Service and Inspection of an Older Boiler

RGII 5-Year Competency Assessment · Put your knowledge to work in context.

All case studies

Service and Inspection of an Older Boiler

You are servicing a 15-year-old open-flued boiler. The boiler is in a cupboard in a bathroom. The cupboard has a louvred door for ventilation. The boiler has a permanent pilot light. The flue goes vertically through the roof. The boiler has not been serviced for 3 years. The customer reports that the boiler sometimes makes a popping noise and the pilot light occasionally goes out. On inspection, you find the heat exchanger is clogged with dust and lint, and the flue is partially blocked by a bird's nest. The gas rate is 10% below the manufacturer's specified rate. The pilot flame is yellow and lazy. The cupboard door louvres are partially blocked by stored items. You perform a flue flow test and find that smoke is spilling from the draught diverter. The boiler is rated at 15 kW. The bathroom has an extractor fan but it is not working. The customer uses the bathroom for showering, creating steam.

1. Identify the faults and classify the boiler's condition according to the Gas Safety (Installation and Use) Regulations. Justify your classification.

Read the worked answer

The faults are: 1) Heat exchanger clogged with dust and lint, reducing heat transfer and causing incomplete combustion. 2) Flue partially blocked by a bird's nest, restricting flue gases and causing spillage. 3) Gas rate 10% below specified, indicating possible blockage or incorrect settings. 4) Pilot flame yellow and lazy, indicating incomplete combustion and possible CO production. 5) Cupboard louvres blocked, reducing ventilation. 6) Flue flow test shows spillage from draught diverter, meaning combustion products are entering the room. 7) Extractor fan not working in bathroom, but bathroom is a special location; however, the boiler is in a cupboard, so the fan may not affect it directly, but steam could affect combustion air. The spillage of flue gases is a serious risk. According to the Gas Safety (Installation and Use) Regulations, an appliance that spills products of combustion is classified as Immediately Dangerous (ID). The yellow pilot flame and clogged heat exchanger also indicate ID. Therefore, the boiler must be classified as ID. You must disconnect the gas supply to the boiler, attach a warning notice, and inform the customer not to use it. You should also advise on remedial work: clean heat exchanger, remove nest, check gas rate, service pilot, ensure ventilation is clear, and repair extractor fan. After remedial work, re-test and re-commission.

2. What immediate actions must you take, and what remedial work is required before the boiler can be returned to service?

Read the worked answer

Immediate actions: Turn off the gas supply to the boiler at the isolation valve. Attach a 'Danger Do Not Use' warning notice. Inform the customer in writing of the danger and the reasons. Do not leave the boiler in a condition where it could be used. If possible, isolate the electrical supply as well. Remedial work required: 1) Remove the bird's nest and clear the flue, then re-test flue flow. 2) Clean the heat exchanger thoroughly. 3) Adjust or clean the pilot burner to achieve a blue flame. 4) Check and adjust the gas rate to manufacturer's specifications. 5) Clear the cupboard louvres and ensure adequate ventilation. 6) Repair or replace the bathroom extractor fan to prevent steam affecting the boiler. 7) After all work, perform a full service, including combustion analysis if possible, and a flue flow test to ensure no spillage. 8) Check for any other safety issues, such as the condition of the flue and ventilation. Only after all faults are rectified and tests pass can the boiler be returned to service. Document all work and provide a service record.