- Ohm's law
- Current through a conductor is directly proportional to the voltage across it and inversely proportional to its resistance: I = V/R, valid for a constant-resistance element at constant temperature.
- Three-phase power formula
- For a balanced three-phase load, total active power equals √3 multiplied by line voltage, line current and power factor: P = √3 × V_L × I_L × cos φ.
- Insulation resistance test
- A DC test voltage, typically 500 V for low-voltage circuits, is applied between conductors and earth; a reading of at least one megohm indicates acceptable insulation.
- RCCB sensitivity
- A residual current circuit breaker rated at 30 mA sensitivity is used for personnel protection; it trips when earth leakage reaches that value within the specified time.
- Megger use precaution
- An insulation resistance tester must only be used on a de-energised, isolated circuit, and electronic equipment must be disconnected to avoid damage from the test voltage.
- Clamp meter limitation
- A clamp meter measures current from the magnetic field around one conductor; if line and neutral both pass through the jaw, the fields cancel and the reading is zero.
- Energy unit calculation
- One unit of electricity is one kilowatt-hour; energy in kWh equals power in kW multiplied by time in hours, so a 2 kW load for 3 hours uses 6 units.
- Fall-of-potential test
- Earth resistance is measured by driving auxiliary electrodes into the soil at specified spacings and passing current through them, then reading the potential difference.
- Two-way switch wiring
- Two strapper wires connect the two switches, with the live feed to the common of one switch and the switched line from the other to the lamp.
- Domestic sub-circuit rating
- A lighting sub-circuit uses a 5 A protective device with 1.0 to 1.5 square millimetre copper conductor; a power sub-circuit uses 15 to 16 A with 2.5 square millimetre.
- Voltage drop limit
- Cable size is chosen so that voltage drop from the origin to the load stays within the permitted percentage of supply voltage, commonly three to five percent.
- IP44 rating
- The first digit 4 means protection against solid objects larger than one millimetre; the second digit 4 means protection against splashing water from any direction.
- Transformer EMF equation
- The induced EMF in a winding equals 4.44 times frequency times turns times maximum flux, which explains why the volts-per-turn ratio is fixed by core area.
- Synchronous speed
- The speed of the rotating magnetic field in an induction motor is 120 times frequency divided by the number of poles, giving 1500 rpm at 50 Hz for four poles.
- Slip
- Slip is the difference between synchronous speed and actual rotor speed, expressed as a fraction of synchronous speed; it is typically two to five percent at full load.
- Back EMF
- In a DC motor the back EMF equals supply voltage minus the armature current multiplied by armature resistance, and it limits the current drawn by the motor.
- Holding contact
- A normally open auxiliary contact of the contactor, wired in parallel with the start push button, keeps the coil energised after the button is released.
- Thermal overload relay
- A device with a bimetallic element heated by motor current; it trips after sustained overload and is set to the motor full-load current from the nameplate.
- MCB type C
- A miniature circuit breaker with a C characteristic trips magnetically at five to ten times its rated current, suiting loads with moderate inrush such as small motors.
- Star-delta starting
- The motor starts with windings in star, reducing phase voltage and starting torque to one third, then switches to delta when the timer completes.
- Busbar short-circuit rating
- The rated short-time withstand current, quoted in kiloamperes for a stated duration such as one second, must exceed the prospective fault current at that point.
- Power factor correction
- Capacitor bank rating in kVAR equals active power multiplied by the difference between the tangents of the initial and target power factor angles.
- Selectivity
- Discrimination between protective devices means the device nearest the fault operates first, so that healthy parts of the installation remain supplied.
- Conduit fill rule
- The total cross-sectional area of conductors should not exceed about forty percent of the conduit internal area, allowing heat dissipation and easy drawing of cables.
- Earth fault location
- Insulation resistance is measured section by section with the circuit isolated and loads disconnected; the section showing a low reading contains the earth fault.
- Lockout tagout
- The supply is isolated, proved dead with a tester, earthed where required, and locked with a personal tag before work begins on a panel or machine.
- Open circuit symptom
- A break in a circuit shows full supply voltage across the break when measured with a voltmeter, while no current flows and the load does not operate.
- Single-line diagram
- A drawing that represents the distribution system with one line per circuit, showing the incoming supply, main switchgear, sub-boards and outgoing feeders.
- Bill of quantities
- A priced schedule listing each item with description, unit, quantity and rate; the total cost is the sum of quantity multiplied by rate for every item.
- Break-even quantity
- The number of units at which total revenue equals total cost, calculated as fixed cost divided by the difference between selling price and variable cost per unit.
- STAR interview method
- A structured answer describing the Situation, the Task required, the Action taken and the Result achieved, used to present practical experience clearly.
- Completion test sequence
- After visual inspection, the installer checks earth continuity, insulation resistance, polarity, residual current device trip time and finally the functional operation of every circuit.