Maharashtra HSC Electrical Technology (Vocational) study materials
Maharashtra HSC Electrical Technology (Vocational) study resources

Maharashtra HSC Electrical Technology (Vocational) cheat sheet

Maharashtra HSC Electrical Technology (Vocational) · Keep the key ideas within reach.

Quick reference

Basic Electrical Concepts and Fundamentals

  • Ohm's law: V = I × R; power P = V × I = I²R = V²/R. In a purely resistive circuit current and voltage stay in phase.

  • Series circuit: same current through all elements, R_total = R1 + R2 + …; voltage divides in proportion to resistance.

  • Parallel circuit: same voltage across all branches, 1/R_total = 1/R1 + 1/R2 + …; current divides inversely with resistance.

  • Kirchhoff's current law: algebraic sum of currents at a node is zero (sum in = sum out). Kirchhoff's voltage law: algebraic sum of EMFs and drops around a closed loop is zero.

  • AC quantities: RMS = peak/√2 for a sine wave; average over a full cycle is zero; form factor = RMS/average = 1.11 for a sine wave.

  • Frequency f = 1/T and angular frequency ω = 2πf. In India the supply is 230 V single-phase, 50 Hz.

  • Inductive reactance X_L = 2πfL; capacitive reactance X_C = 1/(2πfC); impedance Z = √(R² + (X_L − X_C)²).

  • Resistance rises with temperature for metals (positive temperature coefficient); resistivity ρ = RA/L, so R = ρL/A.

  • Power factor = cos φ = R/Z; real power P = VI cos φ, reactive power Q = VI sin φ, apparent power S = VI in VA.

Quick reference

Electrical Materials and Wiring

  • Copper has resistivity about 1.72 × 10⁻⁸ Ω·m; aluminium about 2.83 × 10⁻⁸ Ω·m. Aluminium is lighter and cheaper but needs about 1.6 times the copper area for equal resistance.

  • Conductors: copper, aluminium, silver (best conductivity). Insulators: PVC, rubber, porcelain, bakelite, mica.

  • PVC insulation is rated typically 70 °C continuous; XLPE and butyl rubber allow higher conductor temperatures, so they carry more current for the same size.

  • Fuse wire is made of tinned copper or an alloy with a low melting point; it must be rated slightly above the circuit's normal current but below the cable's current capacity.

  • Wiring systems: cleat, casing-and-capping, batten, conduit (surface or concealed), and cable tray. Concealed conduit is preferred in masonry buildings for mechanical protection.

  • Standard Indian conductor sizes (mm²): 1, 1.5, 2.5, 4, 6, 10, 16, 25, 35, 50, 70, 95. Lighting sub-circuits usually use 1.5 mm²; power sockets 2.5 mm² or larger.

  • A single-phase circuit is normally limited to about 800 W per sub-circuit for lighting; a 15 A power circuit may feed one or two socket outlets.

  • Bending radius of a conduit should be at least about 6 times its outer diameter; conduit fill should not exceed roughly 40 % of the internal area.

  • Cable colour convention (Indian practice): red/yellow/blue for three phases, black for neutral, green for earth.

Quick reference

Electrical Machines and Transformers

  • Transformer EMF equation: E = 4.44 f N Φ_m, where Φ_m is the peak flux. Voltage per turn is the same on both windings, so V1/V2 = N1/N2 = I2/I1.

  • A transformer works only on AC. Core loss (hysteresis + eddy current) is nearly constant at fixed voltage and frequency; copper loss varies as I².

  • Efficiency is maximum when copper loss equals core loss. For a distribution transformer, all-day efficiency weights losses over 24 hours and favours low core loss.

  • DC motor: back EMF E_b = V − I_a R_a; torque T ∝ Φ I_a; speed N ∝ (V − I_a R_a)/Φ. Series motors give high starting torque; shunt motors give nearly constant speed.

  • Induction motor synchronous speed N_s = 120f/P; slip s = (N_s − N)/N_s, typically 2–5 % at full load. It is a singly-fed machine and needs no commutator.

  • Starting methods for squirrel-cage induction motors: direct-on-line (small motors), star-delta (starting current reduced to one-third), autotransformer, and rotor-resistance starting for slip-ring motors.

  • A capacitor-start single-phase induction motor uses a capacitor in the auxiliary winding to create phase displacement and a rotating field.

  • Alternator frequency f = PN/120, where N is rpm and P is the number of poles.

  • Motor protection: overload relay against sustained overcurrent, no-volt release to prevent restart after supply failure, and single-phasing protection for three-phase motors.

Quick reference

Electrical Measurements and Instruments

  • Ammeter is connected in series and should have very low resistance; voltmeter is in parallel and should have very high resistance.

