IMSA Roadway Lighting I · Keep the key ideas within reach.

Quick reference

Roadway Lighting

  • Illuminance (E) is luminous flux incident per unit area, measured in lux (lm/m²) or footcandles (lm/ft²); 1 fc = 10.76 lux.

  • Luminance (L) is reflected or emitted intensity per unit projected area in the observer's direction, measured in cd/m²; roadway visibility design is based on luminance, not illuminance.

  • Luminous intensity (I) in candela equals flux per solid angle (cd = lm/sr); a luminaire's distribution is published as an isocandela diagram or I-table.

  • Inverse-square law: E = I/d² for a point source at perpendicular incidence; at an angle θ from nadir, E = I(θ)·cos³θ/h² where h is mounting height.

  • Uniformity ratios: max-to-min (E_max/E_min) and max-to-average (E_max/E_avg); average-to-minimum (E_avg/E_min) is used in luminance-based design.

  • Veiling luminance ratio (L_vmax/L_avg) limits disability glare; it is computed from luminaire intensity toward the observer and the observer's eye adaptation level.

  • Lamp metrics that matter: luminous efficacy (lm/W), correlated color temperature (CCT), color rendering index (CRI), lumen depreciation (LLD), and luminaire dirt depreciation (LDD).

  • Maintained values = initial value × LLD × LDD; design calculations must use maintained illuminance/luminance, not initial photometric values.

  • IES RP-8 is the primary recommended-practice document for roadway and street lighting design criteria; IES LM-79 covers electrical/photometric measurement and LM-80 covers lumen maintenance testing.

Quick reference

Roadway Lighting

  • Roadway lighting design categories are set by road functional class, pedestrian conflict level, and area classification (commercial, intermediate, residential).

  • Design criteria tables give average maintained luminance, uniformity ratios, veiling luminance ratio, and sometimes average illuminance for each roadway classification.

  • Pole spacing-to-mounting-height ratio (S/H) typically ranges from about 3:1 to 5:1 for luminance uniformity; larger ratios generally degrade uniformity.

  • Standard luminaire arrangements: one-side, staggered/opposite, twin/median-mounted, and central/mast-arm; one-side suits narrow roads with S/H near 3, opposite suits wide roads.

  • Mounting height selection balances glare control (higher is better), uniformity, and spill light; typical street lighting heights run from about 7.5 m to 12 m for major roads.

  • Overhang (luminaire offset beyond the curb) reduces house-side spill and improves roadway-side uniformity; excessive overhang wastes light behind the pole line.

  • Setback is the horizontal distance from the curb face to the luminaire's vertical axis; it affects both spill control and the effective roadway-side distribution.

  • Luminaire classification uses cutoff categories (full cutoff, cutoff, semi-cutoff, non-cutoff) based on the intensity emitted at and above 90° and 80° from nadir.

  • B U G ratings (backlight, uplight, glare) from IES TM-15 describe luminaire light trespass and skyglow characteristics and are often referenced in local ordinances.

Quick reference

Roadway Lighting

  • Luminaire photometric files use the IES LM-63 (.ies) format, containing lumen output, intensity distribution, and CCT/CRI metadata; verify the file matches the actual product configuration.

  • A luminaire's BUG rating is derived from its zonal lumen sums: backlight (B0-B5), uplight (U0-U5), and glare (G0-G5).

  • Pole foundations are designed from the pole's overturning moment, which combines luminaire and bracket weight, wind load on the pole and luminaire, and ice load where applicable.

  • Wind load calculation uses the design wind pressure times the projected area of the pole and luminaire, applied at the appropriate height above the foundation.

  • Anchor bolts, base plates, and handhole orientation must be coordinated with the pole manufacturer's shop drawings and the structural engineer's foundation design.

  • Voltage drop in branch circuits must be checked: V_drop = 2·L·I·R per conductor for single-phase two-wire; keep within the local code or utility limit (commonly 3% on branch circuits).

