Sensible heat formula
Q = 1.08 × CFM × ΔT for standard air at sea level. Use it to estimate airflow from a measured temperature rise or drop across a coil.
Latent heat formula
Q = 0.68 × CFM × Δgrains. It estimates moisture removal capacity and is used with the sensible equation to find total coil load.
Superheat definition
Actual suction line temperature minus the saturated suction temperature at the same pressure. Target 8–12 °F at the evaporator outlet on fixed-orifice systems.
Subcooling definition
Saturated condensing temperature minus liquid line temperature. Target 8–12 °F on TXV systems; low subcooling suggests undercharge or a liquid line restriction.
Ton of refrigeration
One ton equals 12,000 BTU per hour, or 200 BTU per minute. A 3-ton system therefore moves about 36,000 BTU/h at rated conditions.
Standard airflow rule
Approximately 400 CFM per nominal ton. A 2.5-ton system should move about 1,000 CFM; below 350 CFM/ton risks coil freeze-up.
Pressure to head conversion
One psi equals 2.31 feet of water column. Use it to convert static pressure readings to inches of water for duct and fan calculations.
Recovery versus recycling
Recovery removes refrigerant to a container. Recycling cleans it for reuse in the same equipment. Reclaim restores it to ARI 700 purity for any system.
SEER2 versus SEER
SEER2 uses the same 0.5 in. w.c. blower static but higher external static, so SEER2 ratings run about 4–5 percent below SEER for the same equipment.
HSPF2 versus HSPF
HSPF2 uses a 5 °F colder outdoor temperature bin than HSPF, so HSPF2 values run roughly 15 percent lower for the same heat pump.
Undercharge symptoms
Low subcooling, high superheat, reduced capacity, and elevated discharge temperature. Confirm with superheat before adding refrigerant to a fixed-orifice system.
Overcharge symptoms
High subcooling and low superheat, often with elevated head pressure and compressor current. On TXV systems, subcooling is the primary charge indicator.
Low airflow effects
Below 350 CFM/ton, sensible capacity drops and the evaporator can freeze. Above 450 CFM/ton, latent removal falls and blower power rises.
Temperature split check
A tuned 3-ton split system holds 18–22 °F across the coil at 400 CFM/ton with an 80 °F return. A low split suggests low airflow or low charge.
Duct leakage limit
The 2021 IECC caps duct leakage at 4 CFM per 100 ft² of conditioned floor area at 25 Pa for new homes. Older homes often test 15–30 percent.
Economizer high limit
ASHRAE 90.1 sets 65–75 °F for differential dry-bulb changeover. Verify the setpoint with a calibrated reference thermometer before adjusting.
EPA 608 certification
Required to buy or handle ozone-depleting refrigerants. Type I covers small appliances, Type II high-pressure, Type III low-pressure, and Type IV all.
A2L refrigerant class
Lower flammability, low toxicity. R-32 and R-454B are A2L and require ignition-source controls, leak detection, and charge limits per ASHRAE 15.
Venting prohibition
Releasing refrigerant to the atmosphere is illegal. Recovered refrigerant must be recycled, reclaimed, or destroyed, and cylinders must never exceed 80 percent fill.
Leak repair deadline
For appliances with 5 or more lb charge, leaks must be repaired within 30 days of discovery. Comfort cooling over 50 lb also requires verification within 10 days.
R-22 phase-out
Production and import ended January 1, 2020. Reclaimed R-22 remains legal for servicing existing equipment but cannot be used in new equipment.
GWP values
R-410A ≈ 2,088; R-32 ≈ 675; R-454B ≈ 466; R-134a ≈ 1,430; R-1234yf < 1. The AIM Act targets an 85 percent HFC reduction by 2036.
Refrigerant PPE
Safety glasses, refrigerant-rated gloves, and a calibrated leak detector. Never use an open flame to detect leaks, especially with A2L refrigerants.
Ohm's law
V = I × R, and power P = V × I × PF. A 240 V single-phase compressor at 12 A and 0.9 PF draws about 2,592 W.
Locked rotor amps
LRA is typically 5–6 times running load amps. A compressor drawing LRA and tripping on overload indicates a seized or shorted winding.
Run capacitor tolerance
A run capacitor more than 10 percent below nameplate microfarads should be replaced. Measure with a meter rated for the capacitor's value.
Thermostat wiring calls
R to W calls heat, R to Y calls cool, R to G calls fan. A blown low-voltage fuse often follows a shorted contactor coil or miswired thermostat.
Gas furnace sequence
Call for heat, inducer proves via pressure switch, igniter energizes, gas valve opens, flame sensor proves, then the blower delays on.
Primary diagnostics
Superheat and subcooling are the primary readings. Static pressure across the coil confirms airflow, and amp draw confirms mechanical load.
True-RMS meter use
Use a true-RMS multimeter and clamp meter. Verify 24 V at the transformer secondary before condemning a control board.
Start relay check
Measure resistance across the start winding. Infinity means an open winding and zero means a short; either reading condemns the compressor.