HVAC Excellence flashcards
HVAC Excellence · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Superheat definition
- Suction line temperature minus the saturation temperature at the measured suction pressure; used to verify charge on a fixed-orifice system and to check TXV operation.
- Subcooling definition
- Liquid line temperature subtracted from the saturation temperature at the liquid line pressure. Measured at the condenser outlet, it verifies charge on a TXV system.
- R-410A liquid charging
- R-410A is a near-azeotropic blend and must be removed from the cylinder as a liquid; vapor charging can fractionate the blend and change its composition.
- Recovery cylinder fill limit
- Cylinders may be filled to no more than 80 percent of their capacity by weight, so liquid expansion at high ambient temperature does not hydrostatically rupture the cylinder.
- EPA 608 evacuation levels
- Targets are 0 inches Hg vacuum for pre-1993 or under-5-pound systems, 10 inches for 5 to 25 pounds, 15 inches for over 25 pounds, and 20 inches for very-high-pressure refrigerants.
- Ohm's law formula
- E = I × R, meaning voltage equals current times resistance. Rearranged, I = E ÷ R and R = E ÷ I, which lets you solve for an unknown circuit value.
- Run capacitor tolerance
- A run capacitor is acceptable when its measured microfarad value is within about plus or minus 10 percent of the nameplate rating; bulging or leaking means replacement.
- Thermostat terminal letters
- R supplies 24-volt power, W calls for heat, Y calls for cooling, G runs the indoor fan, and O or B energizes the reversing valve on a heat pump.
- Voltage imbalance limit
- Three-phase supply voltage imbalance should not exceed 2 percent; divide the greatest deviation from average by the average and multiply by 100 to find it.
- Compressor winding resistance test
- On a single-phase compressor, run-to-common plus start-to-common resistance equals run-to-start; a large deviation or infinite reading indicates a damaged winding.
- Complete combustion equation
- Methane burns as CH4 + 2O2 producing CO2 + 2H2O. Each cubic foot of natural gas needs roughly 10 cubic feet of air for stoichiometric combustion.
- Natural gas manifold pressure
- Most natural gas appliances are set to about 3.5 inches water column at the manifold, while propane appliances typically run 10 to 11 inches water column.
- Flame rectification current
- A flame sensor proves ignition by passing a small DC current through the flame; readings of roughly 1 to 6 microamps indicate a healthy signal on most controls.
- Natural draft flue pressure
- An atmospheric burner with a natural-draft vent typically shows about 0.02 to 0.04 inches water column negative pressure in the flue, read with a digital manometer.
- Furnace temperature rise
- Supply air temperature minus return air temperature, compared against the nameplate range of about 35 to 65 degrees Fahrenheit; values outside that range indicate an airflow problem.
- Sensible heat airflow formula
- BTU/h = 1.08 × CFM × ΔT for standard air. Rearranged, CFM = BTU/h ÷ (1.08 × ΔT), which is how airflow is checked from a measured temperature change.
- Fan law for static pressure
- Static pressure changes with the square of the speed change, so a 20 percent increase in blower speed raises static pressure by roughly 44 percent while airflow rises only 20 percent.
- Nominal cooling airflow
- Roughly 400 CFM per ton of cooling capacity is the nominal design airflow; humid climates often use about 350 CFM per ton to improve moisture removal.
- Velocity pressure formula
- VP = (V ÷ 4005)² for standard air at 0.075 pounds per cubic foot; velocity in feet per minute is found with V = 4005 × √VP.
- Blower door test pressure
- A blower door measures envelope leakage at 50 pascals, and ACH50 equals CFM50 times 60 divided by the conditioned volume in cubic feet.
- High performance duct leakage limit
- High-performance programs commonly cap duct leakage at about 6 CFM25 per 100 square feet of conditioned floor area, measured with a duct blaster at 25 pascals.
- Duct leakage to outside
- A duct blaster pressurizes the duct system to 25 pascals and reads total leakage in CFM25; subtracting leakage to outside leaves leakage into conditioned space.
- Tight envelope target
- A well-sealed new house often targets 3 ACH50 or less, and natural infiltration can be estimated roughly as CFM50 divided by 20.
- Delta T across evaporator
- Air temperature drop across a wet evaporator coil is typically 15 to 22 degrees Fahrenheit, depending on indoor wet-bulb; a low drop with full charge suggests low airflow.
- Condenser approach method
- Approach temperature is the saturated condensing temperature minus outdoor ambient air temperature; typical values run about 10 to 15 degrees Fahrenheit at design conditions.
- Sensible heat ratio
- SHR equals sensible capacity divided by total capacity. Residential cooling typically runs about 0.70 to 0.75, dropping when the coil removes more moisture.
- AFUE definition
- Annual Fuel Utilization Efficiency is annual heat output divided by annual energy input, expressed as a percentage; non-condensing furnaces typically rate near 80 percent.
- High head pressure causes
- A dirty condenser coil, overcharge, non-condensable air, high outdoor ambient temperature, or a failing condenser fan motor will all push head pressure above normal.
- Undercharge symptoms
- High superheat with low subcooling, low suction pressure, and low compressor amp draw indicate a system short of refrigerant; confirm by weighing in the charge.
- Condensing furnace venting
- Furnaces rated 90 percent AFUE or higher condense flue gas in a secondary heat exchanger and vent through PVC pipe because the flue gas leaves cool enough to condense.
- Non-condensable symptoms
- High head pressure together with high subcooling, a bubbly sight glass, and above-normal discharge temperature points to air in the system, requiring recovery and evacuation.
- SEER2 rating basis
- SEER2 is seasonal efficiency measured at higher external static pressure test conditions than legacy SEER, so SEER2 values run roughly 4 to 5 percent lower for the same equipment.