Basement Bathroom Wet Vent Rejected

NBOPE Journeyperson Plumber · Put your knowledge to work in context.

All case studies

Basement Bathroom Wet Vent Rejected

A 1950s house is being remodeled with a new basement bathroom directly below the first-floor bath. The existing 3-inch cast-iron soil stack is 9 feet from the new group and runs full-size through the roof. The contractor has installed a 1.5-inch lavatory drain that connects to a 3-inch water-closet branch; the shower drain ties into the lavatory drain downstream of the lavatory trap. There are no individual vents. The lavatory trap arm is 8 feet, and the shower trap arm is 7 feet of 2-inch pipe. The contractor says the lavatory wet-vents the water closet because the lavatory is upstream and the drain is open to the stack. The inspector rejects the wet vent and also questions the lavatory trap-arm length. The homeowner wants to avoid opening the first-floor walls, and the contractor proposes an air-admittance valve under the lavatory as a quick fix.

1. Is the proposed wet vent valid? Explain the fixture order, pipe size, and venting requirements.

Read the worked answer

The wet vent is not valid as installed. A 1.5-in lavatory drain is too small to wet-vent a water closet; the wet-vent section must be at least 2 in, and the water closet must be downstream of the wet-vented fixtures. The shower cannot simply tie into the lavatory drain downstream of the lavatory trap and be considered vented; the arrangement must be a recognized wet vent, or each fixture must have its own vent. A workable layout is a 2-in line from the lavatory through the shower connection to the stack, with the water closet connecting downstream and the 2-in line continuing as the vent. The lavatory trap arm must be limited to 6 ft for 1.5-in pipe, or 8 ft if the lavatory drain is upsized to 2 in; the existing 8-ft 1.5-in arm is too long. The shower’s 7-ft 2-in trap arm is within the usual 8-ft limit, but only if the shower is properly vented.

2. Will an air-admittance valve solve the problem? Explain what an AAV can and cannot do here.

Read the worked answer

An AAV does not fix this. AAVs are listed mechanical vents for individual fixtures and are subject to local code restrictions; they do not create a wet vent, and they are not a substitute for venting a water closet. Even where an AAV is allowed for a lavatory, the water closet still needs a code-recognized vent. The reliable correction is to run a 2-in vent from the lavatory-and-shower branch to the existing stack above the fixtures, or to install individual vents. Keep any AAV accessible if one is used elsewhere, but do not bury it in a wall or use it as the only vent for the bathroom group.

3. The shower trap arm is 7 feet of 2-inch pipe and connects downstream of the lavatory trap. Is the shower trap arm itself acceptable? What other defect must be corrected?

Read the worked answer

The 7-ft shower trap arm is not the main defect; 2-in pipe is commonly allowed up to 8 ft from trap to vent. The defect is that the shower connects downstream of the lavatory trap without a proper vent. If the shower is wet-vented through a 2-in lavatory-and-shower line, that line must be sized and arranged as a wet vent; if not, give the shower an individual 2-in vent. Also check trap-arm slope: a 2-in trap arm at 1/4 in/ft over 7 ft falls 1.75 in, which is acceptable, but the trap weir must remain at the required distance above the vent connection. The lavatory’s 8-ft 1.5-in trap arm must be shortened or upsized to 2 in.