ITI/NCVT RAC Mechanic (AITT Theory) flashcards
ITI/NCVT RAC Mechanic (AITT Theory) · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Tonne of refrigeration
- A cooling rate of 3.517 kW, equal to 3024 kcal/h or 12,000 BTU/h, defined as the heat needed to melt one tonne of ice at 0 °C in 24 hours.
- Superheat
- The difference between the actual suction line temperature and the saturation temperature at suction pressure. Measured at the evaporator outlet, it confirms the expansion valve is feeding correctly.
- Subcooling
- The difference between the condensing saturation temperature and the liquid line temperature. It indicates how much liquid refrigerant has been cooled below its condensing point and helps verify charge.
- Compression ratio
- Absolute discharge pressure divided by absolute suction pressure. Ratios above about 10:1 reduce efficiency and call for two-stage compression; always use absolute, not gauge, pressures.
- COP of a refrigerator
- Coefficient of performance equals refrigerating effect divided by compressor work, (h1 − h4) ÷ (h2 − h1). Higher evaporating temperature and lower condensing temperature raise the COP.
- Relative humidity
- The ratio of actual water vapour pressure in air to the saturation vapour pressure at the same dry-bulb temperature, expressed as a percentage. Heating air without adding moisture lowers it.
- Dew point temperature
- The temperature to which air must be cooled at constant pressure for it to become saturated, giving 100% relative humidity. An evaporator below dew point produces condensate and dehumidifies.
- Wet-bulb depression
- Dry-bulb temperature minus wet-bulb temperature. A large depression means dry air and high evaporative potential; used with a psychrometric chart to find relative humidity.
- Gauge versus absolute pressure
- Gauge pressure is measured above atmospheric; absolute pressure equals gauge plus atmospheric (about 1.013 bar). Refrigerant tables and compression ratios require absolute pressure.
- Micron and evacuation
- One micron equals 1/1000 mm Hg. Evacuation below 500 microns with a holding test confirms removal of moisture and non-condensables before charging a system.
- Vernier calliper least count
- One main scale division divided by the number of vernier divisions. With 1 mm main divisions and 20 vernier divisions the least count is 0.05 mm; with 50 divisions it is 0.02 mm.
- Micrometer reading
- Add the sleeve reading in 0.5 mm steps to the thimble graduation multiplied by 0.01 mm. A sleeve at 5.5 mm and thimble at 24 gives 5.74 mm.
- Nitrogen pressure testing
- Leak testing with dry, oil-free nitrogen through a regulator at about 1.5 times working pressure. Never use oxygen or compressed air, which can ignite oil and cause an explosion.
- Flashback arrestor
- A device fitted on oxygen and acetylene regulator outlets and torch inlets that stops a flame from travelling back into the cylinder, preventing regulator and cylinder explosion.
- Asphyxiation risk
- Refrigerant vapour is heavier than air and displaces oxygen in pits, basements and plant rooms. Test the atmosphere and ventilate before entry; never rely on smell alone.
- Phosgene formation
- Burning CFC or HCFC refrigerant in the presence of a flame produces phosgene and hydrogen fluoride, which are highly toxic. Ventilate and evacuate if refrigerant burns.
- Ohm's law and power
- V equals I times R; power equals V times I, also I²R or V²/R. In series circuits current is common; in parallel circuits voltage is common across branches.
- Insulation resistance test
- A 500 V megohmmeter test between winding and earth with the motor disconnected. A healthy motor reads at least 1 MΩ; low readings indicate moisture or winding failure.
- Run versus start capacitor
- The run capacitor stays in circuit with the auxiliary winding; the start capacitor is switched out by a centrifugal switch or potential relay once the motor accelerates.
- Star-delta starting
- The motor starts in star, where each winding sees voltage divided by √3 and line current is one-third of delta, then changes to delta for full-voltage running.
- NTC thermistor sensor
- A temperature sensor whose resistance falls as temperature rises, typically 5–10 kΩ at 25 °C. Drift or open circuit causes wrong defrost, fan or compressor control.
- Low-pressure switch
- A control that cuts out the compressor when suction pressure falls below a set value, protecting against low charge, a restriction or low load; it resets automatically when pressure returns.
- High-pressure switch
- A safety control that trips the compressor when discharge pressure exceeds its setting, as with a dirty condenser, fan failure or overcharge. Some types require manual reset.
- Defrost timer
- A motorised or electronic control that periodically stops the compressor and energises the defrost heater in frost-free refrigerators, ending defrost when the termination thermostat reaches its set temperature.
- Frost-free refrigerator
- A refrigerator with a hidden evaporator, evaporator fan and automatic defrost cycle using a timer, heater and termination thermostat. Ice build-up usually means a failed heater or timer.
- Chest versus upright freezer
- A chest freezer opens at the top, retains cold air and has longer holdover after power failure. An upright has shelves and loses cold air whenever the door opens.
- TXV bulb location
- The thermostatic expansion valve bulb is clamped on the suction line at the evaporator outlet, insulated, and kept away from the liquid line so it senses true superheat.
- Filter-drier function
- A device in the liquid line that removes moisture, acid and dirt from the refrigerant. It must be replaced after a burn-out or whenever the system has been opened.
- Refrigerant GWP and ODP
- Ozone depletion potential ranks damage to the ozone layer (CFC about 1, HFC zero); global warming potential ranks climate impact with CO2 as 1, for example R-410A about 2088.
- POE lubricant handling
- Polyolester oil is used with R-134a, R-410A and R-32. It is hygroscopic, so containers stay sealed, the system is evacuated well, and a new filter-drier is fitted after opening.
- A2L refrigerant safety
- A mildly flammable classification including R-32 and R-1234yf. No open flame or halide torch near the system, ventilate the area, and use spark-free tools and leak detectors.
- Refrigerant recovery
- Removing refrigerant into a labelled recovery cylinder with a recovery machine instead of venting it to atmosphere. Reclaim to AHRI 700 purity before reuse in another system.