Maharashtra SSC Power Consumer Energy Meter Pre-Voc/NSQF: Fault Finding and Repair

Maharashtra SSC Power Consumer Energy Meter Pre-Voc/NSQF · Work through your exam, one topic at a time.

All guide sections

Fault Finding and Repair

Domain 10: Fault Finding and Repair

This domain tests systematic diagnosis of common meter and connection faults.

Core rules

  • Complaint categories include no display, no registration, fast or slow running, reverse running, burnt terminal and communication failure.
  • First isolate and prove dead; check supply voltage, neutral, load current and terminal tightness.
  • No registration with load present: check meter connections, programming, display register and load current.
  • Fast meter: check CT ratio, PT ratio, wiring, calibration and any bypass.
  • Reverse running: check CT polarity, phase sequence and import/export configuration.

Worked example

A consumer says the meter advances with all loads switched off. Isolate, confirm no current in the load circuit and observe. If registration continues, suspect creep, a wiring bypass or a live neutral return. Test with a known load and compare pulses; if the meter is faulty, replace it and record the evidence. Reasoning: separate load-present conditions from meter defect before condemning the meter.

Traps that cost marks

  • Replacing a meter without testing the load circuit.
  • Ignoring a neutral bypass.
  • Resetting a meter without authorization.
  • Failing to record the seal and final reading.
  • Treating a communication fault as an energy-measurement fault.