  • Luminaire circuits are typically protected by a photocell or time clock for dusk-to-dawn control, with contactors for large loads.

  • Electrical service and grounding must comply with the adopted electrical code (e.g., NEC Article 410 for luminaires and Article 250 for grounding) and any local amendments.

Quick reference

Roadway Lighting

  • Field measurement of illuminance uses a calibrated meter with cosine and color correction, held horizontally at the roadway surface and at the specified grid points.

  • Luminance measurement uses a calibrated luminance meter aimed along the observer's line of sight, typically from a point 1.45 m above the roadway and about 83 m ahead.

  • Measurement grid spacing depends on roadway width and mounting height; points are usually taken at the center of each grid cell, avoiding the immediate pole base.

  • Maintained illuminance is verified by comparing field readings to the design values after applying LLD and LDD, accounting for lamp seasoning and dirt on the lens.

  • Lamp seasoning: HID lamps are typically operated about 100 hours before photometric measurement to stabilize output; LED luminaires generally do not require the same seasoning.

  • Photometric testing per LM-79 reports absolute photometry for LED luminaires (lumens and efficacy directly), unlike traditional lamps tested separately from the luminaire.

  • Commissioning checks include verification of photocell operation, circuit voltage at the luminaire, correct aiming/orientation, and absence of visible flicker or color shift.

  • As-built documentation should record actual mounting heights, pole locations, luminaire model and lumen setting, and measured illuminance/luminance values.

Quick reference

Roadway Lighting

  • Adaptive lighting controls dim luminaires during low-traffic periods; design must still meet the reduced criteria applicable to the reduced traffic volume.

  • LED luminaires offer dimming via 0-10 V, DALI, or proprietary protocols; verify compatibility between the driver, controller, and network.

  • Networked lighting controls can provide scheduling, photocell-based dimming, fault monitoring, and energy reporting; commissioning must verify each node's address and profile.

  • Energy code compliance (e.g., ASHRAE 90.1 or local amendments) may cap lighting power density for exterior lighting; controls can be a compliance path.

  • Light trespass limits are often set by local ordinance in terms of vertical illuminance at the property line; verify the luminaire's backlight distribution and aiming.

  • Skyglow reduction favors full-cutoff luminaires with low uplight (U0) ratings and warmer CCT where the local ordinance permits.

  • Retrofit economics compare LED wattage, lumen output, and controls savings against existing HID systems; include maintenance savings from longer life.

  • Maintenance planning should account for group relamping or driver replacement intervals and access equipment needs for high-mast or median-mounted poles.

Quick reference

Roadway Lighting

  • Roadway lighting design is typically delivered as a plan-and-profile sheet showing pole locations, mounting heights, and luminaire schedule.

  • The luminaire schedule lists type, manufacturer, model, lumen output, CCT, CRI, BUG rating, voltage, and mounting accessories.

  • The photometric layout plan shows calculated illuminance or luminance contours overlaid on the roadway, with the design criteria stated in a table.

  • A point-by-point calculation report documents the software used, grid spacing, observer position, maintenance factors, and the resulting average, max, min, and uniformity values.

  • Coordination is required with the roadway geometric design (curb lines, shoulders, clear zones) so poles do not become fixed-object hazards.

  • Clear-zone and breakaway requirements: poles within the clear zone should be breakaway or shielded, per the applicable roadside design guide.

  • Utility coordination is needed for service points, metering, and any conflict with existing overhead or underground facilities.

  • Specifications should reference the applicable IES test standards (LM-79, LM-80, TM-21) and require submittal of photometric files and test reports.

Quick reference

Roadway Lighting

  • Glare is quantified by veiling luminance (L_v) added to the observer's field; the ratio L_vmax/L_avg is a common design criterion.

  • Disability glare reduces contrast and visibility; discomfort glare causes annoyance without necessarily reducing visibility.

  • Trespass light is measured as vertical illuminance at the property line, often at 1.5 m above grade, and is limited by local ordinance.

