Maharashtra HSC Electrical Maintenance (Bifocal) flashcards
Maharashtra HSC Electrical Maintenance (Bifocal) · Build recall with a focused review session.
31 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Ohm's Law
- For a linear conductor at constant temperature, V = IR. Power is P = VI = I²R = V²/R. In AC circuits use RMS values and multiply by cos φ for real power.
- Series and Parallel Resistance
- Series resistances add: R_total = R1 + R2 + … . For parallel, 1/R_total = 1/R1 + 1/R2 + … . Series current is common; parallel voltage is common.
- Three-Phase Power Formula
- Total three-phase power P = √3 × V_L × I_L × cos φ, where V_L and I_L are line values. In star, V_L = √3 V_ph; in delta, I_L = √3 I_ph.
- Faraday and Lenz Law
- Induced EMF e = −N dΦ/dt. Lenz's law states the induced current flows in a direction that opposes the change in flux producing it, explaining self-induction.
- Two-Way Switch Wiring
- Two 2-way switches with COM–L1–L2 terminals interconnected by two strapper wires control one lamp from two positions. An intermediate 4-terminal switch extends control to three or more positions.
- Voltage Drop in Cables
- Voltage drop = 2ρLI/A for single-phase two-wire circuits and √3ρLI/A for three-phase. IS 732 guidance keeps final sub-circuit drop within about 3% of supply voltage.
- Conduit Fill Rule
- The total cross-sectional area of all conductors in a conduit must not exceed 40% of the conduit internal area, allowing cables to be drawn without damage.
- Cable Core Colour Code
- Single-phase live is brown, neutral blue, protective earth green-yellow. Three-phase conductors are brown (L1), black (L2), grey (L3). Old wiring used red, black and green.
- Armoured Cable Construction
- Steel wire armour suits vertical runs; steel tape armour suits horizontal runs. Armour gives mechanical protection and an earth path but must be bonded and does not replace the earth conductor.
- Transformer EMF Equation
- E = 4.44 f N Φ_max, where f is frequency, N turns and Φ_max peak flux. The 4.44 factor arises from the sinusoidal waveform RMS value.
- Induction Motor Slip
- Slip s = (N_s − N)/N_s, where N_s = 120f/P. Rotor frequency equals s·f. At full load typical slip for a squirrel-cage motor is 2–5%.
- Star-Delta Starting
- The motor starts in star, reducing phase voltage to 1/√3, so starting current and torque fall to one-third. After a set time, the timer switches to delta for normal running.
- DC Motor Back EMF
- Back EMF E_b = V − I_aR_a. Armature current I_a = (V − E_b)/R_a. Speed N ∝ E_b/Φ, so field weakening raises speed above base speed.
- RCCB Function
- A residual current circuit breaker trips when the vector sum of live and neutral currents exceeds its sensitivity, typically 30 mA for personnel. It does not detect overload or line-to-neutral shock.
- MCB Trip Types
- Type B trips at 3–5 times rated current, Type C at 5–10 times, Type D at 10–20 times. The magnetic trip covers short circuits; the thermal element covers overload.
- DOL Starter Control Circuit
- The start push button energises the contactor coil; an auxiliary normally-open contact seals the circuit. The stop button and overload normally-closed contact are in series with the coil.
- Insulation Resistance Testing
- Measure with a 500 V DC megger for LV equipment. Minimum 1 MΩ for LV motors and 100 MΩ for new HV windings. Insulation resistance roughly halves for every 10 °C rise.
- Polarisation Index
- PI = R10 min / R1 min from insulation resistance readings. PI of 2 or more indicates healthy insulation; below 1.5 suggests moisture, dirt or degradation requiring investigation.
- Single Phasing Effects
- Loss of one supply phase leaves the motor running on two phases with severe current imbalance and overheating. A phase-failure relay or bimetal overload relay should trip the motor quickly.
- Variable Torque Load
- For centrifugal fans and pumps, torque is proportional to speed squared and power to speed cubed. Reducing speed by 20% cuts power to about 51%, giving large energy savings.
- Power Factor Correction
- Capacitor bank kVAR = P(tan φ1 − tan φ2) to raise power factor from cos φ1 to cos φ2. It reduces line current and losses; overcorrection causes leading power factor and voltage rise.
- VFD Operating Principle
- A rectifier converts AC to DC, a DC link capacitor smooths it, and an IGBT inverter produces PWM output of variable frequency and voltage. V/f is held constant below base speed.
- PLC Scan Cycle
- The PLC reads all inputs, executes the program logic, then updates all outputs. Scan time matters for fast processes; IEC 61131-3 defines ladder, function block and structured text languages.
- 4-20 mA Analogue Signal
- 4 mA represents the minimum value and 20 mA the maximum, with live zero allowing broken-wire detection. A reading below 4 mA indicates an open circuit or sensor fault.
- Earth Resistance Measurement
- The fall-of-potential method uses an earth tester with two auxiliary spikes. Substation earth resistance should be 1 Ω or less; domestic installations typically 5 Ω or less.
- Permit-To-Work System
- Isolate the supply, lock and tag the isolator, prove dead with a tester, discharge capacitors and earth the conductor. Only the person who applied the lock removes it.
- First Aid for Electric Shock
- Switch off the supply before touching the casualty. Use insulated material to separate them from the conductor, start CPR if breathing has stopped, and call medical help immediately.
- Diversity Factor
- Diversity factor = sum of individual maximum demands / maximum demand on the system. Demand factor = maximum demand / connected load. Both are used to size cables and protective devices.
- Earth Conductor Sizing
- For phase conductors up to 16 mm², the earth conductor equals the phase size. For 16–35 mm², use 16 mm². Above 35 mm², use half the phase conductor cross-section.
- Megger Use
- A megger applies DC test voltage to measure insulation resistance between conductors and earth. Always isolate and discharge the circuit before testing and reconnect earth afterwards.
- Star-Delta Motor Connection
- Six-terminal motors connect in star or delta according to the nameplate and supply voltage. Verify with a continuity test before energising; wrong connection causes overheating or failure to start.