Maharashtra HSC Electrical Technology (Vocational) study materials
Maharashtra HSC Electrical Technology (Vocational) study resources

Maharashtra HSC Electrical Technology (Vocational): Electrical Materials and Wiring

Maharashtra HSC Electrical Technology (Vocational) · Work through your exam, one topic at a time.

All guide sections

Electrical Materials and Wiring

Electrical Materials and Wiring tests conductor and insulation selection, wiring system choice, colour code and conduit practice for domestic and workshop installations.

Core rules

  • Copper resistivity is about 0.0175 Ω·mm²/m; aluminium is about 0.028 Ω·mm²/m, so aluminium needs a larger area for the same voltage drop.
  • PVC insulation is rated about 70 °C, XLPE about 90 °C; derate cables for ambient temperature, grouping and enclosure.
  • Common wiring systems: cleat, casing-and-capping, batten, conduit (surface or concealed) and cable tray. Concealed conduit must run in straight lines, with inspection boxes at bends.
  • IS 732 colour code for three-phase: red, yellow and blue for phases; black for neutral; green-with-yellow for protective earth. Older installations may use different phase colours, so test before working.
  • Conduit fill should not exceed about 40% of the internal area; wires must be drawn without damage.

Worked example

A 16 A load is 18 m from the distribution board, wired in 2.5 mm² copper, two wires. Resistance per conductor = 0.0175 × 18 / 2.5 = 0.126 Ω. Loop resistance = 0.252 Ω. Voltage drop = 16 × 0.252 = 4.03 V, which is 1.75% of 230 V. If the same load used 2.5 mm² aluminium, drop = 16 × 2 × 0.028 × 18 / 2.5 = 6.45 V (2.8%), so a 4 mm² aluminium conductor would be selected to keep drop near 2%.

Traps

The most common error is using one-way length; the current goes out and back. Do not mix mm² with wire gauge, and do not assume the earth wire can be smaller on a 2.5 mm² circuit: for phase conductors up to 16 mm², the protective conductor is normally the same size.