Ethylene Oxide Excursion in Sterile Processing With Pregnant Staff

IBFCSM CHEP · Put your knowledge to work in context.

All case studies

Ethylene Oxide Excursion in Sterile Processing With Pregnant Staff

A hospital's sterile processing department runs two 100% ethylene oxide (EtO) sterilizers in a 60 m2 room. Personal sampling over three consecutive shifts gives an 8-hour TWA of 0.8 ppm for the sterilizer operators, with a 12-minute excursion of 4.2 ppm during cartridge changes. Area sampling near the door gasket reads 0.3 ppm with the sterilizer idle. The room's design exhaust is 100 feet per minute face velocity at the hood; a recent measurement shows 78 fpm. The door gasket was replaced two weeks ago after a leak test failed. Three of five technicians report headache, eye irritation, and nausea; two describe symptoms persisting for three months. Two technicians are pregnant. The department has no written respiratory protection program and no medical surveillance. Surgery is scheduled at 07:30 tomorrow with 14 cases requiring EtO-sterilized instruments, and the alternative low-temperature system is at another campus 25 minutes away.

1. Interpret the exposure data against applicable limits and identify what the data do not tell you.

Read the worked answer

The 8-hour TWA of 0.8 ppm is below the OSHA permissible exposure limit of 1 ppm but above the 0.5 ppm action level. Crossing the action level is not a technicality: it triggers ongoing exposure monitoring and, under the EtO standard, medical surveillance obligations for employees exposed at or above the action level for 30 or more days per year. The excursion reading must be handled correctly - 4.2 ppm over 12 minutes is compared to the 5 ppm excursion limit averaged over 15 minutes, so calculate the actual 15-minute average rather than comparing an instantaneous value. NIOSH's recommended limits (0.1 ppm TWA and a 5 ppm 15-minute ceiling) are far more health-protective and should inform the target even though they are not the legal limit.

What the data do not tell you: whether non-operators in the room are exposed; what happens during gasket replacement and maintenance; whether the 0.3 ppm idle reading represents a continuing fugitive emission; and why face velocity is 78 fpm instead of 100. That last number is the most plausible explanation for the idle reading. Symptoms in three of five workers, plus two pregnancies, warrant action independent of compliance status.

2. Recommend the control strategy in order of effectiveness, including interim measures for tomorrow's 14 cases.

Read the worked answer

Engineering controls come first. Repair or rebalance the exhaust to restore at least 100 fpm face velocity before production resumes; the 78 fpm measurement is the likely cause of the idle 0.3 ppm reading and should be corrected and re-verified with a leak test. Enclose cartridge changes under local exhaust, or convert to a closed cartridge system so operators are not opening the sterilizer in their breathing zone. Add continuous EtO monitoring with an alarm.

Administrative: restrict room access, post signage, and make cartridge changes a two-person procedure outside peak hours. PPE is the last line: until engineering controls are verified, provide NIOSH-approved cartridges for EtO with fit testing under a written respiratory protection program - its absence is itself a compliance gap.

For tomorrow's 14 cases, do not simply run the sterilizer as usual. Ranked options: use the alternate campus low-temperature system if turnaround permits; if not, run only the loads actually needed, with the exhaust repaired or with local exhaust plus respirators, and sample the room during the run; if neither is achievable, delay elective cases. Fourteen elective cases do not justify an uncontrolled exposure to pregnant workers.

3. What are your obligations for the three symptomatic workers and the two pregnant technicians?

Read the worked answer

Refer the three symptomatic workers for medical evaluation and a work-relatedness determination. EtO is a known irritant and sensitizer, and the EtO standard requires medical surveillance for exposed workers at or above the action level, including medical and work history, physical examination, and specified laboratory testing. Symptoms consistent with EtO exposure should be evaluated for OSHA 300 recordability if they involve medical treatment beyond first aid or meet other criteria.

For the two pregnant technicians, do not wait for a physician's note. EtO is a reproductive toxicant and there is no established safe exposure level in pregnancy. Offer temporary reassignment away from the sterilizer area while engineering controls are corrected, without penalty, and document the offer and the response. Refer both to occupational health and share the exposure data with them.

Communicate results in writing to all five workers, in a language they understand, stating the measured values and the limits. Do not say "within OSHA limits, so it is safe" - the action level was exceeded and symptoms are present. That statement would be inaccurate and would undermine reporting of the next cluster.