  • Skyglow is upward-directed light; full-cutoff luminaires with U0 uplight ratings minimize it.

  • Light pollution ordinances often combine BUG rating limits, CCT limits, and curfew dimming requirements.

  • Tunnel and underpass lighting requires transition zones to manage adaptation between daylight and interior lighting levels.

  • Pedestrian-scale lighting at crosswalks and transit stops uses lower mounting heights and vertical illuminance criteria for facial recognition.

  • Glare from oncoming luminaires can be mitigated by shielding, reduced intensity at high angles, and proper mounting height and setback.

Quick reference

Roadway Lighting

  • Life-cycle cost includes initial capital, energy, maintenance (lamps, drivers, labor, equipment), and disposal; present-worth analysis discounts future costs.

  • LED luminaires typically have longer rated life (e.g., 50,000+ hours to L70 or L80) than HID lamps, reducing relamping frequency and labor cost.

  • Lumen maintenance for LED is projected using TM-21 from LM-80 test data; the reported L70/L80/L90 values depend on drive current and temperature.

  • Energy savings depend on wattage reduction, controls-based dimming, and reduced losses; calculate annual kWh from connected wattage times operating hours.

  • Utility rebates and demand-side programs may offset capital cost; verify eligibility requirements such as DLC listing or specific lumen/watt thresholds.

  • Maintenance factors for LED systems differ from HID because lumen depreciation and dirt depreciation curves differ; use manufacturer-provided LLD and LDD data.

  • Group relamping strategies for HID systems reduce labor cost per lamp compared with spot relamping.

  • Total cost of ownership comparisons should normalize for maintained lumens, not initial lumens, to avoid overstating one technology's performance.

Quick reference

Roadway Lighting

  • Safety and liability: lighting design should follow recognized recommended practices (IES RP-8) to demonstrate a reasonable standard of care.

  • Photometric calculations must be reproducible; retain software files, input assumptions, and output reports for the project record.

  • Field verification should confirm that installed luminaires match the specified photometric file and that aiming and orientation are correct.

  • Any substitution of luminaires requires recalculation to confirm the design criteria are still met.

  • Documentation of maintenance factors and assumed lamp/luminaire depreciation should be explicit in the design report.

  • Inspection checklists should cover foundation, pole plumbness, anchor bolt torque, handhole orientation, grounding, and luminaire aim.

  • Punch-list items commonly include misaimed luminaires, incorrect photocell settings, damaged finishes, and missing labels.

  • Record drawings should reflect as-installed conditions and be delivered with operation and maintenance manuals.

Quick reference

Roadway Lighting

  • Roadway lighting design software computes point-by-point illuminance and luminance using luminaire photometric files and roadway geometry.

  • Inputs include mounting height, overhang, setback, spacing, arrangement, luminaire tilt, maintenance factors, and observer position.

  • Outputs include average and minimum illuminance/luminance, uniformity ratios, veiling luminance ratio, and contour plots.

  • Grid spacing should be fine enough to capture the minimum values; coarse grids can overstate uniformity.

  • Observer position for luminance calculations is typically 1.45 m eye height and 83 m ahead of the calculation area, per RP-8 conventions.

  • Verify that the photometric file's coordinate system and units match the software's expectations (feet vs. meters, type C vs. type B).

  • Sensitivity checks: vary maintenance factor, spacing, and mounting height to see how robust the design is to field conditions.

  • Results should be compared against the design criteria table for the roadway classification before the design is finalized.

Quick reference

Roadway Lighting

  • Poles are specified by material (steel, aluminum, concrete, fiberglass), height, shaft taper, wall thickness, and finish.

  • Anchor bolts and base plates must match the pole manufacturer's template; verify bolt circle, diameter, and projection.

  • Breakaway or slip-base poles are used in clear zones to reduce collision severity; they must meet the applicable breakaway requirements.

  • Pole grounding: a grounding electrode at each pole, bonded to the equipment grounding conductor, is commonly required by the electrical code.

