators; ASME A17.2 covers inspection, testing, and maintenance frequency and procedures, and ASME A17.3 governs existing installations.

  • Georgia adopts A17.1 through Rules of the Georgia Safety Fire Commissioner, Elevator Rules and Regulations, Chapter 120-3-13; the adopted edition in force governs plan review and acceptance testing.

  • Periodic inspection categories under A17.2: escalators and moving walks are typically inspected every 6 months; elevators by type (electric traction, hydraulic, etc.) carry defined intervals, and Georgia's rules set the actual required frequency.

  • A Category 1 test is performed with the car empty at rated speed; a Category 5 test is performed with rated load (or specified load) and includes the tripping of the safety and the buffer test where applicable.

  • Acceptance tests on new installations include: safety gear test and governor tripping speed, buffer test, oil buffer verification, terminal stopping devices, emergency brake, and rated-load speed and current checks.

  • Governor tripping speed for a car safety must fall within the range specified in A17.1 for the rated speed; the safety must stop and hold the car with rated load without permanent deformation of guide rails.

  • Escalator safety devices that must be tested: comb plate switches, skirt guard (side) switches, handrail entry switches, step/skirt clearance and step sag devices, missing-step device, and the emergency stop button.

  • Clearances under A17.1: minimum refuge (runby) space in the pit, top-of-car clearance to overhead, and minimum overhead clearance for escalators are code-defined dimensions that must be verified at inspection.

  • Inspection findings are documented and corrected within the timeframe set by the authority having jurisdiction; failure to correct can lead to suspension of the operating certificate.

Quick reference

Elevator and Escalator Installation and Maintenance Practice

  • Plumb the guide rails to the code-specified tolerance: rail alignment (plumb) is typically no more than 0.5 mm per 5 m (about 1/16 in. per 15 ft) for each rail, and rail-to-rail twist is limited; verify against the adopted code edition.

  • Guide rail bracket spacing depends on rail size and load; typical maximum spacing is about 4.9 m (16 ft) for standard rails, with closer spacing where the code or rail manufacturer requires.

  • Machine room and overhead requirements: adequate ventilation, machine room temperature limits, a lockable door opening outward, and working space for maintenance and testing.

  • Pit requirements: a ladder or stairway for pit access, a pit light and GFCI receptacle, a sump or drain where required, and a stop switch accessible at the pit entrance.

  • Hydraulic elevator maintenance: check oil level and condition, valve operation, jack packing for leaks, and the pressure relief valve setting; the relief valve must be set to bypass at a pressure below the system's design limit.

  • Traction elevator maintenance: inspect ropes for broken wires, wear, and corrosion per the retirement criteria; check sheave wear, rope equalization, brake lining wear, and brake setting/clearance.

  • Escalator maintenance: check step chain tension and elongation, handrail speed synchronization, comb segment condition, and the step-to-skirt clearance, and verify the step level (sag) at the landing.

  • Before returning an elevator to service after maintenance, verify: door operation, leveling accuracy at each landing, terminal limits, and that all safety switches are functional.

Quick reference

Electrical and Mechanical Controls and Safety Devices

  • A car safety gear is tripped by the governor when the car overspeeds in the down direction (for most traction elevators); the safety is mechanically applied and must stop and hold the car.

  • The governor tripping speed for a car safety is set relative to rated speed; for typical traction elevators it is roughly 115% of rated speed, with the exact value set by A17.1.

  • Final and normal terminal stopping devices: normal limits slow/stop the car at the terminal landing, final limits are a backup, and the final limit switch must open the power circuit to prevent overtravel.

  • Door interlocks: the car cannot move unless all hoistway doors and the car door are closed and locked; the interlock must be electrically monitored so a car cannot start with a door unlocked.

  • The emergency stop switch (where provided) and the machine room disconnect: the main line disconnect must be lockable, and the disconnect must remove power from the driving machine and controller.

  • Hydraulic elevator safety: a pressure relief valve, a check valve, a rupture (pipe break) valve, and a low-oil/oil-temperature protection device; the rupture valve limits oil flow on a pipe failure.

  • Escalator electrical safety chain: any opened safety switch (comb, skirt, handrail, step) opens the control circuit and stops the escalator; the escalator must not restart automatically after a safety trip.

  • Motor overload and phase protection: overload relays protect the driving machine motor, and phase-reversal/phase-failure protection prevents the motor from running in the wrong direction or on a lost phase.

  • Brake setting: the brake must be capable of holding the car at 125% of rated load (per code requirements for the applicable equipment); verify lining condition and spring setting.

Quick reference

Georgia Licensing Law, Rules, and Safety Fire Regulations

  • Elevator contractor and mechanic licensing in Georgia is administered through the Georgia Safety Fire Commissioner's Office, Elevator Division, under Chapter 120-3-13 of the Georgia Rules and Regulations.

  • A licensed elevator mechanic must be at least 18 years old, meet experience requirements (typically several years of documented elevator work under a licensed mechanic), and pass the licensing examination.

  • Work on elevators and escalators must be performed by or under the direct supervision of a licensed elevator mechanic; an apprentice or helper must work under supervision.

  • A permit is required before installing or altering an elevator or escalator; plans are reviewed by the Elevator Division, and an inspection/acceptance test is required before the operating certificate is issued.

  • The operating certificate must be posted in the elevator car or machine room and kept current; operating an elevator without a valid certificate is a violation subject to enforcement action.

  • The Safety Fire Commissioner may suspend or revoke a license or certificate for violations, and may order an elevator taken out of service when it presents an imminent hazard.

  • Reportable accidents (injury or fatality) and serious equipment failures must be reported to the Elevator Division, and the equipment may be required to remain out of service pending investigation.

  • License renewal, continuing education, and fee requirements are set by rule; failure to renew can result in a lapsed license and prohibited practice.