HVAC Excellence Master HP flashcards
HVAC Excellence Master HP · Build recall with a focused review session.
31 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Sensible heat formula
- Q = 1.08 × CFM × ΔT for standard air at sea level. Use it to estimate airflow from a measured temperature rise or drop across a coil.
- Latent heat formula
- Q = 0.68 × CFM × Δgrains. It estimates moisture removal capacity and is used with the sensible equation to find total coil load.
- Superheat definition
- Actual suction line temperature minus the saturated suction temperature at the same pressure. Target 8–12 °F at the evaporator outlet on fixed-orifice systems.
- Subcooling definition
- Saturated condensing temperature minus liquid line temperature. Target 8–12 °F on TXV systems; low subcooling suggests undercharge or a liquid line restriction.
- Ton of refrigeration
- One ton equals 12,000 BTU per hour, or 200 BTU per minute. A 3-ton system therefore moves about 36,000 BTU/h at rated conditions.
- Standard airflow rule
- Approximately 400 CFM per nominal ton. A 2.5-ton system should move about 1,000 CFM; below 350 CFM/ton risks coil freeze-up.
- Pressure to head conversion
- One psi equals 2.31 feet of water column. Use it to convert static pressure readings to inches of water for duct and fan calculations.
- Recovery versus recycling
- Recovery removes refrigerant to a container. Recycling cleans it for reuse in the same equipment. Reclaim restores it to ARI 700 purity for any system.
- SEER2 versus SEER
- SEER2 uses the same 0.5 in. w.c. blower static but higher external static, so SEER2 ratings run about 4–5 percent below SEER for the same equipment.
- HSPF2 versus HSPF
- HSPF2 uses a 5 °F colder outdoor temperature bin than HSPF, so HSPF2 values run roughly 15 percent lower for the same heat pump.
- Undercharge symptoms
- Low subcooling, high superheat, reduced capacity, and elevated discharge temperature. Confirm with superheat before adding refrigerant to a fixed-orifice system.
- Overcharge symptoms
- High subcooling and low superheat, often with elevated head pressure and compressor current. On TXV systems, subcooling is the primary charge indicator.
- Low airflow effects
- Below 350 CFM/ton, sensible capacity drops and the evaporator can freeze. Above 450 CFM/ton, latent removal falls and blower power rises.
- Temperature split check
- A tuned 3-ton split system holds 18–22 °F across the coil at 400 CFM/ton with an 80 °F return. A low split suggests low airflow or low charge.
- Duct leakage limit
- The 2021 IECC caps duct leakage at 4 CFM per 100 ft² of conditioned floor area at 25 Pa for new homes. Older homes often test 15–30 percent.
- Economizer high limit
- ASHRAE 90.1 sets 65–75 °F for differential dry-bulb changeover. Verify the setpoint with a calibrated reference thermometer before adjusting.
- EPA 608 certification
- Required to buy or handle ozone-depleting refrigerants. Type I covers small appliances, Type II high-pressure, Type III low-pressure, and Type IV all.
- A2L refrigerant class
- Lower flammability, low toxicity. R-32 and R-454B are A2L and require ignition-source controls, leak detection, and charge limits per ASHRAE 15.
- Venting prohibition
- Releasing refrigerant to the atmosphere is illegal. Recovered refrigerant must be recycled, reclaimed, or destroyed, and cylinders must never exceed 80 percent fill.
- Leak repair deadline
- For appliances with 5 or more lb charge, leaks must be repaired within 30 days of discovery. Comfort cooling over 50 lb also requires verification within 10 days.
- R-22 phase-out
- Production and import ended January 1, 2020. Reclaimed R-22 remains legal for servicing existing equipment but cannot be used in new equipment.
- GWP values
- R-410A ≈ 2,088; R-32 ≈ 675; R-454B ≈ 466; R-134a ≈ 1,430; R-1234yf < 1. The AIM Act targets an 85 percent HFC reduction by 2036.
- Refrigerant PPE
- Safety glasses, refrigerant-rated gloves, and a calibrated leak detector. Never use an open flame to detect leaks, especially with A2L refrigerants.
- Ohm's law
- V = I × R, and power P = V × I × PF. A 240 V single-phase compressor at 12 A and 0.9 PF draws about 2,592 W.
- Locked rotor amps
- LRA is typically 5–6 times running load amps. A compressor drawing LRA and tripping on overload indicates a seized or shorted winding.
- Run capacitor tolerance
- A run capacitor more than 10 percent below nameplate microfarads should be replaced. Measure with a meter rated for the capacitor's value.
- Thermostat wiring calls
- R to W calls heat, R to Y calls cool, R to G calls fan. A blown low-voltage fuse often follows a shorted contactor coil or miswired thermostat.
- Gas furnace sequence
- Call for heat, inducer proves via pressure switch, igniter energizes, gas valve opens, flame sensor proves, then the blower delays on.
- Primary diagnostics
- Superheat and subcooling are the primary readings. Static pressure across the coil confirms airflow, and amp draw confirms mechanical load.
- True-RMS meter use
- Use a true-RMS multimeter and clamp meter. Verify 24 V at the transformer secondary before condemning a control board.
- Start relay check
- Measure resistance across the start winding. Infinity means an open winding and zero means a short; either reading condemns the compressor.