Hawaii Low Voltage Practice flashcards
Hawaii Low Voltage Practice · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Class 2 circuit
- A circuit supplied by a listed Class 2 power source that limits energy to safe levels, typically 30 V or less and limited current, allowing installation without the physical protection required for power circuits.
- Class 3 circuit
- A circuit powered by a listed Class 3 source with higher permitted voltage and current than Class 2 (up to 100 V and greater power). It still requires separation from power conductors but can support more devices.
- Article 725 scope
- NEC Article 725 governs Class 1, Class 2, and Class 3 remote-control, signaling, and power-limited circuits. It defines wiring methods, separation, and overcurrent protection for low-voltage control and signaling systems.
- Article 800 scope
- NEC Article 800 covers communication circuits, including telephone, data, and broadband. It addresses cable listing, primary protectors, grounding, and separation from power conductors to prevent fire and shock hazards.
- Article 820 scope
- NEC Article 820 governs community antenna television (CATV) and radio distribution systems. It requires listed coaxial cable, primary protectors at building entry, and bonding to the grounding electrode system.
- Power-limited source
- A listed supply whose output is inherently limited in voltage and current (for example, a Class 2 transformer or a listed Class 2 power supply). The listing defines the maximum permitted circuit current.
- Separation requirement
- Class 2 and Class 3 cables must be separated from power conductors by at least 2 inches (50 mm) or by a continuous barrier, unless the cable is listed for the combination or installed in a raceway.
- Primary protector
- A device installed on communication or antenna cables at the building entrance that limits surge voltage to ground. It must be bonded to the grounding electrode system with a conductor sized per the applicable NEC table.
- Grounding electrode system
- The interconnected set of grounding electrodes (rod, water pipe, concrete-encased, ground ring) defined in NEC Article 250. Communication and CATV protectors must be bonded to this system.
- Voltage drop formula
- VD = 2 × L × I × R / 1000, where L is one-way length in feet, I is current in amperes, and R is conductor resistance in ohms per 1000 feet. The factor 2 accounts for the return path.
- Three percent rule
- A common design guideline limits voltage drop on a branch circuit to 3% of source voltage and total feeder plus branch drop to 5%. NEC recommends these values in informational notes.
- Low-voltage definition
- In Hawaii practice, low voltage generally refers to circuits at 50 V or less, covering Class 2/Class 3 signaling, control, and communication systems installed under NEC Articles 725, 800, and 820.
- HRS Chapter 448E
- Hawaii's electricians and plumbers licensing statute. It establishes license categories and authorizes the Department of Commerce and Consumer Affairs to regulate electrical work in the state.
- DCCA PVL
- The Hawaii Department of Commerce and Consumer Affairs, Professional and Vocational Licensing branch. It issues and renews electrician licenses and administers exams and continuing education requirements.
- Journeyman electrician license
- A Hawaii license allowing the holder to perform electrical work under the supervision of a supervising electrician. It requires documented experience and passing a state examination.
- Supervising electrician license
- A Hawaii license authorizing the holder to supervise electrical work and, in some cases, to contract for electrical work. It requires additional experience beyond journeyman and a state exam.
- Permit requirement
- Electrical permits are issued by the county building department (for example, Honolulu DPP or Hawaii County). Permits and inspections are required for most electrical work, including new circuits.
- EMT support spacing
- Electrical metallic tubing must be supported within 3 ft of boxes and at intervals not exceeding 10 ft, per NEC Table 358.30. Supports must be listed and securely fastened.
- PVC support spacing
- Rigid PVC conduit support spacing depends on trade size: 3 ft for 1/2 in through 1 in, 5 ft for 1 1/4 in through 2 in, per NEC Table 352.30.
- Box support distance
- Raceways and cables must be secured within 12 in (300 mm) of a box and supported within 12 in of the box unless the box is designed to support the wiring method.
- Conductor ampacity
- Ampacity is the maximum current a conductor can carry continuously without exceeding its temperature rating. It depends on conductor size, insulation type, ambient temperature, and number of current-carrying conductors.
- Derating for bundling
- When more than three current-carrying conductors share a raceway or cable, ampacity is reduced per NEC Table 310.15(C)(1). Four to six conductors are derated to 80% of table ampacity.
- Ambient temperature correction
- Conductor ampacity is adjusted for ambient temperature using NEC Table 310.15(B)(1). Higher ambient temperatures reduce ampacity; lower temperatures may allow a slight increase.
- GFCI protection
- Ground-fault circuit interrupter protection is required in specific locations (bathrooms, kitchens, outdoors, garages) per NEC 210.8. It trips at 4-6 mA of ground-fault current to prevent shock.
- AFCI protection
- Arc-fault circuit interrupter protection detects dangerous arcing and is required on 120 V branch circuits in dwelling units per NEC 210.12. It reduces the risk of electrical fires.
- Bonding vs grounding
- Grounding connects equipment to earth; bonding connects metal parts together to ensure equal potential. Both are required for safety and are defined in NEC Article 100.
- Equipment grounding conductor
- The conductor that provides a low-impedance path for fault current back to the source, enabling overcurrent devices to trip. It is green, green with yellow stripe, or bare copper.
- Cable tray fill
- Cable tray fill is limited by NEC Article 392. The sum of cable cross-sectional areas must not exceed the tray's permitted fill, and cables must be supported and secured per the article.
- Class 1 circuit
- A circuit that is not power-limited and operates at up to 600 V, typically for remote control or signaling. It requires wiring methods similar to power circuits and overcurrent protection per Article 725.
- Listing and labeling
- Equipment must be listed by a recognized testing laboratory (UL, ETL) and installed per its listing. Field modifications that void the listing are not permitted under NEC 110.3(B).
- Working clearance
- NEC 110.26 requires a minimum working space in front of electrical equipment, typically 3 ft deep and 30 in wide, to allow safe maintenance and operation.
- Hawaii county inspection
- Each county (Honolulu, Hawaii, Maui, Kauai) issues electrical permits and conducts inspections. Work must be inspected before being covered or energized, and final inspection closes the permit.