  • A galvanometer is converted to an ammeter by a low shunt resistance in parallel: I/I_g = 1 + G/R_sh. It becomes a voltmeter by a high series resistance: V = I_g(G + R_se).

  • PMMC instruments measure DC only and deflect linearly; moving-iron instruments work on both AC and DC but have non-linear, compressed scales.

  • Dynamometer-type instruments serve as wattmeters and transfer instruments because deflection depends on the product of two coil currents.

  • Induction-type energy meter: the disc speed is proportional to power; the meter constant is revolutions per kWh. Registration error is checked with a standard load and stopwatch.

  • Wheatstone bridge measures medium resistance; Kelvin double bridge measures very low resistance; megohmmeter (insulation tester) measures insulation resistance in MΩ.

  • Instrument transformers: a current transformer steps current down for measurement (secondary usually 5 A or 1 A); a potential transformer steps voltage down (secondary usually 110 V).

  • Errors: loading error from instrument resistance, temperature error, friction, and stray magnetic field. Ayrton shunt extends ammeter range without changing damping.

  • Digital multimeters have high input impedance (typically 10 MΩ), so they load low-power circuits less than analog moving-coil meters.

Quick reference

Power Systems and Distribution

  • Typical Indian transmission voltages: 66, 110, 132, 220, 400 kV AC; distribution at 11 kV, then 415 V three-phase four-wire for consumers.

  • Transmission at high voltage reduces current for the same power, so I²R line loss and conductor cross-section fall; this is why power is stepped up for long distances.

  • Supply system: generation, transmission, primary distribution (11 kV), secondary distribution (415/230 V), and consumer service connection.

  • A distribution transformer steps 11 kV down to 415 V three-phase, giving 240 V phase-to-neutral (commonly quoted as 230 V).

  • Radial distribution is simple and cheap but has poor reliability; ring main gives two paths and better continuity; interconnected systems improve reliability further.

  • Voltage drop in a feeder ≈ I × R cos φ + I × X sin φ. Permissible voltage variation at the consumer terminal is generally within ±6 % under Indian regulations.

  • Power factor improvement uses shunt capacitors; a capacitor bank reduces reactive demand and line current without changing active power.

  • A transmission line's surge impedance is √(L/C); surge impedance loading indicates the natural power limit of the line.

  • Earthing of the neutral at the transformer star point provides a return path and limits touch voltage during a fault.

Quick reference

Electrical Installation and Maintenance

  • Before any installation work, isolate the supply, prove dead with a tester, and lock off or tag the isolating device.

  • Lighting sub-circuit wiring: phase through the switch, neutral to the lamp. Switches must always be in the phase conductor, never in neutral.

  • Earthing conductor size is generally half the phase conductor for small cables, with a minimum of 1.5 mm² for lighting circuits.

  • Insulation resistance test: apply 500 V DC with a megohmmeter between conductors and earth; a new domestic installation should read at least 1 MΩ.

  • Continuity and polarity tests confirm correct connections; earth electrode resistance is measured with an earth tester and should be low enough to clear faults quickly.

  • Motor maintenance: check bearing temperature and lubrication, terminal tightness, insulation resistance, cooling fan and air filters, and vibration.

  • Common motor faults: single phasing (motor hums and heats), overload, earth fault, shorted winding, and bearing failure.

  • A starter's thermal overload relay must be set to the motor's full-load current, not to the supply fuse rating.

  • Preventive maintenance schedule items: tightening terminals, cleaning dust from windings, checking contactor contacts, and recording insulation resistance trends.

Quick reference

Electrical Safety

  • Electric shock severity depends on current magnitude, path through the body, and duration. About 30 mA through the body can cause breathing difficulty; 50 mA or more can be fatal.

  • Body resistance falls sharply when skin is wet, so the same voltage becomes far more dangerous in wet conditions.

  • First aid for electric shock: switch off or separate the victim using dry insulating material, then call for help and begin CPR if breathing has stopped.

  • Earthing protects by providing a low-resistance path so protective devices operate quickly and touch voltage stays low.

  • Types of earthing: pipe earthing (galvanised iron pipe in a coke-and-salt bed) and plate earthing (copper or GI plate buried below ground).

  • An ELCB/RCCB with 30 mA sensitivity protects people against earth leakage; an MCB protects cables against overload and short circuit but not against small leakage currents.

  • Fire classes: Class C is for electrical fires. Use dry powder or CO₂ extinguishers; never water on live electrical equipment.

  • Safe isolation sequence: identify circuit, switch off, lock and tag, test for dead on all conductors, then work.

  • PPE for electrical work: insulated gloves, safety shoes, helmet, and insulated tools rated for the working voltage.

