HVAC Excellence Master Combustion: Burner and Ignition System Setup and Troubleshooting

HVAC Excellence Master Combustion · Work through your exam, one topic at a time.

All guide sections

Burner and Ignition System Setup and Troubleshooting

Setup

  • Set manifold pressure with the burner firing and steady.
  • Clock the meter: Btu/h = ft3 timed x 3,600 / seconds x heating value.
  • Primary air shutters: yellow tipping means too little primary air; a lifting, blowing flame means too much.
  • Verify inlet pressure under load, with other appliances running.

Ignition and proving

  • Standing pilot, intermittent pilot, hot-surface ignition, and direct spark each follow a sequence: call for heat, inducer, pressure switch proved, ignition, gas valve opens, flame proved, blower.
  • Flame rectification needs flame touching the sensor, a clean sensor, and a good ground. Typical flame current is 1-6 microamps; below roughly 0.5-1.0 microamp the module drops out.
  • Thermocouples generate about 25-30 mV open-circuit and 10-15 mV under load.
  • Clean flame sensors with steel wool, never sandpaper.

Worked example

An 80,000 Btu/h furnace clocks 1.0 ft3 in 45 seconds at 1,000 Btu/ft3: 1 x (3,600 / 45) x 1,000 = 80,000 Btu/h, correct. At 36 seconds the same meter test gives 100,000 Btu/h, 25% overfired, pointing to an oversized orifice or excessive manifold pressure rather than an ignition fault.

Traps

  • Adjusting manifold pressure with the burner off.
  • Jumping a pressure switch to "test" it.
  • Replacing a gas valve before checking flame current and ground.
  • Assuming a glowing igniter is a good igniter; check resistance and current draw.
  • Ignoring the inducer and pressure-switch sequence when the fault looks like ignition.