  • Handholes should face away from traffic and be at a consistent height for maintenance access.

  • Luminaire mounting accessories include brackets, tenons, davit arms, and trunnion mounts; verify arm length and rise match the photometric design.

  • Pole finish (galvanized, painted, anodized) affects corrosion resistance and maintenance; specify per environment (coastal, industrial).

  • Shop drawing review should confirm dimensions, material certifications, and compatibility with the specified luminaire.

Quick reference

Roadway Lighting

  • Roadway lighting design begins with classifying the road by functional class, pedestrian conflict, and area type, then selecting the corresponding design criteria.

  • Select luminaire photometric data and mounting height; check that the S/H ratio supports the required uniformity.

  • Choose an arrangement (one-side, opposite, staggered, median) based on road width and available pole locations.

  • Run point-by-point calculations using maintained values; iterate on spacing, mounting height, and overhang until criteria are met.

  • Check glare criteria (veiling luminance ratio) and light trespass limits in addition to illuminance/luminance.

  • Coordinate with structures, utilities, and clear zones; adjust pole locations as needed and re-verify calculations.

  • Prepare the luminaire schedule, layout plan, and calculation report; specify testing and submittal requirements.

  • Review submittals and shop drawings against the design; perform field verification after installation.

Quick reference

Roadway Lighting

  • IES LM-79 covers electrical and photometric measurements of LED luminaires; results are absolute (lumens, efficacy, CCT, CRI) for the complete luminaire.

  • IES LM-80 covers lumen maintenance and color maintenance testing of LED packages, arrays, and modules at specified case temperatures.

  • IES TM-21 projects lumen maintenance beyond LM-80 test duration; projections are limited to 6× the test duration.

  • IES LM-63 defines the electronic photometric file format (.ies) used by design software.

  • IES TM-15 defines the BUG rating system for luminaires based on zonal lumen distributions.

  • IES RP-8 provides recommended practice for roadway and street lighting design criteria and calculation methods.

  • IES RP-20 addresses parking facility lighting; IES RP-33 addresses lighting for exterior environments including trespass and skyglow.

  • ANSI C136 series covers luminaire testing and performance standards; verify the specific standard referenced in the specification.

Quick reference

Roadway Lighting

  • HID lamps (high-pressure sodium, metal halide) require warm-up and restrike time; HPS has high efficacy but poor CRI, metal halide has better CRI but shorter life.

  • LED luminaires offer instant-on, dimmability, long life, and high efficacy; thermal management is critical to maintaining rated life and lumen output.

  • Fluorescent sources are rarely used for roadway lighting due to low output and cold-weather performance.

  • Induction lamps have long life but lower efficacy than LED and limited dimming capability.

  • Color metrics: CCT describes apparent color (warm to cool), CRI describes color rendering fidelity (0-100).

  • Lumen depreciation curves differ by source; HID lamps depreciate significantly, while LED depreciation is gradual and temperature-dependent.

  • Driver lifetime for LED is often the limiting factor; specify drivers with appropriate surge protection and thermal design.

  • Compatibility of dimming controls with drivers must be verified; not all 0-10 V drivers dim to the same minimum level.

Quick reference

Roadway Lighting

  • Light trespass ordinances commonly limit vertical illuminance at the property line and may also limit luminaire backlight (B) ratings.

  • Skyglow ordinances favor full-cutoff luminaires, low uplight (U0), and sometimes warmer CCT limits.

  • Curfew dimming requirements may mandate reduced output after a specified hour; verify the control system supports the required dimming profile.

  • Some jurisdictions require shielded luminaires near residential areas or dark-sky preserves.

  • Compliance documentation may require photometric calculations showing property-line illuminance and BUG ratings.

  • Ordinance requirements can conflict with design criteria; resolve by adjusting mounting height, aiming, or luminaire selection.

  • Verify the current version of the local ordinance; requirements change and may reference specific IES standards.

