Fire tetrahedron
The four requirements for flaming combustion: fuel, oxidant, heat and an uninhibited chemical chain reaction. Removing any one extinguishes the flame.
t-squared fire growth
A fire growth model in which heat release rate rises with the square of time: Q = αt², where α is the growth coefficient in kW/s².
Flashover
The transition from a growing compartment fire to full involvement of combustible contents, commonly associated with upper-layer gas temperatures near 600 °C or floor radiant flux near 20 kW/m².
Ventilation-limited fire
A compartment fire whose heat release rate is controlled by the air supply through openings rather than by fuel surface area, typical after flashover in a closed compartment.
Smoke layer descent
The downward accumulation of hot combustion products beneath a ceiling, reducing the clear layer and available egress time as the fire grows.
Travel distance
The measured distance an occupant must travel from any point to a place of safety, limited by code according to occupancy, sprinkler protection and escape route arrangement.
Fire resistance rating
The period for which an element satisfies stability, integrity and insulation criteria under a standard fire test, expressed in minutes such as 60/60/60.
Compartmentation
Division of a building into fire-rated compartments by walls, floors and doors to limit fire and smoke spread, fire size and consequential damage.
Protected lobby
A fire-rated lobby separating accommodation from a staircase, fitted with self-closing fire doors to keep smoke out of the escape stair.
Sprinkler design density
The discharge rate in mm/min applied over a specified operating area at the most hydraulically remote heads, selected from the occupancy hazard classification.
Sprinkler K-factor
A coefficient relating head flow to pressure by Q = K√P, characterising the discharge capacity of a sprinkler head.
Clean agent hold time
The period for which a gaseous suppression concentration is maintained in an enclosure after discharge, verified by a door fan integrity test.
Water-mist system
A suppression system producing fine droplets for cooling and oxygen displacement, requiring listing for the specific hazard and not interchangeable with sprinklers.
Cause-and-effect matrix
A documented table linking each detection or alarm input to the required outputs, such as plant shutdown, door release, pressurisation and suppression release.
Pre-action sprinkler system
A dry system in which water is admitted to the pipework only after a detection signal, reducing accidental discharge risk in sensitive occupancies.
Design fire scenario
A justified credible fire case defined by fuel, arrangement, ignition, ventilation and active system reliability, used as the input to fire engineering analysis.
ASET versus RSET
Available safe egress time from tenability analysis compared with required safe egress time from detection, pre-movement and travel, with a safety margin.
Zone model
A fire model assuming uniform upper and lower compartment layers, used for smoke filling and temperature estimates where geometry permits.
CFD fire model
A field model solving the flow equations on a computational grid, used where geometry, smoke control or complex mixing make zone models inadequate.
Tenability criteria
Limits on visibility, temperature, radiant heat flux and toxic gas exposure used to judge whether occupants can escape without injury.
Buildings Ordinance Cap. 123
Hong Kong legislation controlling construction, alteration and use of buildings, administered by the Building Authority through the Buildings Department.
Fire Safety (Buildings) Ordinance
Hong Kong Cap. 572, requiring fire safety improvements to pre-specified composite and domestic buildings in respect of installations, escape and construction.
FSI Code of Practice
The Hong Kong code specifying minimum fire service installations and equipment and their inspection, testing and maintenance requirements.
Occupation permit
Approval allowing a building to be occupied, granted after satisfactory completion and acceptance testing of required fire service installations.
Jockey pump
A small pump maintaining fire main pressure against minor leakage, preventing the main duty fire pump from starting on small pressure fluctuations.
Landing valve
A valved outlet on a fire main at each floor of a building, allowing the Fire Services Department to connect hose and obtain water at that level.
Staircase pressurisation
A smoke control method maintaining positive pressure in an escape stair relative to accommodation, with relief and door force limits.
Fire service water tank
A dedicated stored water supply of specified effective capacity, excluding unusable reserve, providing the design flow for the required duration.
V-pattern burn
A fire damage pattern fanning upward from a point of origin, used with other evidence to indicate fire direction but never conclusive alone.
Char depth analysis
Estimation of fire duration and intensity from the depth of charring on timber, interpreted alongside ventilation and fuel conditions.
Accelerant residue analysis
Laboratory examination, commonly by GC-MS, of fire debris for ignitable liquid residues, which supports but does not alone prove deliberate ignition.
Post-fire structural assessment
Engineering evaluation of residual capacity after fire, considering reduced sections, elevated-temperature strength loss, spalling and distortion before reoccupation.
Certifying engineer duty
Personal professional responsibility for work signed or certified, requiring actual review and the ability to defend the design and its assumptions.