Professional Level certifications (e.g., Air Conditioning, Electrical, Gas Heating, Heat Pump, Commercial Refrigeration) target experienced technicians. Questions probe advanced troubleshooting, system performance, combustion analysis, and electrical diagnostics.
Core rules and concepts
- Psychrometrics: Dry-bulb (sensible), wet-bulb (evaporative), dew point (condensation). Use a psychrometric chart to calculate sensible and latent loads.
- Airflow: Measure static pressure with a manometer; calculate CFM from fan curves or using duct traverse. Target 400 CFM per ton for cooling.
- Combustion: For gas furnaces, measure CO (target <100 ppm), CO2 (8–10%), and draft. Yellow flame + high CO = incomplete combustion-check primary air.
- Electrical: Test capacitors under load (microfarads), check relays and contactors, measure motor windings. Use a clamp meter for current.
- Charging: Weigh-in for new systems, superheat for fixed orifice, subcooling for TXV (target 8–12°F).
Worked example
A gas furnace produces a yellow, lazy flame and a CO reading of 400 ppm. What is the diagnosis? Reasoning: Yellow flame indicates insufficient primary air or a dirty burner. High CO confirms incomplete combustion. First, check the burner for debris and verify the air shutter adjustment. If clean, inspect the heat exchanger for cracks (a safety hazard). Do not leave the system running until CO is below 100 ppm.
Traps that cost marks
- Using superheat method on a TXV system (should use subcooling).
- Ignoring static pressure when diagnosing airflow-high static means duct restriction.
- Testing a capacitor without discharging it (safety and accuracy).
- Forgetting to check combustion air openings in a confined space.