Quick reference

Electrical Codes and Standards

  • The National Electrical Code of India (NEC 2011) is published by the Bureau of Indian Standards as SP 30 and covers wiring installations.

  • IS 732 covers the code of practice for electrical wiring installations; IS 3043 covers earthing; IS 694 covers PVC-insulated cables up to 1100 V.

  • IS 732 requires that every installation have a main switch and that circuits be protected against overload and short circuit by fuses or circuit breakers.

  • Indian Electricity Rules 1956 (now the Central Electricity Authority Regulations) set the supply voltage limits and the requirement for an earth connection at every consumer terminal.

  • Standard supply voltages: 230 V single-phase and 400/415 V three-phase, 50 Hz, with permissible variation of about ±6 % (declared in the supply code).

  • IS 12640 covers residual current operated circuit breakers; 30 mA is the standard sensitivity for personnel protection.

  • Colour code for three-phase wiring per Indian practice: red, yellow, blue for phases; black for neutral; green for protective earth.

  • An MCB's rated breaking capacity (kA) must be at least the prospective short-circuit current at its point of installation.

  • Cable current ratings must be derated for ambient temperature and grouping; IS 3961 gives the current ratings for aluminium and copper conductors.

Quick reference

Electrical Drawing and Estimation

  • Standard electrical symbols: a circle with a cross for a lamp, a switch shown as a break in the line, an earth symbol of three decreasing horizontal lines.

  • Single-line diagram shows the distribution from the supply point through main switch, distribution board, and sub-circuits; each circuit is one line.

  • Wiring diagram shows actual connections of switches, lamps, and sockets; a circuit diagram shows the electrical relationship only.

  • Estimation steps: take off quantities from the drawing, apply wastage allowance, price the materials, then add labour and overheads.

  • Typical wastage allowances: about 5 % for cable and wire, 3–5 % for conduit accessories, and 2 % for switches.

  • Conduit length is measured along the run plus fittings; the number of bends and junction boxes must be counted separately.

  • Lighting circuit load is calculated by summing lamp wattages and dividing by 230 V to get current, then selecting cable size and protective device.

  • Bill of quantities should list item description, unit (metre, number, point), quantity, rate, and amount, and be signed by the estimator.

  • A layout drawing locates fittings and switches on the floor plan and shows the point wiring route between them.

Quick reference

Basic Electronics and Control

  • Diode: conducts when forward biased above about 0.7 V for silicon (0.3 V for germanium); blocks in reverse up to its peak inverse voltage.

  • Rectifiers: half-wave gives one pulse per cycle, full-wave gives two; a bridge rectifier needs four diodes and no centre tap. Ripple frequency is 50 Hz for half-wave and 100 Hz for full-wave on a 50 Hz supply.

  • A Zener diode works in reverse breakdown to give a stable reference voltage; it is used with a series resistor.

  • BJT: I_C = β I_B; the base-emitter junction is forward biased for active operation. A small base current controls a larger collector current.

  • SCR (thyristor) latches on when the gate receives a pulse and the anode is positive; it turns off only when the anode current falls below the holding current.

  • A TRIAC controls AC power in both half cycles and is used in lamp dimmers and fan regulators.

  • A relay is an electromagnetic switch: coil voltage energises it and contacts switch the load. A flyback diode across the coil suppresses the inductive spike.

  • A contactor is a heavy-duty relay with main contacts and an auxiliary contact used for latching in motor starters.

  • Logic basics: AND gives output 1 only when all inputs are 1; OR gives 1 when any input is 1; NOT inverts. A NAND gate is a universal gate.

Quick reference

Practical Skills and Workshop Practice

  • Wire stripping: remove insulation to the required length without nicking the conductor; use a wire stripper matched to the gauge.

  • Straight-through joints are made by twisting conductors and soldering, then insulating with tape; a Britannia joint is used for overhead conductors.

  • Crimping is preferred over soldering for terminals: select the correct lug size, insert fully, and crimp with the proper die.

  • Continuity test: use a multimeter on the resistance range; a reading near zero ohms confirms a sound connection.

  • Insulation resistance test at 500 V DC between phase and earth must read at least 1 MΩ before energising a new circuit.

  • When using a megger, disconnect sensitive equipment and confirm the circuit is dead and isolated before applying the test voltage.

  • Bench practice: keep the work area dry, use insulated tools, and never work on a live circuit during workshop exercises.

  • Soldering: heat the joint, apply solder to the joint not the iron, and let it cool without movement to get a shiny joint.

  • Cable gland and termination: strip the outer sheath to the gland length, fit the gland and shroud, and ensure the earth continuity conductor is connected.