- Sensible heat equation
- Btu/h = 1.08 × CFM × ΔT for standard air at sea level. The constant combines air density, specific heat, and 60 minutes per hour to convert airflow and temperature change into heat rate.
- AFUE
- Annual Fuel Utilization Efficiency is the seasonal efficiency rating for heating equipment, accounting for steady-state combustion efficiency plus cycling, standby, and jacket losses over a typical heating season.
- Condensing furnace
- A furnace that extracts latent heat by cooling flue products below the water vapor dew point, reaching 90%+ AFUE. The acidic condensate requires PVC venting and a drain with neutralizer.
- Hydronic Btu formula
- Btu/h = 500 × GPM × ΔT for water. The 500 constant reflects 8.33 lb per gallon, specific heat of 1.0, and 60 minutes per hour, so 10 GPM at 20°F delivers 100,000 Btu/h.
- Heat pump balance point
- The outdoor temperature where heat pump capacity equals the building heat loss. Below this point, supplemental heat must make up the shortfall to maintain indoor setpoint.
- Flame rectification sensor
- A rod that proves burner flame by sensing the tiny DC current that flows when flame conducts ions between the rod and grounded burner. A dirty rod causes lockout or short cycling.
- Breathing-zone ventilation rate
- ASHRAE 62.1 formula Vbz = Rp × Pz + Ra × Az, where people and area components are summed to give the minimum outdoor airflow required for a zone.
- MERV rating
- Minimum Efficiency Reporting Value rates filter capture of particles from 0.3 to 10 microns on a 1–16 scale. Higher MERV means finer capture but greater pressure drop and fan energy.
- Demand-controlled ventilation
- A control strategy that modulates outdoor air based on measured occupancy, often via CO2 sensors. It saves energy in variable-occupancy spaces while maintaining acceptable indoor air quality.
- Building pressure relationship
- A space is negative when exhaust exceeds supply and positive when supply exceeds exhaust. Contaminant sources such as bathrooms and kitchens are held negative to prevent migration.
- Makeup air requirement
- Outdoor air supplied to replace air exhausted by hoods or fans. Unbalanced exhaust depressurizes the building, causing backdraft of combustion appliances and infiltration of unconditioned air.
- Radon action level
- EPA recommends mitigation when indoor radon exceeds 4 picocuries per liter. Sub-slab depressurization is the standard mitigation method for existing homes.
- Superheat definition
- The difference between actual suction line temperature and saturated suction temperature at the same pressure. It confirms that refrigerant is fully vapor before entering the compressor.
- Subcooling definition
- The difference between saturated condensing temperature and liquid line temperature. It confirms that liquid refrigerant is fully condensed and indicates charge level on a TXV system.
- Sensible heat ratio
- Sensible capacity divided by total capacity. A typical residential value near 0.75 means about three-quarters of the cooling effect lowers temperature and the rest removes moisture.
- Refrigeration cycle order
- Compressor raises pressure and temperature, condenser rejects heat and condenses, metering device drops pressure, and evaporator absorbs heat before returning vapor to the compressor.
- Evaporator freezing threshold
- Coil temperature must remain above 32°F to prevent condensate freezing. Low airflow, low charge, or a restricted metering device can drop coil temperature below freezing and ice the coil.
- Compression ratio
- Absolute discharge pressure divided by absolute suction pressure. Ratios above roughly 10:1 on single-stage equipment produce high discharge temperatures that degrade oil and compressor life.
- Zeotropic refrigerant blend
- A mixture whose components boil at different temperatures, causing a temperature glide. R-410A must be charged as liquid to avoid fractionation that changes blend composition.
- Equal friction duct sizing
- A method that selects duct sizes so friction loss per unit length stays constant along the run. It uses available static pressure and equivalent length to set the friction rate.
- Velocity pressure formula
- VP = (V ÷ 4,005)² in inches of water column, where V is velocity in feet per minute. Total pressure equals static pressure plus velocity pressure.
- Equivalent length of fittings
- The straight-duct length that produces the same pressure loss as a fitting. A radius elbow is about 30 ft; a hard tee can equal 60 to 100 ft of duct.
- Return grille sizing
- Return free area is commonly sized near 2 square feet per ton of cooling. Undersized returns raise system static pressure and reduce delivered airflow.
- Suction line oil return
- Suction line velocity must stay above roughly 500 feet per minute to carry oil back to the compressor, while staying below about 4,000 feet per minute to avoid noise.
- TXV function
- A thermostatic expansion valve modulates refrigerant flow to maintain a set superheat at the evaporator outlet, responding to bulb temperature and evaporator pressure.
- Ohm's law and power
- V = I × R and P = V × I = I²R. These relationships let technicians compute current, resistance, and wattage for heaters, motors, and control circuits.
- Thermostat terminal letters
- R is 24 V hot, W calls heat, Y calls cooling, G calls fan, O or B reverses the heat pump valve, and C provides common power for smart thermostats.
- Run capacitor failure
- A failed run capacitor prevents the motor from starting under load, causing hum and overload trips. A bulged case or capacitance below 10% of rating confirms replacement.
- Temperature rise check
- Measure supply minus return air temperature and compare with the data plate value, typically within plus or minus 10%. High rise suggests low airflow; low rise suggests excess airflow.
- Manual J load calculation
- The ACCA method that sums transmission losses (U × A × ΔT) and infiltration losses (1.08 × CFM × ΔT) for heating, and radiant plus internal gains for cooling.
- Manual S equipment selection
- The ACCA procedure for choosing equipment whose capacity matches the Manual J load without exceeding it. Oversizing causes short cycling, poor dehumidification, and higher energy use.
- A2L refrigerant classification
- ASHRAE 34 class for mildly flammable refrigerants such as R-32 and R-454B. Installations require ignition-source controls, leak detection, and charge limits in occupied spaces.