HVAC Excellence Master HP · Put your knowledge to work in context.

All case studies

Cold-Climate Heat Pump With Excessive Auxiliary Heat

A 2,000 ft² house has a 3-ton variable-speed heat pump with a 10 kW electric auxiliary heater. The thermostat is configured with an auxiliary heat lockout at 40°F outdoor and a compressor lockout at 0°F. At 20°F outdoor, the homeowner complains that auxiliary heat runs almost continuously and electric bills have doubled. The technician measures 68°F return air, 92°F supply air, and 1,050 cfm airflow. Manufacturer data show the heat pump capacity at 20°F is 22,000 Btu/h and at 17°F is 20,000 Btu/h. A block load calculation shows the house load is 24,000 Btu/h at 20°F and 28,000 Btu/h at 17°F. The outdoor temperature sensor reads 20°F and is within 1°F of a calibrated thermometer. The refrigerant charge was last verified in cooling mode at 10°F subcooling, which matches the manufacturer’s table.

1. Is the 40°F auxiliary lockout appropriate? Determine the balance point and the actual auxiliary heat needed at 20°F.

Read the worked answer

No. At 20°F the heat pump delivers 22,000 Btu/h and the load is 24,000 Btu/h, so the heat pump covers about 92% of the load. The deficit is 2,000 Btu/h, which is only about 0.59 kW. A 10 kW auxiliary heater adds about 34,000 Btu/h, far more than the deficit, so continuous auxiliary operation explains the high bill.

The balance point is where capacity equals load. Interpolating, capacity falls about 667 Btu/h per °F and load rises about 1,333 Btu/h per °F as it gets colder. At 20°F the deficit is 2,000 Btu/h; moving warmer reduces the deficit and moving colder increases it. The balance point is approximately 23°F. A 40°F auxiliary lockout is therefore well above the balance point and permits resistance heat when the heat pump can handle the load. Set the auxiliary lockout near the balance point, about 20–23°F, with a small allowance for defrost and recovery.

2. The supply-to-return temperature difference is 24°F at 1,050 cfm. What does this tell you, and what checks would you perform?

Read the worked answer

Sensible heat is approximately 1.08 × 1,050 × 24 = 27,200 Btu/h. The heat pump alone at 20°F is rated 22,000 Btu/h, so the extra roughly 5,200 Btu/h is consistent with auxiliary heat being energized. If auxiliary heat were confirmed off, a 27,200 Btu/h output would exceed the heat pump’s capacity and point to a measurement or airflow problem, not normal operation.

Check the auxiliary heat amp draw at the sequencer or breaker, verify the thermostat is actually calling auxiliary, and confirm the blower is set for the correct airflow. At 1,050 cfm the system is at 350 cfm/ton, which is acceptable for many units but near the low end; verify static pressure, filter condition, and coil cleanliness. Do not adjust charge by heating-mode superheat alone. Use the manufacturer’s heating charging chart or weigh-in method, and confirm the cooling-mode subcooling was taken at the correct conditions.

3. Recommend thermostat settings and a test sequence to reduce auxiliary use without sacrificing comfort.

Read the worked answer

Set the auxiliary lockout near the balance point, about 20–23°F, and set the compressor lockout at the manufacturer’s minimum operating temperature. If the thermostat supports staging, configure auxiliary as emergency/second stage only, not as primary heat. Enable adaptive recovery only if it does not force unnecessary auxiliary heat. Verify the thermostat is set for heat pump with electric backup, not for a conventional electric furnace.

Test sequence: at 25°F outdoor, lock out auxiliary and confirm the heat pump holds setpoint. At 15°F, allow auxiliary and confirm it stages on only as needed. Measure supply temperature and runtime in both tests. During defrost, auxiliary must operate to temper supply air, so do not disable it completely. If the 10 kW heater is single-stage and causes temperature swings, consider staging it or replacing it with a smaller staged bank. Finally, review the load calculation; a 28,000 Btu/h load at 17°F leaves little margin, so air sealing or insulation may be more cost-effective than relying on resistance heat.