ICC ECS flashcards
ICC ECS · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Working clearance depth rule
- Depth of working space in front of electrical equipment depends on voltage to ground and on whether live parts are exposed on the opposite side; ranges from 3 ft to 4 ft.
- Dwelling receptacle spacing
- In dwelling units, no point along the floor line of a wall space may be more than 6 ft from a receptacle, and wall spaces 2 ft or wider require one.
- GFCI required locations
- GFCI protection is required for receptacles in bathrooms, garages, outdoors, kitchens, laundry areas, and within 6 ft of sinks in dwelling units.
- AFCI branch circuit rule
- Arc-fault circuit-interrupter protection is required for branch circuits supplying outlets in dwelling-unit bedrooms, family rooms, dining rooms, and similar living areas.
- Grounding versus bonding
- Grounding connects the electrical system to earth to establish a voltage reference; bonding connects metal parts together to provide a low-impedance fault-current path.
- Main bonding jumper
- The connection between the grounded service conductor and the equipment grounding conductor at the service; it must be omitted at subpanels to keep neutrals isolated.
- Grounding electrode conductor sizing
- The grounding electrode conductor is sized from the table keyed to the largest ungrounded service-entrance conductor, not from the overcurrent device rating.
- Equipment grounding conductor sizing
- The equipment grounding conductor is sized from the table keyed to the rating of the overcurrent device protecting the circuit, with minimum size rules.
- Box fill calculation steps
- Count conductors entering the box, add one for each device yoke, add equipment grounding conductors, then compare total volume to the box cubic-inch capacity.
- Conductor color identification
- Grounded conductors must be white or gray; equipment grounding conductors green, green with yellow stripe, or bare; ungrounded conductors may be other colors.
- NM cable restrictions
- Nonmetallic-sheathed cable is permitted in dwellings but prohibited in hazardous locations, outdoors in raceways, and where subject to physical damage.
- Raceway support intervals
- EMT and rigid metal conduit must be supported within 3 ft of boxes and every 10 ft thereafter; supports must be listed and secure the raceway.
- Junction box accessibility
- Splices and taps must be made in approved enclosures, and those enclosures must remain accessible without removing permanent building finish.
- Unused opening closure
- Unused openings in boxes, cabinets, and enclosures must be closed with listed plugs or plates to maintain the enclosure integrity and rating.
- Dwelling general lighting load
- General lighting load for dwellings is calculated at 3 VA per square foot of floor area, with demand factors applied above the first 3,000 VA.
- Small-appliance branch circuits
- Dwelling units require at least two 20-A small-appliance branch circuits for kitchen countertop receptacles and at least one 20-A laundry circuit.
- Range demand calculation
- Household electric ranges use the demand table; a single range rated up to 12 kW may be calculated at 8 kW demand for service sizing.
- Optional dwelling calculation method
- The optional method uses 100% of noncoincident loads plus 40% of other loads, with a minimum service rating of 100 A for a single-family dwelling.
- Multioutlet receptacle load
- In non-dwelling occupancies, each receptacle outlet on a multioutlet branch circuit is calculated at 180 VA, with demand factors applied per the table.
- Next-higher overcurrent rating
- The next standard overcurrent device rating above conductor ampacity is permitted only where ampacity does not exceed 800 A and the load is protected.
- Standard overcurrent device ratings
- Standard ratings include 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, and 200 amperes.
- Series-rated system requirement
- A series combination rating is valid only when the line-side and load-side devices are listed together as a combination; substituting a breaker voids the rating.
- Service disconnecting means location
- The service disconnecting means must be at a readily accessible location nearest the point of entry of service conductors, outside or inside nearest the entry.
- Hazardous location classes
- Class I covers flammable gases and vapors, Class II combustible dusts, and Class III ignitable fibers; each is divided into Division 1 or 2 or zones.
- Hazardous location equipment marking
- Equipment in classified locations must be marked with class, division or zone, and group, and that marking must match the area classification exactly.
- Motor branch-circuit protection
- Motor overload protection protects the motor, while branch-circuit short-circuit and ground-fault protection protects conductors; breakers may be sized up to 250% of full-load current.
- Motor disconnecting means
- A motor disconnecting means must be within sight of the motor and controller and must be capable of being locked in the open position.
- Fire pump circuit protection
- Fire pump conductors must be protected against overload but the overcurrent device must carry locked-rotor current indefinitely so power is not lost during a fire.
- Photovoltaic rapid shutdown
- Photovoltaic systems require rapid shutdown provisions to reduce conductor voltage near the array, plus marked DC conductors and a disconnecting means.
- Permit exemptions
- A permit is required for new and altered electrical work; ordinary repair or replacement of lamps, fuses, or snap switches does not require one.
- Rough-in versus final inspection
- Rough-in inspection occurs before concealment of wiring, and final inspection occurs after finish work; concealed work lacking rough-in approval must be exposed.
- Alternate materials and methods
- The code official may approve alternate materials or methods when equivalent in performance, safety, and quality; the approval must be recorded in writing.