Maharashtra SSC Power Consumer Energy Meter Pre-Voc/NSQF: Wiring and Connection Practices

Maharashtra SSC Power Consumer Energy Meter Pre-Voc/NSQF · Work through your exam, one topic at a time.

All guide sections

Wiring and Connection Practices

Domain 6: Wiring and Connection Practices

This domain tests correct meter wiring for single-phase and three-phase services, CT connections and safe isolation.

Core rules

  • Single-phase: supply phase to line-in, supply neutral to neutral-in; load phase and neutral from load-out terminals. Polarity must not be reversed.
  • Three-phase: connect R, Y, B and neutral in sequence; confirm phase sequence and voltages of about 415 V between phases and 230 V phase-to-neutral.
  • For CT-operated meters, CT secondary leads go to meter current terminals; use shorting links before removing the meter. Never open a live CT secondary.
  • Use correct cable size, ferrules, crimped lugs and torque; keep CT burden within the meter rating.
  • Test continuity and insulation before energizing.

Worked example

A CT-operated meter reads 10 kWh on a 200/5 CT. The CT ratio is 40, so primary energy is 10 × 40 = 400 kWh. If a PT ratio of 100 is also present, primary energy is 400 × 100 = 40,000 kWh. Reasoning: the meter registers secondary quantities; both ratios multiply the register.

Traps that cost marks

  • Opening a CT secondary under load, which creates dangerous high voltage.
  • Reversing CT polarity.
  • Connecting load to supply terminals.
  • Sharing a neutral with another consumer.
  • Ignoring the PT ratio.