  • Environmental review may require assessment of impacts on wildlife and dark-sky resources.

Quick reference

Roadway Lighting

  • Project delivery includes design, specification, bidding, submittal review, construction observation, and closeout.

  • Submittals should include luminaire cut sheets, photometric files, LM-79 reports, LM-80/TM-21 data, and pole shop drawings.

  • Substitution requests require recalculation and comparison against the specified performance criteria.

  • Construction observation should verify pole locations, mounting heights, luminaire aim, and electrical connections.

  • Commissioning verifies controls operation, photocell settings, dimming profiles, and network connectivity.

  • Closeout documents include as-builts, O&M manuals, warranties, and training records.

  • Warranty terms should cover luminaire, driver, finish, and pole; verify duration and exclusions.

  • Punch-list resolution should be documented and verified before final acceptance.

Quick reference

Roadway Lighting

  • Energy calculations: annual kWh = connected watts × operating hours / 1000; include controls savings from dimming schedules.

  • Demand charges may apply to roadway lighting circuits; verify with the utility rate schedule.

  • Lighting power density limits for exterior lighting may apply under energy codes; controls can provide a compliance path.

  • Utility rebates often require DLC listing, minimum efficacy, and controls; document eligibility before bidding.

  • Maintenance cost estimates should include lamp/driver replacement, labor, equipment, and disposal.

  • Life-cycle cost analysis discounts future costs to present value using an appropriate discount rate.

  • Payback period = initial incremental cost / annual savings; simple payback ignores discounting.

  • Sensitivity analysis on energy prices and maintenance intervals improves the reliability of the economic comparison.

Quick reference

Roadway Lighting

  • Roadway lighting design must consider the roadway geometry: number of lanes, median width, curvature, and intersection locations.

  • Intersections require higher illuminance and uniformity than midblock sections due to conflict points.

  • Crosswalks and pedestrian areas require vertical illuminance for facial recognition and conflict detection.

  • Roundabouts require lighting of the circulatory roadway and approach legs; glare control is important for drivers entering.

  • Tunnels and underpasses require transition lighting to manage adaptation; design must consider daytime and nighttime conditions.

  • Bridges may have restrictions on pole mounting and require coordination with the bridge designer.

  • Work zone lighting must maintain safe illuminance while minimizing glare to workers and drivers.

  • Parking facilities and transit stops have their own recommended practices (RP-20 and related).

Quick reference

Roadway Lighting

  • Maintenance factors for roadway lighting include lamp lumen depreciation (LLD) and luminaire dirt depreciation (LDD); maintained = initial × LLD × LDD.

  • LED lumen maintenance is projected using TM-21 from LM-80 data; the projection depends on drive current and temperature.

  • Dirt depreciation depends on environment (clean, moderate, dirty) and luminaire design (sealed vs. open).

  • Group relamping reduces labor cost per lamp but may replace lamps before end of life; spot relamping reduces waste but increases labor.

  • Maintenance schedules should account for access equipment and traffic control costs.

  • Field measurements should be taken after lamp seasoning and cleaning to compare against maintained design values.

  • Record keeping of failures and relamping dates supports predictive maintenance.

  • Warranty claims require documentation of installation conditions and operating hours.

Quick reference

Roadway Lighting

  • Electrical design includes service entrance, branch circuits, voltage drop, grounding, and overcurrent protection.

  • Voltage drop limits are commonly 3% on branch circuits and 5% total; verify against the adopted code and utility requirements.

  • Grounding and bonding must comply with the electrical code; each pole typically requires a grounding electrode conductor.

  • Photocell and time clock control circuits should be coordinated with contactors for large loads.

  • Surge protection is recommended for LED luminaires, especially in areas with frequent lightning.

  • Circuit loading must account for inrush current of LED drivers and HID ballasts.

  • Conductor sizing must consider ambient temperature, conduit fill, and derating factors.

  • As-built electrical drawings should show circuit assignments, panel schedules, and control settings.

