Maharashtra HSC Power Distribution Lineman (NSQF): Power Distribution System Overview: Generation, Transmission, Distribution

Maharashtra HSC Power Distribution Lineman (NSQF) · Work through your exam, one topic at a time.

All guide sections

Power Distribution System Overview: Generation, Transmission, Distribution

This domain checks whether you understand the overall power path and the vocabulary of distribution: generation voltage, transmission levels, primary and secondary distribution, substations, feeders, distributors and service mains. Questions often test where a component sits in the chain and why a particular voltage level is used.

Core rules

  • Generation is produced at moderate voltage, stepped up for transmission to reduce current and I²R loss, then stepped down in stages.
  • In India, transmission is commonly 132 kV, 220 kV or 400 kV; sub-transmission and primary distribution use 66 kV, 33 kV or 11 kV; secondary distribution is 415 V three-phase, 240 V single-phase.
  • A distribution substation typically has an 11 kV incoming feeder and an 11/0.433 kV distribution transformer. The transformer no-load secondary is about 433 V so that consumers receive near 415 V at load.
  • A feeder carries power from the substation to a distribution transformer or load point and should not be tapped along its length. A distributor is tapped to serve consumers. A service main connects the distributor to the consumer's installation.
  • Radial distribution is simple and cheap but has poor reliability; ring and interconnected systems improve continuity but need more switching and protection.

Worked example

A 400 kVA, 11 kV/433 V distribution transformer is fully loaded. Find the HV and LV line currents.

HV current = 400000 / (√3 × 11000) = 400000 / 19052 ≈ 21.0 A. LV current = 400000 / (√3 × 433) = 400000 / 750 ≈ 533 A. The HV current sets the HV fuse and cable requirement; the LV current sets the LV breaker, busbar and outgoing distributor capacity. The calculation uses line voltage and line current because the transformer is rated in three-phase kVA.

Traps that cost marks

  • Confusing a feeder with a distributor; feeders are not meant for consumer tappings.
  • Using 415 V instead of the transformer's 433 V secondary when calculating full-load LV current.
  • Forgetting that transmission is stepped up to reduce current, not to increase power.
  • Treating a ring system as automatically more reliable without correct switching and protection.