ICAA Insulator flashcards
ICAA Insulator · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Asbestos PEL for construction
- 0.1 fiber per cubic centimeter as an 8-hour TWA under OSHA 29 CFR 1926.1101; Class I thermal system insulation removal also requires a negative-pressure enclosure, decontamination unit, and competent person.
- Fall protection trigger height
- OSHA construction rules require fall protection at 6 feet (1.8 m) above a lower level under 29 CFR 1926.501; the general-industry trigger under 29 CFR 1910.28 is 4 feet.
- Silica action level
- 25 micrograms per cubic meter as an 8-hour time-weighted average, with a permissible exposure limit of 50 micrograms per cubic meter under OSHA 29 CFR 1926.1153.
- Respirator fit test interval
- Fit testing is repeated annually and whenever a different respirator model, style, or size is used; a medical evaluation is required before fit testing under 29 CFR 1910.134.
- k-value definition
- Thermal conductivity in Btu-in per hour-square foot-degree Fahrenheit: heat flow through one inch of material per square foot per degree of temperature difference. R-value equals thickness divided by k.
- ASTM E84 indices
- Surface burning test reporting flame spread index and smoke developed index; many insulation specifications require a flame spread of 25 or less and smoke developed of 450 or less.
- Cellular glass properties
- Closed-cell, noncombustible, and essentially impermeable to water vapor, so no separate vapor retarder is needed; it is brittle, strong in compression, and must be chloride-free on stainless steel.
- Chloride stress corrosion cracking
- Austenitic stainless steel under insulation can crack when leachable chlorides concentrate at the surface; ASTM C795 sets acceptance limits and ASTM C871 is the leachable-chloride test method.
- Pipe insulation seam location
- Longitudinal joints are rotated off the top of the pipe to the side or bottom, so the seam is not a water-collection point and is not visible from the floor.
- Staggered double-layer joints
- When two insulation layers are required, the outer layer joints are offset from the inner layer joints so no straight-through path exists for heat flow or moisture migration.
- Contact adhesive technique
- Apply adhesive to both mating surfaces, let the solvent flash until tacky, then join and press firmly; a wet bond traps solvent and produces a weak joint that later opens.
- Effect of compression
- Compressing fibrous insulation reduces installed thickness and R-value; pieces are cut slightly long and fitted without forcing so joints stay tight along the run.
- Hanger insert purpose
- High-density insulation inserts or blocks at pipe hangers carry the load, prevent crushing of the insulation, and preserve thermal performance at each support point.
- NFPA 90A duct limits
- Duct insulation and coverings must have a flame spread index of 25 or less and a smoke developed index of 50 or less when tested in accordance with ASTM E84.
- Removable insulation blankets
- Fabricated pads with lacing hooks and straps that cover valves, flanges, and strainers so the component stays insulated but can be opened for service and reused.
- Insulating expansion loops
- Loops and offsets use oversized sections, slip joints, or extra clearance so pipe movement is absorbed without tearing the insulation or opening the vapor retarder joints.
- Perm rating scale
- One perm equals one grain of water vapor per hour per square foot per inch of mercury; materials rated 0.1 perm or less are Class I vapor retarders.
- ASJ jacket
- All-service jacket is a factory-applied foil-scrim-kraft laminate with permeance near 0.02 perm or less; every joint, lap, staple, and puncture must be sealed.
- Metal jacket lap direction
- Laps are at least 2 inches and are installed upper over lower like shingles so water runs off; stainless bands secure the jacket about 12 inches on center.
- PVC jacketing temperature limit
- PVC jacketing is typically limited to about 150 F service; CPVC or metal jacketing is used at higher temperatures or where UV and impact resistance are needed.
- Division 23 07 13
- The MasterFormat section number for HVAC duct insulation, covering insulation materials, thicknesses, vapor retarders, facings, and installation requirements.
- Purpose of submittals
- Product data, shop drawings, ASTM test reports, and samples submitted for designer approval before installation; installing unapproved material is at the contractor's risk.
- RFI definition
- A Request for Information is a formal written question to the designer used to resolve drawing conflicts, missing details, or ambiguous specifications before work proceeds.
- Drawing revision block
- A block on each sheet listing revision number, date, and description; layout and fabrication are performed only from the current issued revision.
- Banding tool use
- Tensions stainless steel bands around jacketing and crimps a seal; bands are typically spaced about 12 inches on center and set back from jacket ends.
- Gore count on elbows
- Segmented 90-degree elbows are commonly fabricated from 3, 4, or 5 gores; more gores give a smoother curve and less wrinkling on large diameters.
- Serrated insulation knife
- A long serrated blade cuts fibrous insulation with minimal compression; a sawing motion against a straightedge produces square cuts and tight-fitting joints.
- Insulation storage requirements
- Keep insulation indoors, off the floor, and in original wrapping until installation; wet fibrous insulation loses R-value and laminated facings can delaminate.
- Labor unit definition
- Installed craft hours required per unit of material, such as per linear foot of pipe or per fitting; multiplied by quantity to give total estimated hours.
- Waste factor
- A percentage added to the takeoff for cutting loss and damage, commonly 5 to 10 percent for pipe insulation and 10 to 15 percent for fittings.
- Installed thickness check
- Verify thickness with a thin probe or gauge at random locations; compressed, thin, or missing sections reduce R-value and fail the specification requirement.
- As-built drawings
- Marked-up drawings recording actual installed routing, sizes, and quantities; they support final payment, change-order substantiation, and future maintenance work.