IE F-Gas Category III cheat sheet
IE F-Gas Category III · Keep the key ideas within reach.
F-Gas and ODS Regulations
F-Gas Regulation (EU) 517/2014 applies to HFCs, PFCs, SF6, and blends containing these; ODS Regulation (EC) 1005/2009 covers CFCs, HCFCs, halons, and methyl bromide.
Placing on the market of HFCs is subject to a phase-down quota measured in CO2e; quota allocations are managed via the European Commission's F-Gas Portal.
Certification under F-Gas Regulation is mandatory for personnel handling refrigerants in equipment above certain charge sizes; Category III covers servicing and maintenance of equipment containing less than 3 kg of F-Gas (or 5 tCO2e if hermetic).
Leak checks are required at intervals based on CO2e charge: at least every 12 months for 5–50 tCO2e, every 6 months for 50–500 tCO2e, and every 3 months for >500 tCO2e; with leak detection systems, intervals double.
Record keeping: operators must maintain records of refrigerant quantity and type, leak checks, repairs, and recovery for at least 5 years.
Labelling: equipment containing F-Gases must be labelled with the refrigerant type and CO2e charge; ODS containers must be labelled accordingly.
Ban on use of HFCs with GWP ≥ 2500 for servicing equipment from 1 January 2020, except for reclaimed refrigerant or equipment intended for export.
ODS phase-out: production and use of HCFCs banned except for feedstock and specific essential uses; recovery and destruction required for ODS.
Penalties for non-compliance vary by Member State but include fines and certification withdrawal.
Environmental Impact of Refrigerants and ODS
ODP (Ozone Depletion Potential) is relative to CFC-11 (ODP=1); HCFC-22 has ODP 0.055, CFC-12 has ODP 1.
GWP (Global Warming Potential) is relative to CO2 over 100 years; R-404A GWP=3922, R-410A GWP=2088, R-134a GWP=1430.
CO2e = mass of refrigerant (kg) × GWP; used for leak check thresholds and quota calculations.
ODS destroy stratospheric ozone, increasing UV radiation; HFCs do not deplete ozone but are potent greenhouse gases.
Atmospheric lifetime affects overall impact; CFC-12 lifetime ~100 years, HFC-134a ~14 years.
TEWI (Total Equivalent Warming Impact) = direct emissions (refrigerant leaks) + indirect emissions (energy use).
Recovery and destruction of ODS and F-Gases prevents emissions; incineration with energy recovery is common for ODS.
Leakage of 1 kg R-404A equals 3922 kg CO2e, equivalent to driving ~15,000 km in an average car.
Containment, Recovery and Handling of Refrigerants
Recovery cylinders must be dedicated, labelled, and never filled above 80% of capacity by volume; use a calibrated scale.
Before recovery, identify refrigerant type; never mix refrigerants in the same cylinder unless the blend is specified.
Recovery efficiency: for systems with charge <3 kg, recover at least 90% of refrigerant; for larger systems, recover at least 95%.
Use recovery equipment with a certified efficiency; evacuate hoses and equipment to minimise emissions.
When transferring refrigerant, use proper hoses with low-permeation and shut-off valves; purge with nitrogen if necessary.
Recovered refrigerant must be analysed if to be reused; reclaimed refrigerant must meet standard purity (e.g., AHRI 700).
Never vent refrigerant to atmosphere; it is illegal and harmful.
For flammable refrigerants (e.g., R-290, R-600a), use recovery equipment rated for flammables and follow safety procedures.
Record the quantity of refrigerant recovered and the destination (recycled, reclaimed, destroyed).
Safety, Records and Leak Checking
Leak checking methods include: visual inspection, soap bubble, electronic leak detector, and UV dye (where permitted).
Electronic leak detectors must be calibrated for the refrigerant type and sensitivity (e.g., 5 g/yr).
If a leak is detected, repair must be completed within 14 days; if repair is not feasible, a plan must be documented and leak check frequency increased.
After repair, a follow-up leak check must be performed within 1 month.
Records must include: date, refrigerant type, quantity added, leak check results, repairs, and technician ID.
Safety: use PPE (gloves, goggles), ensure ventilation, avoid inhalation; refrigerant vapours can cause asphyxiation.
For flammable refrigerants, eliminate ignition sources, use gas detectors, and follow ATEX requirements.
Cylinders must be stored upright, secured, and away from heat; temperature limits per cylinder specification.
Leak detection systems must be checked annually and alarm function tested.