- Superheat definition
- Suction line temperature minus the evaporator saturation temperature, measured at the evaporator outlet. It confirms the evaporator is fully fed with liquid refrigerant without flooding the compressor.
- Subcooling definition
- Condenser saturation temperature minus the liquid line temperature. It proves the condenser has fully liquefied the refrigerant and that the liquid line holds a solid column of liquid.
- Ohm's law in HVAC
- E equals I times R, and power P equals E times I. Technicians use these to compute expected current draw, verify winding resistance, and diagnose open or shorted circuits.
- Capacitor tolerance rule
- A run capacitor reading within plus or minus ten percent of its nameplate microfarad value is acceptable. Bulging, leaking, or out-of-tolerance units are replaced rather than re-rated.
- Locked rotor amps
- The current a motor draws when the rotor cannot turn, typically five to seven times rated load amps. Reading LRA with no rotation points to a start circuit or winding failure.
- Nitrogen purge purpose
- Flowing dry nitrogen through piping during brazing displaces oxygen, preventing internal scale and copper oxide that would later clog the metering device and contaminate the compressor.
- Deep vacuum target
- Evacuation below 500 microns that holds after the pump is isolated. A rising micron reading indicates residual moisture or an unresolved leak in the circuit.
- EPA 608 Type I scope
- Covers small appliances containing five pounds or less of refrigerant, including household refrigerators, freezers, and window air conditioners, and allows system-dependent recovery on many of them.
- EPA 608 Type II scope
- Applies to high-pressure appliances other than small appliances, such as split air conditioners and commercial refrigeration. It requires certified recovery equipment and documented evacuation levels.
- R-410A pressure characteristic
- A near-azeotropic blend of R-32 and R-125 operating at roughly fifty to seventy percent higher pressures than R-22, so gauges, hoses, and recovery machines must be rated for it.
- Liquid charging of blends
- Near-azeotropic blends like R-410A must be charged as liquid from the cylinder. Vapor charging can fractionate the mixture and leave the system with an incorrect composition.
- Cylinder fill limit
- Refrigerant cylinders are never filled above eighty percent liquid by volume. Leaving vapor space allows for thermal expansion and prevents hydrostatic rupture of the cylinder.
- Leak detection sequence
- Start with an electronic detector, confirm with soap bubbles, then pressure test with dry nitrogen and a trace of refrigerant. Each step narrows the location before repair.
- Sensible airflow formula
- CFM equals sensible BTUH divided by 1.08 times the temperature difference in Fahrenheit. It converts measured air temperature change into airflow at standard air density.
- External static pressure
- The total pressure the blower works against, measured across the return and supply taps. It is compared to the fan performance table to confirm delivered airflow.
- ECM constant CFM motor
- An electronically commutated motor programmed for constant airflow increases torque as static pressure rises. It maintains delivered CFM within limits instead of slowing like a PSC motor.
- TXV superheat adjustment
- Turning the adjusting stem clockwise reduces refrigerant flow and raises superheat; counterclockwise increases flow and lowers superheat. Adjust in small increments and allow stabilization.
- Heat pump balance point
- The outdoor temperature where heat pump capacity equals building heat loss. Below it, auxiliary or emergency heat must make up the difference to hold indoor temperature.
- Defrost termination check
- Verify the coil sensor, timer, and board terminate defrost before the coil overheats, and that the reversing valve shifts properly on demand defrost systems.
- Dilution air baseline
- The classic draft-hood standard of one hundred cubic feet of carbon-dioxide-free dilution air per cubic foot of flue gas, used to interpret combustion test readings.
- VRF charge verification
- Variable refrigerant flow systems are charged using subcooling targets plus recorded total and branch pipe lengths. Weigh-in per manufacturer tables is the primary method.
- Inverter compressor module
- The drive rectifies AC to a DC bus and switches an intelligent power module to vary compressor speed. Check bus voltage and stored fault codes before replacing parts.
- Chiller approach temperature
- Leaving chilled water temperature minus evaporating refrigerant temperature. A rising approach signals fouling in the evaporator tubes or non-condensable gases in the circuit.
- Economizer changeover
- The outdoor condition at which the economizer enables free cooling. Verify enthalpy or dry-bulb setpoint, actuator stroke, and damper linkage before blaming the controller.
- BACnet object types
- Analog input, analog output, binary input, binary output, and analog value objects carry points between devices. Document each point and its instance number before commissioning integration.
- Floating suction control
- A refrigeration rack strategy that raises suction pressure to the highest level that still holds case product temperature, cutting compressor energy while protecting product quality.
- Item difficulty index
- The proportion of examinees answering an item correctly. Values around 0.30 to 0.70 usually discriminate best between stronger and weaker candidates on classroom tests.
- Point-biserial flag
- A correlation between item score and total test score. A negative value means strong students missed it while weak students passed, usually indicating a miskeyed or ambiguous item.
- Distractor requirement
- A wrong answer option must be plausible to someone with incomplete knowledge yet unambiguously incorrect. Only one option may be defensible as the best answer.
- Formative versus summative
- Formative assessment is given during instruction to guide teaching adjustments. Summative assessment comes at the end of a unit or course to certify achievement.
- Rubric inter-rater agreement
- Performance tasks are scored against observable criteria, and multiple raters score sample work first. Agreement is confirmed before scores are released to candidates.
- Lab safety prerequisite
- Before any hands-on refrigerant work, students don goggles and gloves, confirm ventilation, and set up recovery equipment. Safety instruction precedes tool use in every lab session.