- Light hazard density
- The minimum design density for light hazard occupancies is 0.10 gpm/ft² over a 1,500 ft² remote area, per the NFPA 13 density/area curves.
- Ordinary Group 1 density
- Ordinary Group 1 occupancies require a design density of 0.15 gpm/ft² over a 1,500 ft² remote area under the NFPA 13 density/area curves.
- Hazen-Williams formula
- Head loss per foot of pipe equals 4.52 times Q to the 1.85 power divided by C to the 1.85 power times diameter to the 4.87 power, with C typically 120 for steel.
- Sprinkler K-factor equation
- Flow from a sprinkler equals the K-factor times the square root of the discharge pressure, so a K-5.6 head at 7 psi flows about 14.8 gpm.
- Maximum light hazard spacing
- Light hazard sprinklers may be spaced no more than 15 feet apart and may cover no more than 225 square feet each, unless a calculated design permits otherwise.
- Deflector distance below ceiling
- Standard spray sprinkler deflectors must be positioned 1 to 12 inches below combustible ceilings and 1 to 18 inches below noncombustible ceilings per NFPA 13.
- Dry-pipe area increase
- Dry-pipe and preaction systems require a 30 percent increase in the hydraulically calculated design area to account for delayed water delivery to the remote heads.
- Minimum remote head pressure
- The pressure at the hydraulically most remote standard spray sprinkler must be at least 7 psi to produce the required discharge density and pattern.
- Main drain test frequency
- NFPA 25 requires an annual main drain test, and the test must also be repeated after any water supply change or valve closure to confirm supply adequacy.
- Waterflow alarm test interval
- Vane-type and pressure-switch waterflow alarms must be tested quarterly; the device must activate within 90 seconds at a flow equal to one sprinkler.
- Dry-pipe valve trip time
- The dry-pipe valve must deliver water to the test outlet within 60 seconds of the trip test, and a full-flow trip test is required every three years.
- Sprinkler head inspection frequency
- Sprinkler heads are inspected annually from floor level, and any head with corrosion, paint, damage, or loading must be replaced with a matching spare.
- Five-year internal pipe inspection
- An internal inspection or flushing of piping is required every five years for dry systems, galvanized pipe, and systems where obstruction is suspected.
- Standpipe hydrostatic test
- Standpipe and hose system piping must be hydrostatically tested at 200 psi, or 50 psi above the maximum working pressure, for two hours every five years.
- Antifreeze concentration limits
- Antifreeze solutions must be tested annually and kept between the minimum freeze-protection concentration and a maximum of 30 percent propylene glycol or 40 percent glycerin.
- Gauge inspection frequency
- Gauges on wet-pipe systems are inspected monthly to confirm normal supply pressure, and gauges must be replaced or recalibrated every five years.
- Valve tamper switch testing
- Supervisory valve tamper switches are tested semiannually, while main control valves are operated annually to verify they open and close fully.
- Illinois contractor license requirement
- Under 225 ILCS 317, any entity that designs, installs, repairs, alters, or maintains fire sprinkler systems must hold an OSFM-issued contractor license.
- Responsible managing employee
- Each licensed contractor must designate an RME who holds NICET Level III certification in water-based systems layout or an equivalent OSFM-approved qualification.
- Installer certification
- Individual sprinkler installers must be certified by the OSFM or hold NICET Level II certification, and must work under a licensed contractor.
- License renewal cycle
- Illinois fire sprinkler contractor licenses are renewed annually, and the OSFM may require continuing education as a condition of renewal.
- Unlicensed work penalties
- Performing sprinkler work without a license subjects the person to civil penalties and cease-and-desist orders, and local permits may be denied.
- RME change notification
- The contractor must notify the OSFM when its designated RME changes; failure to maintain an RME can result in suspension of the license.
- OSFM Fire Prevention Code
- 41 Ill. Adm. Code 141 adopts NFPA 13, 13D, 13R, 14, 20, and 25 by reference, giving those standards the force of Illinois regulation.
- Local amendment authority
- Municipalities may adopt stricter amendments to the state code, but a state contractor license is still required regardless of local permit requirements.
- NFPA 13D design basis
- One- and two-family dwelling systems must flow at least two sprinklers simultaneously, provide a 10-minute supply, and maintain no more than 7 psi at the remote head.
- NFPA 13R scope
- NFPA 13R applies to residential occupancies up to and including four stories, allowing omission of sprinklers in closets, bathrooms, and certain concealed spaces.
- Water supply flow test
- NFPA 13 requires a flow test within the prior 12 months, or a documented municipal supply curve, adjusted for seasonal and daily fluctuations.
- Hydrostatic acceptance test
- Before being placed in service, system piping must be hydrostatically tested at 200 psi, or 50 psi above working pressure, for two hours without leakage.
- Plan review requirement
- Installation requires plan review and approval by the OSFM or a delegated local authority, with hydraulic calculations and drawings submitted before work begins.
- NFPA 20 scope
- NFPA 20 governs the selection and installation of stationary fire pumps, including drivers, controllers, and the required pump performance and acceptance tests.