Mistake 1

Reading flue-gas O2 or CO2 without also recording the excess-air and stack-temperature context, then declaring the appliance 'in spec' from a single number.

Candidates memorize target CO2/O2 windows and treat them as pass/fail absolutes, forgetting that the correct value shifts with fuel type, burner design, and dilution air from draft hoods or barometric dampers.

What to do instead

For every combustion test, record fuel type, steady-state stack temperature, O2, CO2, CO (air-free and as-measured), and ambient CO. Interpret O2/CO2 only alongside stack temp and draft, and state whether the sample was taken before or after any dilution device.

Mistake 2

Confusing as-measured CO with air-free (undiluted) CO, or reporting one while quoting limits that apply to the other.

Meters display both values and the labels look similar; candidates don't internalize that dilution air from a draft hood lowers as-measured CO and can mask a real problem.

What to do instead

Always convert to air-free CO using the measured O2 (or CO2) before comparing to any limit, and state the conversion basis in the answer. Know that air-free CO is always equal to or higher than as-measured CO when dilution is present.

Mistake 3

Assuming a Category I appliance needs no venting review because 'it worked before,' skipping checks of vent connector slope, rise, lateral run, and whether the connector is single-wall or double-wall in an unconditioned space.

Venting questions emphasize code tables that candidates skim; field habits favor 'it's already installed' thinking over verifying slope back to the appliance and proper rise.

What to do instead

Memorize the direction of slope (upward toward the chimney, minimum rise per foot), the limits on connector length and number of elbows, and the rule that single-wall connectors need greater clearance to combustibles than double-wall. Apply the table values rather than intuition.

Mistake 4

Diagnosing a draft problem by checking only the chimney and ignoring the competition for air inside the space-exhaust fans, clothes dryers, and other appliances.

Candidates focus on the flue path and forget that depressurization from other fans can reverse draft even with a clean, correctly sized chimney.

What to do instead

Use worst-case depressurization testing: operate all exhaust fans and dryers, then measure pressure in the combustion appliance zone and confirm draft at the appliance. If the zone goes negative enough to spill, address the air supply before blaming the vent.

Mistake 5

Sizing combustion air openings from memory or by 'one square inch per 1,000 BTU' alone, without distinguishing indoor-air, outdoor-air, horizontal-duct, and vertical-duct methods.

The rule of thumb is widely repeated but the code tables differ by method, by whether the space is confined or unconfined, and by free area of louvers and grilles.

What to do instead

Identify whether the space is confined or unconfined and which air-source method applies, then use the correct table. Apply free-area corrections for louvers and screens rather than using the gross opening size.

Mistake 6

Testing gas line pressure at the wrong point-measuring manifold pressure at the meter, or supply pressure at the burner orifice-and treating the two as interchangeable.

Both are 'gas pressure' readings; candidates don't separate static supply pressure (inlet) from manifold (outlet) pressure and the conditions under which each is measured.

What to do instead

State clearly which pressure is being measured and where the tap is. Verify inlet pressure with the appliance running and other appliances off, then verify manifold pressure per the rating plate. Know that a manifold reading taken while other appliances cycle can mislead.

Mistake 7

Setting up a burner by adjusting only the primary air shutter to make the flame 'look right,' ignoring flame signal, ignition timing, and combustion readings after the adjustment.

Visual flame appearance is intuitive and fast, and candidates underuse the meter and the flame-safeguard diagnostics after each change.

What to do instead

Treat setup as a measured sequence: verify gas pressure, set primary air, then confirm O2/CO2 and CO, then check flame signal strength and ignition trial/lockout timing. Recheck combustion after any air or gas adjustment, since each change shifts the others.

Mistake 8

Diagnosing intermittent lockouts by replacing the flame sensor or control board without first measuring flame current and verifying the sensor's position and grounding.

Parts-swapping is common field practice and the flame rectification circuit is poorly understood; candidates skip the microamp reading because it seems abstract.

What to do instead

Measure flame signal in microamps (or the manufacturer's specified units) and compare to the minimum. Check sensor rod position in the flame, cleanliness, ceramic integrity, and burner/chassis ground. Replace parts only after the signal is proven inadequate.

Mistake 9

Treating a CO alarm callback as a 'no reading, no problem' call and leaving without documenting ambient CO, air-free CO, draft, and spillage findings.

Alarms can be caused by transient backdrafting or by the alarm itself; candidates measure once at the appliance and skip the zone and ambient checks, then can't explain the event.

What to do instead

Follow a documented sequence: ambient CO in the space, worst-case depressurization, draft and spillage at each appliance, then combustion analysis. Record all values, note transient conditions (fans, doors, weather), and state the corrective action or referral.

Mistake 10

Tuning for efficiency by chasing the lowest stack temperature or highest CO2 without confirming the appliance is not condensing in a non-condensing vent or over-firing.

Efficiency numbers are the visible score, and candidates push them without checking vent material limits, flue-gas dew point, or that input rate matches the rating plate.

What to do instead

Verify input rate by clocking the meter before and after tuning, confirm the vent category and material can tolerate the resulting stack temperature, and keep CO and draft within limits. Efficiency gains that push flue gases below dew point in a Category I vent are a defect, not a win.