RGII 5-Year Competency Assessment flashcards
RGII 5-Year Competency Assessment · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Gas Safe Register
- The UK statutory gas registration body (since 2009) that replaced CORGI; only registered businesses may legally carry out gas work in domestic and commercial premises.
- CP12 Landlord Record
- The Landlord Gas Safety Record issued after an annual safety check of gas appliances and flues in rented domestic premises; a copy is given to the tenant and records kept for two years.
- ID Warning Notice
- Immediately Dangerous classification: an appliance or installation posing an immediate risk; it is turned off, labelled with a warning notice, and the responsible person is informed.
- AR Warning Notice
- At Risk classification: a defect that could become dangerous; the appliance is labelled and the user advised, but the immediate risk to life is not present.
- RIDDOR Gas Reporting
- The Reporting of Injuries, Diseases and Dangerous Occurrences Regulations require certain gas incidents, including dangerous gas fittings and deaths, to be reported to the HSE.
- Natural Gas Relative Density
- Natural gas (methane, G20) has a relative density of about 0.6, so it is lighter than air and tends to rise and disperse at high level.
- LPG Relative Density
- Liquefied petroleum gas (propane, G31) has a relative density of about 1.55, so it is heavier than air and accumulates at low level in pits and voids.
- Methane Flammable Limits
- Methane is flammable in air at approximately 5% to 15% by volume; below the lower limit the mixture is too lean, above the upper limit too rich, to ignite.
- Propane Flammable Limits
- Propane (G31) is flammable in air at approximately 2.1% to 9.5% by volume, a wider and lower range than methane, increasing leak hazard at low level.
- Methane Combustion Equation
- Complete combustion of methane: CH4 + 2O2 -> CO2 + 2H2O, requiring about 9.5 volumes of air per volume of gas for stoichiometric burning.
- Gas Odorisation
- Natural gas is odorised with a sulphur compound (typically THT) so leaks are detectable by smell at about one-fifth of the lower explosive limit.
- Carbon Monoxide Properties
- CO is colourless, odourless and tasteless; it binds haemoglobin about 200-250 times more readily than oxygen, causing chemical asphyxiation at low concentrations.
- CO/CO2 Ratio Action Levels
- Industry guidance: a flue CO/CO2 ratio above 0.004 indicates a potential problem; above 0.008 is generally At Risk; above 0.02 is Immediately Dangerous.
- Excess Air Effect
- Excess air dilutes flue products, lowering measured CO2; insufficient air raises CO and produces yellow, lazy flames and sooting.
- Flue Flow Test
- A smoke pellet test confirming the flue pulls combustion products clear of an open-flued appliance under normal conditions before the spillage test is performed.
- Spillage Test
- A test at the draught diverter of an open-flued appliance under worst-case conditions (doors, fans, extractors) confirming products do not spill into the room.
- Room-Sealed Appliance Air
- A room-sealed appliance draws combustion air directly from outside via a balanced or concentric flue, so it does not rely on room ventilation for combustion air.
- Permanent Ventilation Sizing
- Permanent openings for open-flued natural gas appliances are sized per BS 5440-2 and manufacturer instructions; a common guide is 5 cm2 free area per kW above 7 kW.
- Domestic Gas Operating Pressure
- Natural gas at the meter outlet is nominally 21 mbar (typically 19-23 mbar); appliance inlet pressure must be within the manufacturer's stated tolerance.
- Domestic Pipework Pressure Drop
- BS 6891 sizing limits the pressure drop from meter to appliance to about 1 mbar for natural gas, leaving adequate inlet pressure at the appliance.
- Pipe Sleeving Requirement
- Pipe passing through a wall, floor or cavity must be sleeved and sealed, with the sleeve vented where it enters a void, to prevent gas accumulation.
- Buried Compression Fitting Rule
- Compression fittings on gas pipework must remain accessible and must not be buried in walls or floors; inaccessible joints require approved alternatives.
- Equipotential Bonding
- Main protective bonding of the gas installation pipework near the meter is required to equalise potential and reduce spark risk; the connection must be to a suitable earth.
- Tightness Test Sequence
- A let-by test at operating pressure, a stabilisation period, then a pressure-loss test at the specified test pressure for the specified duration with no allowable drop.
- IGEM/UP/1B Domestic Testing
- The domestic tightness testing and purging standard; specifies test pressures, stabilisation and test durations for low-pressure domestic natural gas installations.
- Gas Rate Check
- Timed meter reading compared with the appliance data badge input; a metric meter reads m3 and an imperial meter reads cubic feet (1 ft3 = 0.0283 m3).
- Appliance Data Badge
- The label giving model, gas type and category (e.g. II2H3P), input and output in kW, and NOx class; used to confirm suitability for the gas supply.
- Flue Terminal Clearances
- BS 5440-1 sets minimum distances from flue terminals to openings and boundaries (e.g. 300 mm from an opening window); manufacturer instructions take precedence.
- FSD Test Procedure
- Extinguish the flame and confirm the flame supervision device closes the gas valve within the manufacturer's specified time, typically within 60 seconds on many domestic appliances.
- Service Combustion Records
- Recording CO/CO2 ratio, CO ppm, O2% and CO2% at each service allows comparison with previous readings to detect deterioration of combustion performance.
- Low Inlet Pressure Diagnosis
- Correct meter pressure with low appliance inlet pressure indicates a pipework restriction; low meter pressure indicates a supply-side fault rather than an appliance fault.
- Gas Emergency Procedure
- On a gas escape: turn off the ECV, extinguish flames, avoid electrical switches, ventilate, evacuate and call the National Gas Emergency Service on 0800 111 999.