SOLAS Refrigeration: Refrigeration and Air Conditioning

SOLAS Refrigeration · Work through your exam, one topic at a time.

All guide sections

Refrigeration and Air Conditioning

Domain overview

This section covers the Refrigeration and Air Conditioning domain of the craft apprenticeship curriculum. The assessment checks whether you can explain the vapour-compression cycle, interpret pressure–temperature readings, apply safe refrigerant handling, and relate air-conditioning performance to airflow and psychrometrics.

Core rules

  • The cycle has four steady-flow processes: compression, condensation, expansion and evaporation. The compressor raises refrigerant pressure and saturation temperature; the condenser rejects heat; the expansion device drops pressure; the evaporator absorbs heat.
  • Superheat = suction-line temperature − evaporating saturation temperature. It protects the compressor from liquid return and is controlled by the TXV/EEV.
  • Subcooling = condensing saturation temperature − liquid-line temperature. It shows the liquid seal and condenser margin; low subcooling can indicate undercharge or flash gas.
  • Use pressure–temperature charts with the correct gauge/absolute basis. Test with dry nitrogen, never oxygen; evacuate and hold a vacuum to the manufacturer’s limit; charge by weight where possible.
  • Air-conditioning performance depends on sensible and latent load: dry-bulb change shows sensible cooling, while wet-bulb or dew-point change shows moisture removal. Check airflow, filter pressure drop and condensate drainage before adjusting charge.
  • Isolate and prove dead before electrical work; check overloads, capacitors and contactor operation.

Worked example

A system using R404A reads suction pressure equivalent to 2°C saturation and a suction-line temperature of 8°C. Superheat = 8 − 2 = 6 K. The liquid-line temperature is 38°C and condensing saturation is 45°C, so subcooling = 45 − 38 = 7 K. Reasoning: both values compare a measured line temperature with the saturation temperature at the same pressure-not with ambient or room temperature. A 6 K superheat is a reading to compare with the manufacturer’s target, not a universal pass mark.

Traps

Confusing superheat with subcooling; using the liquid line for superheat; taking readings before the system stabilises; ignoring gauge versus absolute pressure; failing to insulate the temperature probe; using air or oxygen for pressure testing; and overlooking airflow, filter or condensate-drain faults in air-conditioning diagnosis. Do not add refrigerant to correct a low superheat caused by a restricted TXV or poor airflow.