Quick reference

Roadway Lighting

  • Roadway lighting design criteria are organized by roadway classification: freeway, major, collector, local, and pedestrian facilities.

  • Each classification has recommended average maintained luminance, uniformity ratios, and veiling luminance limits.

  • Pedestrian conflict levels (high, medium, low) modify the criteria for a given roadway class.

  • Area classification (commercial, intermediate, residential) further refines the criteria.

  • Some jurisdictions use illuminance-based criteria instead of luminance-based; verify the adopted standard.

  • Adaptive lighting allows reduced criteria during low-traffic periods; the reduced criteria must be documented.

  • Design criteria should be stated explicitly in the calculation report and compared against results.

  • When criteria conflict between documents, the more stringent applicable requirement generally governs unless the authority having jurisdiction directs otherwise.

Quick reference

Roadway Lighting

  • Quality assurance during construction includes inspection of foundations, pole erection, and luminaire installation.

  • Foundation inspection verifies dimensions, reinforcement, anchor bolt placement, and concrete strength.

  • Pole erection inspection verifies plumbness, anchor bolt torque, and handhole orientation.

  • Luminaire inspection verifies model, lumen setting, aim, and orientation against the design.

  • Electrical inspection verifies grounding, circuit continuity, voltage, and control operation.

  • Nonconformance should be documented and resolved before acceptance.

  • Testing records should include photometric measurements where required by the specification.

  • Final acceptance should be contingent on resolution of all punch-list items.

Quick reference

Roadway Lighting

  • Roadway lighting design must consider the visual task: drivers detect obstacles, pedestrians, and other vehicles against the roadway background.

  • Luminance contrast between an object and its background determines visibility; higher contrast improves detection.

  • Small target visibility (STV) is an alternative design method that weights visibility of small targets across the roadway.

  • Adaptation level affects visibility; bright surroundings reduce contrast sensitivity.

  • Glare reduces visibility by adding veiling luminance to the field of view.

  • Pedestrian visibility depends on vertical illuminance and contrast against the background.

  • Design should consider both daytime and nighttime conditions where applicable.

  • Visibility-based design may be appropriate where luminance-based criteria are not sufficient.

Quick reference

Roadway Lighting

  • Pole spacing is determined by the required uniformity and the luminaire's distribution; S/H ratios commonly range from 3 to 5.

  • Mounting height affects both uniformity and glare; higher mounting heights improve uniformity but may increase spill light.

  • Overhang and setback affect the distribution of light on the roadway and the amount of spill behind the pole line.

  • Luminaire tilt changes the photometric distribution and should match the manufacturer's tested configuration.

  • Median-mounted luminaires can light both roadway directions but may require taller poles and careful glare control.

  • Twin-arm luminaires on median poles can be cost-effective for wide roadways.

  • Spacing should be checked against the calculated uniformity, not just the S/H rule of thumb.

  • Field adjustments to aim or tilt require recalculation to confirm criteria are still met.

Quick reference

Roadway Lighting

  • Roadway lighting design should consider sustainability: energy efficiency, longevity, and recyclability of components.

  • LED luminaires generally have higher efficacy and longer life than HID, reducing energy and maintenance impacts.

  • Dark-sky friendly design reduces skyglow and ecological impacts.

  • Life-cycle assessment can compare environmental impacts of design alternatives.

  • Disposal of lamps and drivers must comply with applicable regulations (e.g., mercury-containing lamps).

  • Reducing light trespass improves neighbor acceptance and may be required by ordinance.

  • Controls that dim during low-use periods reduce energy consumption.

  • Specifying repairable luminaires extends service life and reduces waste.

Quick reference

Roadway Lighting

  • Roadway lighting design software typically supports point-by-point calculations for illuminance and luminance.

  • Input geometry includes roadway width, lane configuration, curb lines, and median.

  • Luminaire input includes photometric file, mounting height, overhang, setback, tilt, and maintenance factor.

  • Observer position for luminance calculations is typically 1.45 m eye height and 83 m ahead.

