IL Fire Alarm flashcards
IL Fire Alarm · Build recall with a focused review session.
33 cards. Read the term and the definition here. The deck at the top of this page is optional.
- IDC
- Initiating Device Circuit: the supervised wiring path from the fire alarm control unit to initiating devices such as smoke detectors, heat detectors, and manual pull stations.
- NAC
- Notification Appliance Circuit: the power and supervision path from the control unit to notification appliances such as horns, strobes, and speakers.
- Addressable system
- A fire alarm system in which each initiating device and notification appliance has a unique address, allowing the control unit to identify the specific device in alarm or trouble.
- Presignal
- A feature that routes alarm signals to a designated location for acknowledgment before general occupant notification, delaying the general alarm within NFPA 72 time limits.
- Positive alarm sequence
- A NFPA 72 feature allowing 15 seconds for acknowledgment and up to 180 seconds total for investigation before automatic general alarm notification, if the sequence is completed.
- Conventional zone limits
- In a conventional system, a zone must not exceed 22,500 square feet, must not span more than one floor, and must be separately annunciated at the control unit.
- Spot smoke detector spacing
- On smooth ceilings, spot-type smoke detectors are spaced no more than 30 feet apart, with the first detector within 15 feet of any wall.
- Heat detector spacing
- Ordinary-rated heat detectors are spaced up to 50 feet apart on smooth ceilings, reduced 4 percent per foot of ceiling height above 10 feet.
- Rate-of-rise detector
- A heat detector that responds to a rapid temperature increase, typically about 12 to 15 degrees Fahrenheit per minute, rather than a fixed temperature setpoint.
- Pull station height
- Manual fire alarm pull stations are mounted 42 to 48 inches above the finished floor, within 5 feet of exit doorways, and unobstructed along the egress path.
- Audibility requirement
- Notification appliances must produce 15 dBA above ambient or 5 dBA above maximum ambient lasting 60 seconds, whichever is greater, measured at 10 feet.
- Strobe candela
- Visible notification appliance intensity selected from the NFPA 72 room-size table; a 20-by-20-foot room typically requires a 15 candela strobe.
- Duct smoke detector
- A detector installed in an HVAC duct with sampling tubes spanning the duct width, listed for the air velocity and supervised for airflow and power.
- Supervisory signal
- A signal indicating an off-normal condition of a system component, such as a closed sprinkler valve or low air pressure, annunciated distinctly from alarm and trouble.
- Class A circuit
- A supervised circuit that returns to the control unit so a single open conductor does not disable the circuit, also called Style D or Style X.
- Class B circuit
- A two-wire supervised circuit with an end-of-line resistor; an open conductor disables all devices beyond the break, also called Style B or Style Y.
- Voltage drop formula
- Vdrop equals two times current times conductor resistance per foot times one-way length, used to verify the last appliance receives its listed minimum voltage.
- Battery sizing
- Required ampere-hours equal standby current times standby hours plus alarm current times alarm hours, with a 20 percent aging factor applied.
- EOL resistor
- End-of-line resistor sized to the control unit; a missing or incorrect resistor produces a trouble condition on a supervised circuit.
- Power-limited circuit
- A circuit whose power output is limited per NFPA 70 Article 725, allowing reduced wiring methods but requiring separation from non-power-limited circuits.
- Ground fault detection
- A control unit function that annunciates a trouble when conductor-to-ground impedance falls below the listed threshold, commonly around 10 kilohms.
- Smoke detector testing
- Annual sensitivity testing with a listed method; detectors out of their listed sensitivity range, such as 0.5 to 3.5 percent per foot obscuration, are recalibrated or replaced.
- Record of completion
- A NFPA 72 document signed by the installing contractor and witness confirming the system was installed and tested per the design and applicable standards.
- Battery load test
- Applying the calculated alarm load for the listed duration, typically five minutes, and verifying terminal voltage remains above 85 percent of nominal.
- Inspection frequency table
- NFPA 72 Table 14.4.3.2 lists intervals: monthly for control unit indicators, quarterly for waterflow devices, semiannually for valve tamper switches, annually for detectors.
- Detector clearance
- Initiating devices require clearance from obstructions, including 18 inches below sprinkler deflectors, to ensure proper smoke or heat entry into the sensing chamber.
- NFPA 70 Article 760
- The National Electrical Code article governing fire alarm wiring, divided into general, non-power-limited, and power-limited fire alarm circuit parts.
- High-rise threshold
- NFPA 101 generally requires fire alarm systems in high-rise buildings, commonly defined as 75 feet or more above the lowest level of fire department access.
- Raceway fill limit
- NFPA 70 Chapter 9 limits raceway fill to 40 percent for three or more conductors, and EMT must be supported within 3 feet of boxes and every 10 feet.
- NFPA 1 fire code
- The Fire Code adopts NFPA 72 by reference and adds requirements for system maintenance, impairment procedures, and hot work fire watch.
- Illinois contractor license
- The Illinois Office of the State Fire Marshal requires a state fire alarm contractor license to install, alter, or repair fire alarm systems in Illinois.
- Illinois technician CE
- Licensed Illinois fire alarm technicians must complete continuing education, commonly eight hours per renewal cycle, to maintain their license with the State Fire Marshal.
- Local AHJ permits
- Illinois jurisdictions such as Chicago and Cook County may impose additional permitting, plan review, and licensing requirements beyond state law before installation begins.