- Ohm's law
- For a resistive circuit, voltage equals current multiplied by resistance (V = I × R). Power equals V × I, and can also be written as I²R or V²/R.
- Parallel circuit resistance
- Branches share the same voltage, and total resistance is found from the reciprocal sum of branch resistances. Total resistance is always lower than the smallest branch.
- Three-phase power formula
- For a balanced load, power equals √3 times line voltage times line current times power factor. Line voltage is √3 times phase voltage in a star connection.
- Power factor
- Cosine of the phase angle between voltage and current. A low value means higher current for the same real power, raising line loss and voltage drop.
- kWh unit
- One kilowatt-hour equals 3.6 million joules and is one billing unit. Energy consumed equals power in kilowatts multiplied by time in hours.
- Transmission voltage advantage
- Raising transmission voltage reduces current for the same power, so resistive line loss falls in proportion to the square of the voltage ratio.
- Radial distribution system
- A single supply path from source to consumer. It is the simplest and cheapest layout, but any feeder fault interrupts every downstream consumer.
- Ring main system
- The feeder loops back to the source so a section can be supplied from either end. Isolators at section ends allow fault isolation without full shutdown.
- Load factor
- Average load divided by maximum demand over a period. A high load factor means plant is used efficiently and fixed costs are spread over more units.
- ACSR conductor
- Aluminium conductor steel reinforced. Aluminium outer strands carry current while the central steel core provides tensile strength, allowing longer spans with less sag.
- Sag formula
- For level supports, sag equals weight per unit length times span squared, divided by eight times tension. Sag rises when tension falls or span increases.
- Pin insulator
- A single-piece insulator fixed on a pin or spigot, used on low and medium voltage lines. The conductor sits in a groove and is tied with binding wire.
- Creepage distance
- The shortest path along the insulator surface between phase and earth. It must be longer in polluted coastal or industrial areas to prevent surface flashover.
- Dyn11 vector group
- Delta-connected high voltage winding and star-connected low voltage winding with neutral brought out. Low voltage lags high voltage by 30 degrees.
- Transformer all-day efficiency
- Efficiency calculated over 24 hours, weighting iron loss for the whole period and copper loss only during loaded hours. It matters for distribution transformers with light night loads.
- Buchholz relay
- A gas-operated relay fitted in the pipe between transformer tank and conservator. It alarms on gas accumulation and trips on sudden oil surge from internal faults.
- Drop-out fuse
- A horn-gap expulsion fuse on the transformer pole. The fuse carrier drops open visibly after operation, giving clear isolation and easy replacement.
- Pole setting depth
- A common rule is to bury about one-sixth of the pole length, for example 1.5 metres of a 9 metre pole, with proper foundation and compacted backfill.
- Stringing rollers
- Pulley blocks suspended from supports that carry the conductor during pay-out. They prevent abrasion and allow the conductor to be pulled and tensioned freely.
- Stay wire
- A guy wire anchored in the ground to resist unbalanced pull at angle, termination, and section poles. It is set at roughly 45 degrees where space permits.
- Service connection
- The insulated cable and fittings linking the utility pole to the consumer's premises, including service bracket, protective fuse or MCB, and sealed energy meter.
- Heat-shrink joint insulation
- Tubing that shrinks on heating to wrap the joint tightly, restoring insulation and moisture sealing. Correct size and even heating are essential for a sound joint.
- Crimping versus twisting
- Compression crimping with the correct die and lug gives a low-resistance, mechanically sound joint. Twisting is not accepted for service or line connections.
- Energy meter constant
- The number of disc revolutions per kilowatt-hour, marked on the meter. It is used to calculate energy during accuracy testing against a known load.
- CT multiplier
- For current-transformer metering, actual energy equals meter reading multiplied by the CT ratio. A 200/5 CT gives a multiplier of forty.
- Sanctioned load
- The load in kilowatts or kVA approved by the utility for a consumer. It fixes the service cable, meter rating, and fixed charges.
- Earth resistance limit
- Substation earthing is kept near one ohm, while consumer installations commonly need about five to eight ohms, depending on the applicable standard.
- RCCB
- A residual current circuit breaker that trips when earth leakage current exceeds its setting, typically 30 milliamperes for personal protection. It does not sense overload.
- Prove-test-prove
- Safety sequence for proving dead: test the voltage detector on a known live source, test the isolated conductors, then test the detector again to confirm it works.
- Line clear permit
- A written authorisation issued after a line is isolated, locked, proved dead, and earthed. It is returned only when work is finished and the line is restored.
- Safety earths at work site
- Temporary earths applied on every side of the work towards any possible supply source. They are removed only after all personnel and tools are withdrawn.
- Insulation resistance test
- A megger applies DC voltage, commonly 500 volts for low voltage, to measure insulation resistance. A very low reading indicates moisture, damage, or contamination.