  • Grid spacing should be fine enough to capture minimum values; verify convergence by refining the grid.

  • Results should be exported and included in the design report with all input assumptions.

  • Software version and photometric file names should be recorded for reproducibility.

  • Sensitivity analysis helps identify which inputs most affect the results.

Quick reference

Roadway Lighting

  • Roadway lighting specifications should reference applicable IES standards for testing and performance.

  • Specifications should require submittal of photometric files and test reports for verification.

  • Luminaire specifications should include lumen output, CCT, CRI, BUG rating, voltage, and dimming protocol.

  • Pole specifications should include material, height, finish, anchor bolt details, and breakaway requirements.

  • Installation specifications should cover foundation construction, pole erection, and luminaire aiming.

  • Testing and commissioning requirements should be stated explicitly.

  • Warranty requirements should cover luminaire, driver, finish, and pole.

  • Substitution procedures should require recalculation and comparison against the specified criteria.

Quick reference

Roadway Lighting

  • Roadway lighting design must coordinate with the roadway geometric design to avoid poles in clear zones.

  • Poles within the clear zone should be breakaway or shielded per the applicable roadside design guide.

  • Coordination with utilities is required for service points and conflicts with existing facilities.

  • Coordination with structures is required for bridge-mounted or building-mounted luminaires.

  • Coordination with landscaping is required to avoid conflicts with trees and to prevent light blockage.

  • Coordination with pedestrian facilities ensures adequate lighting at crosswalks and transit stops.

  • Coordination with traffic signals and signage avoids conflicts and ensures visibility.

  • Coordination with the authority having jurisdiction is required for permits and approvals.

Quick reference

Roadway Lighting

  • Roadway lighting design should be documented with a design report that states criteria, assumptions, and results.

  • The report should include the luminaire schedule, layout plan, and calculation output.

  • Maintenance factors and their basis should be documented.

  • Software inputs and photometric file names should be recorded for reproducibility.

  • Deviations from recommended practice should be justified and documented.

  • The report should be reviewed and sealed by the responsible professional where required.

  • As-built documentation should reflect any changes made during construction.

  • Records should be retained per project and jurisdictional requirements.

Quick reference

Roadway Lighting

  • Roadway lighting design should consider the needs of all road users, including drivers, pedestrians, and cyclists.

  • Pedestrian crossings require vertical illuminance for facial recognition and conflict detection.

  • Bicycle facilities may require lighting that reveals surface hazards and other users.

  • Transit stops require lighting for waiting passengers and security.

  • Accessible design considerations include lighting of ramps, stairs, and signage.

  • Glare control is important for all users, especially pedestrians and cyclists who may be more sensitive.

  • Lighting should be consistent along a route to avoid dark gaps.

  • Community input may inform design decisions in residential areas.

Quick reference

Roadway Lighting

  • Roadway lighting design must consider the visual environment: background luminance, signage, and adjacent lighting.

  • Bright adjacent areas (e.g., commercial signage) can increase adaptation level and reduce visibility.

  • Dark surroundings can cause discomfort glare from luminaires.

  • Transition zones between bright and dark areas require gradual changes in illuminance.

  • Tunnel lighting design requires careful management of adaptation.

  • Lighting of intersections should consider the approach lighting from each direction.

  • Lighting of curves may require closer spacing or different aiming.

  • Lighting of hills and grades may require adjustment of mounting height and aiming.

Quick reference

Roadway Lighting

  • Roadway lighting design should consider the maintenance access: poles should be accessible for bucket trucks or other equipment.

  • Median-mounted poles may require special access considerations.

  • High-mast lighting requires specialized access equipment and maintenance procedures.

  • Handholes should be oriented for safe access away from traffic.

  • Maintenance schedules should account for traffic control costs.

  • Spare parts should be stocked for critical components.

  • Training for maintenance staff should cover safe access and proper procedures.

  • Maintenance records should be kept for warranty and planning purposes.