Mistake 1

Setting the combustion efficiency number by reading only the stack temperature and smoke spot, then declaring the unit 'efficient' without measuring CO2 or O2, so the candidate reports a made-up efficiency and cannot explain the excess-air tradeoff.

Candidates memorize 'low stack temp plus zero smoke equals good' from field habit and skip the CO2/O2 reading that actually drives the efficiency calculation; they also confuse gross and steady-state efficiency.

What to do instead

Practice the full Bacharach/stack-plus-CO2 sequence on paper: record smoke, CO2 (or O2), stack temp, and net temp, then compute steady-state efficiency from a table. Drill the relationship that raising excess air lowers CO2 and raises stack loss, and be able to state why zero smoke with high CO2 can still mean poor efficiency.

Mistake 2

Adjusting the burner air shutter or electrode settings to make a flame look 'nice' instead of setting them to the manufacturer's specified dimensions, then answering exam questions from that improvised setting.

Hands-on apprentices are taught by feel on one burner type and generalize; exam items ask for specified nozzle-to-electrode distances, insertion depth, and head settings that vary by burner model.

What to do instead

Memorize the standard starting specs (typical electrode gap, nozzle-to-electrode setback, head/static plate position) and, more importantly, learn the rule: always use the burner manufacturer's spec sheet for that model. On the exam, treat 'looks good' as a distractor and choose the specified measurement.

Mistake 3

Choosing a nozzle by GPH alone and ignoring spray angle, pattern, and the pump pressure that produces the rated flow, so the candidate selects a 1.00 GPH nozzle for a job that needs a different angle or a derated flow at 100 psi.

Nozzle ratings are published at 100 psi, and flow changes with the square root of pressure; candidates forget this and also overlook that hollow vs. solid pattern and 45/60/70/80 degree angle must match the combustion chamber.

What to do instead

Drill the derating math (flow varies as the square root of pressure ratio) and the pattern/angle selection rules tied to chamber shape and firing rate. Practice reading a nozzle catalog line: capacity at 100 psi, angle, pattern, and filter type, and match all four to the appliance spec.

Mistake 4

Diagnosing a no-heat call as a bad transformer or control without first proving flame presence and cad cell resistance, so the candidate replaces parts instead of following the primary control's lockout sequence.

The cad cell and primary control sequence (prepurge, trial for ignition, lockout timing) is abstract on paper, and candidates jump to the component they replaced last time on the job.

What to do instead

Build a mental ladder: call for heat, limit closed, primary control powers burner, ignition and oil valve, flame sensed, cad cell resistance drops to the specified range (roughly under 1,600 ohms in good light, much higher when dark). Practice stating what a steady 1,600+ ohm reading during burn means and which step to test next.

Mistake 5

Mixing up the roles of the primary safety control, the high-limit aquastat, and the low-limit/circulator control on a boiler, so the candidate answers that the high limit starts the circulator or that the low limit is the safety lockout.

The three controls share a single aquastat housing on many boilers and their setpoints interact; candidates memorize one boiler's wiring and misapply it to exam scenarios.

What to do instead

Learn each device by function and typical setpoint: high limit cuts burner off at the upper temperature (often 180-200 F) and is a safety, low limit maintains boiler temperature and starts/stops the circulator (often 140-160 F with differential), and the primary control provides flame safety and lockout. Practice tracing which device opens which circuit in a described fault.

Mistake 6

Ignoring tank and oil supply issues such as a clogged oil filter, failed pump coupling, or air in the suction line, and instead blaming the burner's ignition system for an intermittent lockout.

Intermittent lockouts look electrical, and candidates underweight the one-pipe/two-pipe suction rules, lift limits, and the need for a bypass plug on two-pipe systems.

What to do instead

Review the oil delivery path: tank, filter, shutoff, suction line, pump, nozzle. Know when a two-pipe system requires the bypass plug, the maximum lift for a one-pipe system, and the symptoms of a partially clogged filter (delayed ignition, rumbling, sooting). On exam items, check supply-side causes before condemning the ignition transformer.

Mistake 7

Treating a puffback or heavy soot as a nozzle-only problem and not linking it to delayed ignition causes such as a wrong electrode gap, oil spraying before ignition, or a cold, wet chamber.

Puffbacks are dramatic and candidates fixate on the visible soot; the underlying sequence of oil accumulation then late ignition is the actual exam concept.

What to do instead

Learn the delayed-ignition chain: oil enters before spark, pools, then ignites explosively. Map each cause (electrode position, weak spark, dirty nozzle strainer, low pump pressure, long prepurge with no ignition) to the symptom. Practice explaining why correcting the nozzle alone will not prevent a repeat puffback if the ignition timing is wrong.

Mistake 8

Skipping the draft and venting check, so the candidate cannot say whether the appliance is in a confined space, what draft reading is expected in the flue, or why a blocked chimney causes spillage and CO.

Draft is invisible and often treated as a formality; candidates also confuse draft pressure with stack temperature and do not know typical overfire or flue draft values.

What to do instead

Study the venting rules: combustion air requirements for confined vs. unconfined spaces, barometric draft regulator function, and expected draft in the flue (a small negative pressure, roughly -0.02 to -0.04 in. w.c. at the breech for many residential units). Practice explaining spillage at the draft hood as a CO hazard and the test that confirms it.

Mistake 9

Confusing CO2 readings with CO readings or misreading a combustion analyzer, then answering that a high CO2 means high carbon monoxide, or that a CO reading of a few ppm is always a failure.

The two gases share an abbreviation pattern and analyzer screens show both; candidates without analyzer time invert their meanings.

What to do instead

Lock in definitions: CO2 is a normal product of complete combustion and tracks excess air inversely; CO is a product of incomplete combustion and is the safety concern, with accepted limits far lower than CO2 percentages. Practice reading a sample analyzer printout, identifying which number indicates excess air and which indicates incomplete combustion, and stating the corrective action for each.

Mistake 10

Answering oil heat safety and code items from generic gas-furnace knowledge, such as clearance to combustibles, oil tank location and venting, or the required oil line shutoff, without applying oil-specific requirements.

Many candidates cross-train on gas equipment and assume the rules transfer; oil tanks, fill/vent pipes, and emergency shutoffs have their own installation rules.

What to do instead

Review oil-specific installation basics: tank support and clearance, fill and vent pipe sizing and termination, the oil shutoff valve at the burner, and clearance-to-combustible tables for oil appliances. When an item describes a tank or line, ask 'is this an oil-specific rule?' before choosing the gas-derived answer.